15.35.260 Amendment to 2025 CFC Section 5003 (General Requirements).

Section 5003 of the 2025 California Fire Code is amended as follows: 5003.1 – 5003.2.4 {CFC text not modified} 5003.2.4.1 Underground Tanks. Underground tanks used for the storage of liquid hazardous material shall be provided with secondary containment. In lieu of providing secondary containment for an underground tank, an above-ground tank in an underground vault complying with Section 5704.2.8 may be permitted. Underground tanks shall also comply with the laws and regulations set forth in Chapter 6.7, Division 20, Sections 25280 through 25299.7, Underground Storage of Hazardous Substances, of the California Health and Safety Code and the associate regulations in the California Code of Regulations Title 23, Waters, Chapter 3, Water Resources Control Board, subchapter 16, Underground Tank Regulations, as amended, are adopted by reference to be the minimum standards in effect in the city. The city can require more stringent standards through other sections of this Code. 5003.2.4.2 – 5003.2.9.2 {CFC text not modified} 5003.2.10 Fire Protection for Workstations and chemical wet-benches. When the building is protected by an automatic fire protection system, an approved fire protection system in accordance with Section 2703.10 shall be provided for all combustible (plastic) workstations and chemical wet-benches where hazardous materials are dispensed, stored or used. 5003.3 – 5003.5 {CFC text not modified} 5003.5.1 Markings. Individual containers, cartons or packages shall be conspicuously marked or labeled in an approved manner. Rooms or cabinets containing compressed gases shall be conspicuously labeled: COMPRESSED GAS. Product conveying ducts for venting hazardous materials operations shall be labeled with the hazard class of the material being vented and the direction of flow. 5003.6 –5003.9.10 {CFC text not modified} 5003.9.11 Monitoring. Liquid and solid hazardous materials storage or use systems must be monitored on a regular or continuous basis. A written monitoring plan must be submitted for approval by the chief and must be included in the Hazardous Materials Business Plan. Monitoring methods may include but are not limited to the following: 1. Visual inspection, no less than monthly (requires trained personnel and documentation). 2. Approved continuous leak detection and alarm system. 3. Any system which will provide continuous, reliable monitoring of the primary container(s) capable of alerting occupants to an alarm or trouble condition; all systems are subject to approval by the chief. 5003.9.12 Spill Control for hazardous materials liquids. Regardless of the exempt amounts and containment requirements in Chapter 50, all containers of liquid hazardous materials regulated by this or any other article shall be provided with an approved means to control spills. The spill control shall take into consideration the amount and hazard of the materials and the nature of the facility. 5003.9.13 Secondary Containment requirements. When deemed necessary to protect life safety, emergency responders, or the environment and regardless of the exempt amounts and secondary containment requirements in Chapter 50, the fire chief, or his designee, may require containers of liquid, solid, or gaseous hazardous materials regulated by this or any other article to be provided with secondary containment in accordance with Section 5004.2.2. If parts of this Code differ in their requirements for secondary containment, the more stringent shall apply. The chief may require outside containment areas to be covered with a roof or canopy for protection from the environment. 5003.10 – 5003.12 {CFC text not modified} (Ord. 11-2025 § 2, 9-16-25.)

Ask a question about Fremont law

Corpus searches the Fremont sections it holds and shows the ones that match, with their citations. Free, no sign-in.