§ 3-905.10 — System design
Code of the City of Harrisburg, Pennsylvania · Harrisburg Code § 3-905.10
Corpus is an independent public-information project, not the official City of Harrisburg website. Stable reference: corpuslaw.us/code/4779344a-18b0-4379-88f9-f54cb14023da
§ 3-905.10: System design.
A. The system shall provide a discharge of not less than 18 gallons per minute to any single operating sprinkler and not less than 13 gallons per minute to the number of design sprinklers. If the design discharge area is to be increased, the gallonage per sprinkler shall meet the criteria as outlined in each manufacturer's specification sheet. B. The number of design sprinklers shall include all sprinklers within a compartment to a maximum of four sprinklers. Calculations must be provided to show the sprinkler flow at the highest elevation and the most hydraulically remote sprinkler water supply within the building as follows: (1) For rooms or areas with no more than one or two sprinklers, calculate to flow one or two sprinklers. (2) For rooms or areas with three sprinklers, calculate to flow three sprinklers. (3) For rooms or areas with four or more sprinklers, calculate to flow four sprinklers. C. In determining the number of design sprinklers, a compartment is a space which is completely enclosed by walls and a ceiling. The compartment enclosure may have openings to an adjoining space, if the openings have a minimum lintel depth of eight inches from the ceiling.