§ 3-905.3 — System design and installation

Code of the City of Harrisburg, Pennsylvania · Harrisburg Code § 3-905.3

Corpus is an independent public-information project, not the official City of Harrisburg website. Stable reference: corpuslaw.us/code/86f6838e-b266-4ed3-a069-777eeb7bed81

§ 3-905.3: System design and installation.

A. All sprinklers shall be listed by Underwriters' Laboratories, Inc., fast response for residential use. B. Only listed and approved Factory Mutual or Underwriters' Laboratories, Inc., materials shall be used in sprinkler systems. C. Approved listing may be waived for tanks, pumps, hangars, water flow detection devices, water flow valves, check valves, and gauges. D. All systems shall be tested for leakage as follows: (1) Tested hydrostatically prior to sprinkler head and dry wall installation in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems, if Fire Bureau connection is required. (2) Tested for leakage at normal operating pressure prior to dry wall installation, if not required to be hydrostatically tested. (3) Tested for leakage at normal operating water pressure after sprinkler head installation.