§ 5-713 — National Electrical Code—Section 230.28 amended
Code of Ordinances of the City of Lawrence, Kansas (Codified through Ordinance No. 10209, enacted April 14, 2026 (Supp. No. 4)) · Lawrence Code of Ordinances § 5-713
Corpus is an independent public-information project, not the official City of Lawrence website. Stable reference: corpuslaw.us/code/60377a70-cd05-44cb-86aa-37b8088e4d1d
Sec. 5-713. - National Electrical Code—Section 230.28 amended.
Section 230.28 of the NPFA 70, National Electrical Code, 2017 edition, is hereby amended to read as follows: 230.28 Service masts as supports. Where a service mast is used for the support of service-drop conductors, it shall be a galvanized rigid conduit with a minimum trade size diameter of two inches. Where the service mast projects above the roof surface in excess of three feet, the mast shall be supported by braces or guys to withstand safely the strain imposed by the service-drop. Where raceway-type service masts are used, all raceway fittings shall be identified for use with the service masts. Only power service-drop conductors shall be permitted to be attached to a service mast.
(Code 2018, § 5-413)