§ 3-905.13: System types.
A. Dropped escutcheons shall be used if sprinklers are obstructed by light fixtures or beams. The installer may use additional sprinklers for areas where obstructions block spray pattern. B. When ceiling fans are used, sprinklers shall be located so that the fan blade does not interfere with the spray pattern. Relocation of sprinklers shall still conform to spacing requirements. Rooms exceeding nine feet by nine feet with ceiling fans shall have a minimum of two sprinklers. C. Wet pipe systems shall be used when all piping is installed in all areas not subject to freezing. No antifreeze solution or any other type of additive shall be allowed in any combination sprinkler system. D. A dry pipe system shall be used where system piping is located in unheated areas subject to freezing. Only copper tubing with brazed fittings and steel tubing shall be used in dry pipe systems.