25.06.370 Section 506.3.4 Amended; Air Velocity.
Section 506.3.4 of the International Mechanical Code is amended to read as follows: 506.3.4 Air velocity. Grease duct systems serving a Type I hood shall be designed and installed to provide an air velocity within the duct system of not less than 1,500 feet per minute and not to exceed 2,500 feet per minute. Ducts for Type II hoods that collect and remove steam, vapors, heat, and odors shall have a minimum velocity of 1,000 feet per minute. Exception: The velocity limitations shall not apply within duct transitions utilized to connect ducts to differently sized or shaped openings in hoods and fans, provided that such transitions do not exceed three feet in length and are designed to prevent the trapping of grease. Air velocity may be lowered, but not less than 500 fpm, where a registered design professional can demonstrate that grease will not collect in the grease ducts. (: Ord. 20526 §47, August 21, 2017).
(Ord. 21815 §34; December 15, 2025)