§ 15.35.340 — Amendment to 2025 CFC Section 6004 (Highly Toxic and Toxic Compressed Gases)
Fremont Municipal Code (Fremont Municipal Code current through Ordinance 02-2026 passed May 5, 2026 (Code Publishing Company, codepublishing.com, scraped 2026-11-18)) · Fremont Municipal Code § 15.35.340
Corpus is an independent public-information project, not the official City of Fremont website. Stable reference: corpuslaw.us/code/10f06e57-a4e8-47d8-bc11-3e7824f58a9e
15.35.340 Amendment to 2025 CFC Section 6004 (Highly Toxic and Toxic Compressed Gases).
Section 6004 of the 2025 California Fire Code is amended as follows: 6004.1 General. The storage and use of highly toxic and toxic compressed gases and those with health hazard rankings of 3 or 4 in accordance with NFPA 49 or NFPA704 shall comply with this section. 6004.1.1 – 6004.1.1.3 {CFC text not modified} 6004.1.1.4 Other areas of Group B, F, M, S or L occupancies. Storage, use, and handling of highly toxic and toxic compressed gases shall comply with the following: 1. When located inside, highly toxic and toxic compressed gases shall be permitted, stored or used only when located within approved gas cabinets, exhausted enclosures, or gas rooms. See also Sections 6004.1.2, 6004.1.3, and 6004.2.2.6. Exceptions: 1.1 Cylinders of compressed gases with a health hazard ranking of 4 and with a capacity not exceeding 10 cubic feet at normal temperature and pressure (NTP) are allowed in fume hoods or approved tools designed for their use. 1.2 Cylinders of compressed gases with a health hazard ranking of 3 and with a capacity not exceeding 20 cubic feet at normal temperature and pressure (NTP) are allowed in fume hoods or approved tools designed for their use. 2. When located outside, and when required by the fire chief, highly toxic and toxic compressed gases shall be kept under a canopy in accordance with 6004.3. 6004.1.2 – 6004.1.3 {CFC text not modified} 6004.1.4 Automatic Shut-Off Valve. An automatic shut-off valve, which is of a fail-safe to close design, shall be provided to shut off the supply of highly toxic gases for any of the following: 1. Activation of a manual fire alarm system. 2. Activation of the gas detection system. 3. Failure of emergency power. 4. Failure of primary containment. 5. Seismic activity. 6. Failure of required ventilation. 7. Manual activation at an approved remote location. Exceptions: 1. Cylinders of compressed gases with a capacity not exceeding 10 cubic feet at normal temperature and pressure (NTP) when used in gas cabinets, fume hoods, or approved tools designed for their use. 6004.1.5 Emergency Control Station. Signals from emergency equipment used for highly toxic gases shall be transmitted to an emergency control station or other approved monitoring station, which is continually staffed by trained personnel. 6004.1.6 Maximum Allowable Quantity. Toxic gases stored or used in quantities exceeding the maximum allowable quantity in a single vessel per control area or outdoor control area shall comply with the additional requirements for highly toxic gases of Section 6004 of this Code. 6004.1.7 Reduced Flow Valve. All containers of materials other than lecture bottles containing Highly Toxic material and having a vapor pressure exceeding 29 psia shall be equipped with a reduced flow valve when available. If a reduced flow valve is not available, the container shall be used with a flow-limiting device. All flow limiting devices shall be part of the valve assembly and visible when possible; otherwise, they shall be installed as close as possible to the cylinder source. A lecture bottle is defined as a 3E cylinder, meeting the specifications outlined in 49 CFR 178.42, having a diameter of less than 2 inches, a length of less than 2 feet and service pressure of 1800 psig. 6004.1.8 Annual Maintenance. All safety control systems at a facility shall be maintained in good working conditions and tested according to the manufacturers’ specifications, but not less than annually. Maintenance and testing shall be performed by people qualified to perform the maintenance and tests. Maintenance records and certifications shall be available to any representative of the Fire Department for inspection upon request. 6004.1.9 Fire Extinguishing Systems. Buildings and covered exterior areas for storage and use areas of materials regulated by this Chapter shall be protected by an automatic fire sprinkler system in accordance with NFPA 13. The design of the sprinkler system for any room or area where highly toxic or toxic gases are stored, handled or used shall be in accordance with Section 5004.5. 