Sec. 22-135. - Installation requirements for certain institutions.
(a) Direct refrigerating systems shall not be placed in wards, private and operating rooms of hospitals or asylums; cell blocks of prisons; homes for infants, aged, or infirm; or any building where people are confined or are helpless, except class E unit systems containing a nonirritant and nonflammable refrigerant. Refrigerating systems installed in any such rooms or buildings shall be subject to the subsection of this section dealing therewith. (b) Direct systems wholly confined to a kitchen or laboratory may be installed in institutional occupancies; provided, however, that the system does not contain more than 20 pounds of a nonirritant and nonflammable refrigerant. Such kitchen or laboratory shall be equipped with tightfitting self-closing doors and shall have natural or mechanical means of ventilation to the outside. (c) Indirect systems containing not more than 2,000 pounds of a class 1 nonirritant and nonflammable refrigerant may be installed in institutional occupancies; provided, however, that all refrigerant-containing equipment is placed in a machinery room located on the first floor or in a basement. Such machinery room shall have tightfitting self-closing doors and shall be provided with natural or mechanical means of ventilation. (d) Indirect systems operating above atmospheric pressure containing not more than 350 pounds of a class 2 nonirritant and nonflammable refrigerant may be installed in institutional occupancies; provided, however, that all refrigerant-containing parts are placed in a machinery room located on the first floor or in a basement as provided in subsection (c) of this section. (e) Indirect systems operating below atmospheric pressure containing not more than 2,000 pounds of class 2 nonirritant and nonflammable refrigerant may be installed in institutional occupancies; provided, however, that all refrigerant-containing equipment is placed in a machinery room located on the first floor or in a basement as provided in subsection (c) of this section. (f) Indirect systems containing 100 pounds or less of class 1 or class 2 nonirritant and nonflammable refrigerant may be installed on the roof or in a penthouse; provided, however, that all refrigerant-containing parts are placed in a machinery room having tightfitting self-closing doors and provided with natural or mechanical means of ventilation.
(Ord. of 7-19-1948, §§ 9—14; Code 1958, § 28-9)
Ask a question about Cicero law
Corpus searches the Cicero sections it holds and shows the ones that match, with their citations. Free, no sign-in.