§ 25.06.445 — Section 606.4.1 Amended; Supervision
Lincoln, Nebraska Municipal Code (enCodePlus online edition as published 2026-11-08 (history notes seen through Ord. 21775, Sept. 15, 2025)) · Lincoln Municipal Code § 25.06.445
Corpus is an independent public-information project, not the official City of Lincoln website. Stable reference: corpuslaw.us/code/672869fe-2577-4b42-923d-31a6c95e3f38
25.06.445 Section 606.4.1 Amended; Supervision.
Section 606.4.1 of the International Mechanical Code is hereby amended to read as follows: 606.4.1. The duct smoke detectors shall be connected to a fire alarm system where a fire alarm system is required by Section 907.2 of the International Fire Code. The actuation of a duct smoke detector shall activate a visible and audible supervisory signal at a constantly attended location. Exceptions: (1) The supervisory signal at a constantly attended location is not required where the duct smoke detector activates the building's alarm-indicating appliances. (2) In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and audible signal in an approved location. Duct smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble. (3) On existing installations with common supply and/or return systems, the required audio/visual notification need only be installed on the units being replaced.
(Ord. 20526 §65, August 21, 2017)
Ask a question about Lincoln law
Corpus searches the Lincoln sections it holds and shows the ones that match, with their citations. Free, no sign-in.