6004.1.10 Local Gas Shut Off. Manual activation controls shall be provided at locations near the point of use and near the source, as approved by the fire code official. The fire code official may require additional controls at other places, including, but not limited to, the entry to the building, storage or use areas, and emergency control stations. Manual activated shut-off valves shall be of a “fail-safe-to-close” design. 6004.1.11 Exhaust Ventilation Monitoring. For highly toxic gases and toxic gases exceeding threshold quantities, a continuous monitoring system shall be provided to ensure that the required exhaust ventilation rate is maintained. The monitoring system shall initiate a local alarm. The alarm shall be both visual and audible and shall be designed to provide warning both inside and outside of the interior storage, use, or handling area. 6004.1.12 Emergency Response Plan. If the preparation of an emergency response plan for the facility is not required by any other law, responsible persons shall prepare, or cause to be prepared, and filed with the fire code official, a written emergency response plan. If the preparation of an emergency response plan is required by other laws, a responsible person shall file a copy of the plan with the fire chief. 6004.1.16 Inert Gas Purge System. Gas systems shall be provided with dedicated inert gas purge systems. A dedicated inert gas purge system may be used to purge more than one gas, provided the gases are compatible. Purge gas systems inside buildings shall be in an approved gas cabinet unless the system operates by vacuum demand. Exceptions: 1. Cylinders of compressed gases with a health hazard ranking of 4 and with a capacity not exceeding 10 cubic feet at normal temperature and pressure (NTP) when used in gas cabinets, fume hoods or approved tools designed for their use. 2. Cylinders of compressed gases with a health hazard ranking of 3 and with a capacity not exceeding 20 cubic feet at normal temperature and pressure (NTP) when used in gas cabinets, fume hoods or approved tools designed for their use. 6004.1.17 Seismic Shutoff Valve. An automatic seismic shutoff valve, which is of a fail-safe to close design, shall be provided to shutoff the supply of highly toxic, and toxic gases upon a seismic event within five seconds of a horizontal sinusoidal oscillation having a peak acceleration of 0.3G (1.47m/sec2) and a period of 0.4 seconds. Exceptions: 1. Cylinders of compressed gases with a health hazard ranking of 4 and with a capacity not exceeding 10 cubic feet at normal temperature and pressure (NTP) when used in gas cabinets, fume hoods or approved tools designed for their use. 2. Cylinders of compressed gases with a health hazard ranking of 3 and with a capacity not exceeding 20 cubic feet at normal temperature and pressure (NTP) when used in gas cabinets, fume hoods or approved tools designed for their use. 6004.2 – 6004.2.2.6 {CFC text not modified} 6004.2.2.7 {CFC text not modified} Exceptions: deleted 6004.2.2.7.1 – 6004.2.2.7.5 {CFC text not modified} 6004.2.2.8 {CFC text not modified} Exceptions: 1. Emergency power is not required for mechanical exhaust ventilation, treatment systems, and temperature control systems where approved fail-safe systems are installed. 2. When the aggregate quantities of toxic or highly toxic gases do not exceed the maximum allowable quantities set forth in Tables 5003.1.1 (2) and 5003.1.1 (4). 6004.2.2.8.1 – 6004.3.2.4 {CFC text not modified} 6004.3.3 Outdoor Storage Weather Protection for Portable Tanks and Cylinders. Weather protection in accordance with Section 5004.13 and this section shall be provided for portable tanks and cylinders located outdoors and not within gas cabinets or exhausted enclosures. The storage area shall be equipped with an approved automatic sprinkler system in accordance with Section 5004.5. Exception: deleted 6004.3.3.1 Gas Detection Under Canopies. Gas detection in conformance with 6004.2.2.10 shall be provided when the maximum rate of release from a cylinder or tank could result in gas levels above the accepted permissible exposure level at the property line. 6004.3.4 – 6004.3.4.3 {CFC text not modified} (Ord. 11-2025 § 2, 9-16-25.)
Ask a question about Fremont law
Corpus searches the Fremont sections it holds and shows the ones that match, with their citations. Free, no sign-in.