15.35.050 Amendment of 2025 CFC Appendix B.

Appendix B of the 2025 California Fire Code is amended as follows: B101.1 – Table B105.1(2) {CFC text not modified} Table B105.2 | TABLE B105.2 REQUIRED FIRE FLOW FOR BUILDINGS OTHER THAN ONE-AND TWO-FAMILY DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOMES | AUTOMATIC SPRINKLER SYSTEM (Design Standard) | MINIMUM FIRE FLOW (gallons per minute) | FLOW DURATION (hours) | No automatic sprinkler system | Value in Table B105.1(2) | Duration in Table B105.1(2) | Section 903.3.1.1 of the California Fire Code | 50% of the value in Table B105.1(2)a | Duration in Table B105.1(2) at the reduced flow rate | Section 903.3.1.2 of the California Fire Code | 50% of the value in Table B105.1(2)b | Duration in Table B105.1(2) at the reduced flow rate | For SI: 1 gallon per minute = 3.785L/m a. The reduced fire flow shall not be less than 1,000 gallons per minute b. The reduced fire flow shall not be less than 1,500 gallons per minute B105.2 – B106 {CFC text not modified} (Ord. 11-2025 § 2, 9-16-25.)