16.16.050 - Water distribution facilities.

A. General. All designs shall be in accordance with these standards: the Wyoming Department of Environmental Quality, Water Quality Rules and Regulations, Chapter XII, the Uniform Plumbing Code, as adopted by the city of Casper, and other city ordinances, rules and regulations and policies. B. Design Period. All water main and appurtenances shall be designed to provide for all contiguous or adjacent areas which may, within a reasonable period in the future, be tributary thereto. Contiguous or adjacent areas to be included in the design, and the tributary population to be provided for, shall be subject to approval by the city of Casper. All mains ten inches and larger shall be sized and located in accordance with the city of Casper's current master plan of water facilities; provided, however, the city reserves and has the right to specify sizes and locations, including those not delineated on the master plan. C. Design Flow. 1. The consultant shall substantiate and have approved by the city population densities per acre or per unit. 2. Water mains and looping must be designed to provide a minimum residual pressure of twenty psi under maximum day demand conditions with a fire flow of one thousand gpm at any one hydrant, and a total fire flow of one thousand five hundred gpm at any combination of two hydrants in the area, and/or must meet the requirements of the insurance service office. A minimum of forty-five psi residual pressure must be maintained under normal peak hour conditions without fire flow. An average daily flow of one hundred ninety gallons per person per day should be used in this design. A minimum 3:1 maximum day to average day demand and a minimum 5:1 maximum hour to average day demand should also be used. 3. The system must be looped and valved such that a break in any one length of main will put no more than six hundred feet of main nor more than two fire hydrants out of service while maintaining adequate minimum service in the remainder of the water system, once the break is isolated. 4. High density residential, commercial, or industrial areas will require special investigation to determine fire flow requirements. Existing and future static pressure and flow information used in the design must be obtained from, and approved by the city. 5. In large developments where justified, the developer may be required to help participate in a water distribution analysis of the proposed development as well as effects on the existing water distribution system. D. Depth of Cover. The minimum depth of cover for water mains shall be a minimum of six feet below the final grade of the street or as determined by the city engineer. Where final grades have not been established, mains shall be installed to a depth great enough to insure six feet of cover below future grade, based upon the best information available. E. Minimum Size. The minimum size of a water main shall be eight inches in diameter. Hydrant leads may be six inches in diameter. F. Alignment. The water main shall generally be located along the centerline of the street. G. Valves. Valves shall generally be spaced such that no single break shall require more than six hundred feet, one block length, or two fire hydrants, whichever is less, to be out of service during repairs, except for major transmission mains where longer spacing will be allowed. All distribution mains connecting to larger supply mains must be valved at the connection. At intersecting pipelines, valves shall be placed on two of the three, or three of the four leads from the intersection. Valves, generally, shall be located at street intersections in line with an extension of a property line. H. Fire Hydrants. Fire hydrants shall be spaced and located as follows: 1. At each intersection; 2. When on a divided highway, a hydrant shall be placed on each side of the highway; 3. In residential areas, fire hydrant spacing shall be no greater than four hundred feet, and no house shall be greater than two hundred fifty feet from a hydrant via a public access to the property being served; 4. In multiple-family, industrial, business, or commercial areas, fire hydrant spacing shall be no greater than three hundred feet, and no building shall be greater than one hundred fifty feet from a hydrant via public access to the property being served; 5. At the end of all dead-end mains; 6. Generally, hydrants should be located in line with an extension to the property line when located mid-block; 7. Hydrants shall be placed about three feet from the back of sidewalk, with a three feet elliptical radius of clearance to adjacent obstacles and with the lowest water outlet not less than eighteen inches or more than thirty inches from the final ground elevation. All other utility structures (i.e., electrical equipment, telephone, and television stands) must be kept at least three feet from the hydrant and not in line with the hydrant nozzles; 8. All public hydrant installations must be on dedicated easements or public rights-of-way and are to be owned and maintained by the city, and must be connected to mains owned and maintained by the city; 9. All fire hydrant spacing and locations are subject to the review and approval of the city of Casper fire chief. I. Corrosion Protection. The Casper water distribution system is located in soils that vary from mildly corrosive to extremely corrosive. In an effort to increase the long term performance and service history of the water system construction materials, the following shall be required: 1. Soil resistivity measurements using the "Wenner" four-pin method may be required for all new developments. Soil layer resistivities shall be calculated using the "Barnes" method. If warranted, resistivity measurements using a soil box and saturated soil from the five to seven feet depth may also be required by the city. City staff shall assist the developer's engineer in resistivity measurements. 