For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 25.06.447 — Section 607.4.1 Amended; Access

Lincoln, Nebraska Municipal Code (enCodePlus online edition as published 2026-11-08 (history notes seen through Ord. 21775, Sept. 15, 2025)) · Lincoln Municipal Code § 25.06.447

Corpus is an independent public-information project, not the official City of Lincoln website. Stable reference: corpuslaw.us/code/9b747010-47d3-4f4a-b433-9af073f9f203

25.06.447 Section 607.4.1 Amended; Access.

Section 607.4.1 of the International Mechanical Code is amended to read as follows: 607.4.1 Access. Fire and smoke dampers shall be provided with an approved means of access that is large enough to permit inspection and maintenance of the damper and its operating parts. Dampers equipped with fusible links, internal operators or both shall be provided with an access door that is not less than 8 inches (305 mm) square or provided with a removable duct section. ().

(Ord. 21815 §45; December 15, 2025)

Ask a question about Lincoln law

Corpus searches the Lincoln sections it holds and shows the ones that match, with their citations. Free, no sign-in.