25.06.387 Section 507.2.6 Amended; Clearances for Type I hood.
Section 507.2.6 of the International Mechanical Code is hereby amended to read as follows: A Type I hood shall be installed with a clearance to combustibles of not less than 18 inches (457mm). Exceptions: (1) Clearance shall not be required from gypsum wallboard or ½-inch (12.7 mm) or thicker cementitious wallboard attached to noncombustible structures provided that a smooth, cleanable, nonabsorbent, and noncombustible material is installed between the hood and the gypsum or cementitious wallboard over an area extending not less than 18 inches (457 mm) in all directions from the hood. Hoods having a 3 inch stand off and attached to such wall may be less than 18 inches from combustibles on opposite side of such wall providing that minimum ½ inch new gypsum or cementitious wallboard is installed on both sides of the non-combustible structure. (2) Type I hoods listed and labeled for clearance less than 18 inches in accordance with UL 710 shall be installed with the clearances specified by such listings. (: Ord. 20526 §53, August 21, 2017).
(Ord. 21113 §26; August 23, 2021)