24.12.285 Section 608.5 Amended; Discharge Piping.
Section 608.5 of the Uniform Plumbing Code is amended to read as follows: 608.5 Discharge Piping. Relief valves located inside a building shall be provided with a drain, not smaller than the relief valve outlet, of galvanized steel, hard drawn copper piping and fittings, or listed relief valve drain tube with fittings which will not reduce the internal bore of the pipe or tubing (straight lengths as opposed to coils) and shall extend from the valve to the outside of the building with the end of the pipe not more than six (6) inches above the ground or the flood level of the area receiving the discharge and pointing downward. Such drains may terminate at other approved locations. No part of such drain pipe shall be trapped or subject to freezing. The terminal end of the drain pipe shall not be threaded. (: Ord. 20525 §56, August 21, 2017).
(Ord. 21817 §28; December 15, 2025)