25.06.454 Section 607.6.2 Amended; Membrane Penetrations.
Section 607.6.2 of the International Mechanical Code is amended to read as follows: Ducts and air transfer openings constructed of approved materials, in accordance with Section 603, that penetrate the ceiling membrane of a fire-resistance-related floor/ceiling or roof/ceiling assembly shall be protected with one of the following: (1) 1. A shaft enclosure in accordance with Section 713 of the International Building Code. (2) 2. A listed ceiling radiation damper installed at the ceiling line where a duct penetrates the ceiling of a fire-resistance-rated floor/ceiling or roof/ceiling assembly. (3) 3. A listed ceiling radiation damper installed at the ceiling line where a diffuser with no duct attached penetrates the ceiling of a fire-resistance-rated floor/ceiling or roof/ceiling assembly. (4) 4. A dryer vent of 26 gauge galvanized metal may penetrate a fire-resistance-rated roof ceiling assembly. A dryer vent of 26 gauge galvanized metal may penetrate a fire-resistance-rated floor ceiling assembly if draped with unfaced R-19 fiberglass insulation. (: Ord. 20526 §66, August 21, 2017).
(Ord. 21815 §46; December 15, 2025)