25.06.422 Section 601.4 Amended; Contamination Prevention.
Section 601.4 of the International Mechanical Code is amended to read as follows: Exhaust ducts under positive pressure, chimneys, and vents shall not extend into or pass through ducts or plenums. Exceptions: (1) Exhaust systems located in ceiling return air plenums over spaces that are permitted to have 10 percent recirculation in accordance with Section 403.2.1, Item 4. The exhaust duct joints, seams, and connections shall comply with Section 603.9. (2) This section shall not apply to chimneys and vents that pass through plenums where such venting systems comply with one of the following requirements: 2.1 The venting system shall be listed for positive pressure applications and shall be sealed in accordance with the vent manufacturer’s instructions. No joints may be in the return air space even if covered with insulation material. 2.2 The venting system shall be installed such that fittings and joints between sections are not installed in the above ceiling space. 2.3 The venting system shall be installed in a conduit or enclosure with sealed joints separating the interior of the conduit or enclosure from the ceiling space.
(Ord. 20526 §59, August 21, 2017)
Ask a question about Lincoln law
Corpus searches the Lincoln sections it holds and shows the ones that match, with their citations. Free, no sign-in.