2. Soil layer resistivities at depths from zero to seven and one-half feet or soil box resistivities of less than five thousand ohm-cm shall be considered to be medium to high soil corrosivity zones and water system materials used in this zone shall require special corrosion protection, as detailed in Section 503 of city of Casper standard specifications for public works construction and infrastructure improvements. a. If the soil resistivities are from one thousand five hundred ohm-cm to five thousand ohm-cm, magnesium anodes shall be used for protecting metallic pipe and fittings. b. If the soil resistivities are below one thousand five hundred ohm-cm, zinc anodes shall be used for protecting metallic pipe and fittings. c. City staff shall assist the consultant in the material selection, sizing, and placement of all required galvanic anodes and accompanying test stations. d. Copper service line piping and appurtenances connected to PVC pipe shall be protected by use of cast iron or regular anodes, as detailed in the standard specifications. e. If warranted, the city shall direct the developer to use PVC pipe in medium to high soil corrosivity zones. 3. Soil layer resistivities at depths from zero to seven and one-half feet or soil box resistivities of greater than five thousand ohm-cm shall be considered to be a low soil corrosivity zone, and water system materials used in this zone shall require only the corrosion protection, as detailed in city of Casper standard specifications for public works construction and infrastructure improvements. Copper service line piping and appurtenances do not need protection by cast iron or other anodes in this zone. J. Townhouse Manifolds. 1. Townhouse developments may elect to use a "manifold" water distribution system for service to individual properties, if a valid homeowner's association exists among all property owners. 2. The "manifold" system is restricted to townhouse developments and must conform to the following requirements: a. The "manifold" system must be owned and maintained by a viable homeowner's association. The city will be responsible for the single service line from the public main to the single curb stop located approximately three feet behind the property line, beyond which, it will remain the total responsibility of the homeowner's association. b. No more than four privately owned units may be placed on any "manifold." c. The "manifold" shall be located at the back of the front lot utility easement. Individual curb stops for each property owner shall be located in the utility easement and must be accessible at all times to the city. d. City staff shall review and approve the plans for the manifold construction. Following city approval, three copies of the plans and specifications shall be submitted to the State Department of Environmental Quality for their approval (private systems need DEQ permit). e. The "manifold" system shall meet all requirements of the Uniform Plumbing Code adopted by the city of Casper. The inspection of the "manifold" system beyond city jurisdiction shall be made by the city of Casper plumbing inspector. K. Mobile Home Communities. 1. All mobile home communities utilizing public streets and utilities shall be designed in accordance with these standards. 2. Mobile home rental communities (private) shall be designed in accordance with Part F of the Wyoming Department of Environmental Quality, Water Quality Rules and Regulations, Chapter XI. Following city approval, the plans and specifications shall be submitted to the State Department of Environmental Quality for their approval. L. Other Design Criteria. 1. All public water mains shall be installed in an easement at least twenty feet in width (ten feet each side of center line), or in public rights-of-way with access for maintenance vehicles. Easements containing both water and sewer mains must be at least thirty feet in width. No other utilities or related items (sprinkler systems, buildings, sidewalks, etc.) shall be installed within ten feet of the water main unless approved by the city. 2. Materials approved for main construction includes: a. Polyvinyl chloride pipe AWWA C900 or AWWA C909, four inches through twelve inches: i. Pressure Class 150 shall be used for working pressures less than one hundred twenty-five psi, ii. Pressure Class 200 shall be used for working pressures greater than one hundred twenty-five psi; b. Polyvinyl chloride pipe AWWA C905, fourteen inches through forty-eight inches: i. DR 25 shall be used for working pressures less than one hundred psi, ii. DR 18 shall be used for working pressures greater than one hundred psi and less than one hundred twenty-five psi, iii. DR 14 shall be used for working pressures greater than one hundred twenty-five psi; c. Ductile iron pipe AWWA C151 Pressure Class 350, four inches and larger, shall be used in soils contaminated by hydrocarbon and other locations designated by the city; d. Gaskets for ductile iron pipe installed in soil contamination areas shall be "Buna N-nitrile." Viton gaskets shall be required in severe soil contamination areas. 3. Materials approved for service lines include: a. Polyethylene service pipe AWWA C901 SDR 9, Pressure Class 200; b. Copper service pipe ASTM Class K; c. All services in areas with contaminated soils shall use flared copper pipe and fittings. 