§ 3-905.15 — Locations of sprinklers

Code of the City of Harrisburg, Pennsylvania · Harrisburg Code § 3-905.15

Corpus is an independent public-information project, not the official City of Harrisburg website. Stable reference: corpuslaw.us/code/85bcf207-6e9c-4ced-b5ef-9dd912f3369f

§ 3-905.15: Locations of sprinklers.

A. When a dead-end system is used, the sprinkler system shall be isolated from the domestic water supply system by not less than a dual-action spring-loaded check valve or its equivalent conforming to ASSE Standard 1024 and providing the flow requirement of the system without exceeding the allowable pressure drop of the standard of the system, need or whichever is less. The system components as indicated previously shall be acceptable to the Bureau of Codes Enforcement. The mandatory pressure-reducing valve (as part of the system components) shall be regulated at 125 psi. A Watts WTS 530c50 or equivalent reseating pressure-relief valve shall be used on all domestic sprinkler systems. B. The requirements of this section shall not apply in the following situations: (1) One check valve may be omitted when a backflow (dual check valve assembly) is required by the local water authority. (2) A backflow (dual check valve assembly) shall be required in all instances where a Fire Bureau connection is installed. (Note: Where the structure would normally not require a backflow preventer but a Fire Bureau connection is required, the dual check valves may be omitted where the backflow preventer is installed in place thereof.) (3) In low-pressure areas only, where residual pressure or flow gpms do not meet minimum requirements, one head must flow with a minimum of 18 gpm with at least 40 psi residual pressure, and two heads must flow with a minimum of 30 gpm with a 30 psi residual, unless otherwise Underwriters' Laboratories, Inc., listed. A circulated system may be used. The terminal end of the sprinkler supply shall be tied directly into the supply to a regularly used water closet or other approved fixture. Branch lines shall not exceed 25 feet on any circulating system. The dual check valves requirement is waived on such systems. C. If the sprinkler system is designed for more than one dwelling unit, all shutoffs in the system shall be secured, with lock and key, in the open position. A sign on the valves should read "Fire Bureau." The Fire Bureau is to be notified when valves are turned off and back on. All shutoffs shall be readily accessible at all times. D. If the sprinkler system is designed for more than one unit and separate electric service is used for each unit, the alarm switch with bell (horn-strobe) shall be on the electric house meter. Where townhouse-type condominiums are constructed, a fire-resistant construction of at least one hour shall be utilized between each dwelling unit with a separate riser, flow switch system components and outside bell (horn-strobe) installed, except that a single sprinkler system riser may be utilized where access is provided to all control valves for fire service and all system piping, sprinkler heads, valves and components are controlled under the authority of the condominium association and are included as such within the declaration or declaration of covenants. E. A supply line to the sprinkler system shall be tapped off the water service line at a point that would be downstream (customer side of meter) of any backflow preventer that the water purveyor might subsequently require in the service line to contain the domestic system from the public mains. F. All mechanical rooms (furnaces, water heater, etc.) shall have 165° to 212° F. standard sprinklers. G. All spacing of sprinklers in relation to obstructions such as fireplaces and heaters shall be to the sprinkler manufacturer's requirements. H. All sprinkler piping in unheated areas shall be protected from freezing. Where attached garages are unheated, a dry, pendant-type commercial sprinkler head shall be used where the sprinkler piping is to remain wet at all times. I. Sprinklers shall be installed in all areas, except that sprinklers may be omitted from: (1) Small closets where the least dimension does not exceed three feet, the area does not exceed 24 square feet and the walls and ceiling are surfaced with noncombustible materials. (2) Open attached porches, carports, and similar structures. (3) Attics and crawl spaces which are not used or intended for living purposes or storage. (4) The bathroom area if the total area does not exceed 55 square feet.

Ask a question about Harrisburg law

Corpus searches the Harrisburg sections it holds and shows the ones that match, with their citations. Free, no sign-in.