§ 25.06.325 — Section 304.11 Amended; Guards

Lincoln, Nebraska Municipal Code (enCodePlus online edition as published 2026-11-08 (history notes seen through Ord. 21775, Sept. 15, 2025)) · Lincoln Municipal Code § 25.06.325

Corpus is an independent public-information project, not the official City of Lincoln website. Stable reference: corpuslaw.us/code/ad7516f7-2a05-409b-bed9-2b673287b2f3

25.06.325 Section 304.11 Amended; Guards.

304.11 Guards. Guards shall be provided where appliances, equipment, fans, or other components that require service and roof hatch openings are located within 10 feet (3048mm) of a roof edge or open side of a walking surface and such edge or open side is located more than 30 inches (762mm) above the floor, roof, or grade below. The guard shall extend not less than 30 inches (762mm) beyond each end of such appliances, equipment, fans, components, and roof hatch openings and the top of the guard shall be located not less than 42 inches (1067 mm) above the elevated surface adjacent to the guard. The guard shall be constructed so as to prevent the passage of a 21-inch-diameter (533mm) sphere and shall comply with the loading requirements for guards specified in the International Building Code. Exception: When condensing units are replaced the distance to the roof edge may be reduced to 5 feet from closest point of equipment if control side and refrigerant access ports are located on the side of equipment furthest from roof edge.

(Ord. 20526 §34, August 21, 2017)

Ask a question about Lincoln law

Corpus searches the Lincoln sections it holds and shows the ones that match, with their citations. Free, no sign-in.