4. Dead-end mains shall be avoided wherever possible and shall generally not exceed six hundred feet. Hydrants shall be located at the end of dead-end mains for flushing purposes as well as for fire protection. If allowed by the city, flushing hydrants may be used on dead-end mains when fire protection is not required. For dead-end mains twelve inches and larger, a fire hydrant shall be used in all cases. 5. All water mains constructed to serve new customers or subdivisions shall be extended to at least the furthest property line or plat boundary. 6. Each building shall be served by a separate service line, except as stipulated elsewhere in this section. 7. All service line taps shall be machine-tapped at the time of the water main installation. Service lines must be installed prior to testing and acceptance of the water main and shall be located at the mid-point of the lot. Whenever possible, all curb stops shall be located two feet back of the sidewalk. 8. A domestic water service line cannot be connected into a building fire suppression line. Each must be separately connected to the water main. 9. Materials and methods approved for water system construction, and other design and, construction details, may be found in the city of Casper standard specifications for public works construction and infrastructure improvements. 10. Whenever possible, water main connections shall be made by a live tap under pressure. 11. Water mains shall be laid at least ten feet horizontally from any sanitary sewer, storm sewer, or sewer manhole, whenever possible. The distance shall be measured edge-to-edge. When local conditions prevent a horizontal separation of ten feet, a water main may be laid closer to a storm or sanitary sewer, provided that such construction is strictly in accordance with Section 501.13 of the city of Casper standard construction specifications. 12. Water mains crossing house sewers, storm sewers, or sanitary sewers shall be laid above the sewers to provide a separation of at least eighteen inches between the bottom of the water main and the top of the sewer, whenever possible. When local conditions prevent a vertical separation, as described in this section, construction shall be strictly in accordance with Section 501.13 of the city of Casper standard specifications for public works construction and infrastructure improvements. 13. Water service lines shall be installed on the lot center lines whenever possible. 14. Permanent pressure booster pumps are prohibited. 15. Fire hydrants or air release-vacuum relief assemblies shall be provided at high points whenever the pipe crown drops below the pipe invert. Fire hydrants may be used for air release only on eight-inch water mains. Flushing hydrants cannot be used for air release. 16. No water pipe shall pass through or come into contact with any part of a sewer or sewer manhole. 17. Surface water crossings, both over and under water, present special problems. This situation should be discussed with the city and the reviewing authority before final plans are prepared. a. For above water crossings, the pipe shall be: i. Adequately supported; ii. Protected from damage and freezing; and iii. Accessible for repair or replacement. b. For underwater crossings: i. The pipe shall be of special construction, having flexible, watertight joints; ii. Valves shall be provided at both ends of water crossings so that the section can be isolated for test or repair; iii. The valves shall be easily accessible and not subject to flooding; iv. Sampling taps should be available at each end of the crossing; v. Permanent taps should be made for testing and locating leaks. 18. There shall be no physical connection between the distribution system and any pipes, pumps, hydrants, or tanks whereby unsafe water or other contamination materials may be discharged or drawn into the system, unless adequately protected by approved backflow prevention devices. All ordinances, rules and regulations and policies of the city in regards to cross-connection control shall be adhered to. a. The approval of the city and the reviewing authority shall be obtained for interconnections between potable water supplies. b. Neither steam condensate, nor cooling water from engine jackets or other heat exchange devices, shall be returned to the potable water supply. 19. Where it is planned to extend a water line at a future date, the water line stub shall extend at least a distance of one hundred pipe diameters beyond a valve. The stub shall be securely plugged with an approved pressure-tight plug and concrete thrust block. 20. All hydrants, plugs, caps, tees, reducers, and bends deflecting eleven and one-fourth degrees or more shall be provided with reaction backing against undisturbed ground with concrete backing. 21. New materials, equipment, or technology not covered by these design standards or city of Casper standard specifications for public works construction and infrastructure improvements may be considered on an individual basis, if such a variance has the potential to initiate more cost-effective service to the citizens of Casper. Facilities not covered by these standards must be reviewed and approved jointly by the city and the Department of Environmental Quality in accordance with Section 5 of the Wyoming Department of Environmental Quality, Water Quality Rules and Regulations, Chapter XII.

(Ord. 2-06 (part), 2006)

Ask a question about Casper law

Corpus searches the Casper sections it holds and shows the ones that match, with their citations. Free, no sign-in.