25.06.400 Section 507.6 Amended; Commercial Kitchen Hoods; Performance Test.

Section 507.6 of the International Mechanical Code is amended to read as follows: 507.6 Performance test. A performance test shall be conducted upon completion and before final approval of the installation of a ventilation system serving commercial cooking appliances. The test shall verify the rate of exhaust airflow required by Section 507.5, makeup airflow required by Section 508, and proper operation as specified in this chapter. The permit holder shall furnish the necessary test equipment and devices required to perform the tests. For Type I hoods an air balance report shall be submitted by a NEPB, AABC, NCI, or equivalent Certified Air Balancer. (: Ord. 20526 §55, August 21, 2017).

(Ord. 21815 §38; December 15, 2025; Ord. 21113 §28; August 23, 2021)