§ 51.80: Double check valve backflow prevention assembly.

Double check valve assemblies may be utilized at a premises where a substance is handled that could be objectionable - but not hazardous to health - if the substance is introduced into the potable water system. In addition to the provisions of section 51.76, a DC shall be installed in accordance with the following requirements in order to ensure the proper operation of and accessibility to the assembly: (1) DCs shall be sized to provide an adequate supply of water and pressure for the premises being served. (2) On premises where non-interruption of water supply is critical, two assemblies of the same type installed in parallel shall be provided. The assemblies shall be sized in such a manner that either assembly will provide the minimum water requirements, while the two together will provide the maximum flow required. (3) Bypass lines are prohibited. Pipe fittings that could be used for connecting a bypass line shall not be installed. (4) The assembly shall be readily accessible with adequate room for testing and maintenance. DCs may be installed below grade provided all test cocks are fitted with brass pipe plugs. All vaults containing a DC shall be well drained, constructed of suitable materials, and sized to allow for the minimum clearances established below. (5) DC assemblies two (2) inches and smaller shall have at least a three-inch clearance below and on both sides of the assembly, and if located in a vault, the bottom of the assembly shall be not more than twenty-four (24) inches below grade. All DC assemblies larger than two (2) inches shall have a minimum clearance of twelve (12) inches on the back side, twenty-four (24) inches on the test cock side, and twelve (12) inches below the assembly. Headroom of six (6) feet is required in vaults without a fully removable top. A minimum access opening of twenty-four (24) inches square is required on all vault lids. (6) Vertical installations are allowed on sizes up to and including four (4) inches that meet the following requirements: (a) The DC assembly shall contain internally spring-loaded check valves; (b) Flow is upward through assembly; (c) The assembly manufacturer specifies that the assembly can be used in a vertical position; and (d) The Managing Director authorizes the vertical installation of the DC assembly. (7) No deviations shall be permitted without prior written approval of the Managing Director.

( Ordinance 6393 , sec. 1, adopted 4/20/10 )

Ask a question about Garland law

Corpus searches the Garland sections it holds and shows the ones that match, with their citations. Free, no sign-in.