§ 3-905.11 — Sprinkler coverage

Code of the City of Harrisburg, Pennsylvania · Harrisburg Code § 3-905.11

Corpus is an independent public-information project, not the official City of Harrisburg website. Stable reference: corpuslaw.us/code/314f3c4a-b108-40da-87c0-170aacb5e1bc

§ 3-905.11: Sprinkler coverage.

A. The water demand for the system shall be determined by multiplying the design discharge by the number of design sprinklers. B. Residential sprinklers shall be spaced so that the maximum area protected by a single sprinkler does not exceed 144 square feet or is used in accordance with the manufacturer's design criteria. C. The maximum distance between sprinklers shall not exceed 12 feet on or between pipelines, and the maximum distance to a wall or partition shall not exceed six feet. Greater coverage may be achieved if Underwriters' Laboratories, Inc., has listed coverage as such. D. The minimum operating pressure of any sprinkler shall provide the minimum flow rates in accordance with the listing information of the sprinkler. E. Application rates, design areas, areas of coverage, and minimum design pressures other than those specified may be used with special sprinklers which have been listed for such specific residential installation conditions.