§ 15.35.180 — Amendment to the 2025 CFC Section 907 (Fire Alarm and Detection Systems)

Fremont Municipal Code (Fremont Municipal Code current through Ordinance 02-2026 passed May 5, 2026 (Code Publishing Company, codepublishing.com, scraped 2026-11-18)) · Fremont Municipal Code § 15.35.180

Corpus is an independent public-information project, not the official City of Fremont website. Stable reference: corpuslaw.us/code/f921670a-b123-4ca8-b409-532a1932f267

15.35.180 Amendment to the 2025 CFC Section 907 (Fire Alarm and Detection Systems).

Section 907 of the 2025 California Fire Code is amended as follows: 907.1 – 907.1.2 {CFC text not modified} 907.1.3 Equipment. Systems and their components shall be California State Fire Marshal listed and approved for the purpose for which they are installed. The building owner shall provide a serially numbered certificate from an approved nationally recognized testing laboratory for all fire alarm systems indicating that the system has been installed in accordance with the approved plans and specifications and meets minimum NFPA Standards. A copy shall be provided to the fire marshal’s office at no cost to the city. Certification shall be required for all new systems installed after January 1, 1996. Existing systems that can no longer be serviced or maintained or those that are deemed problematic shall also be required to obtain this certification within 12 months of notification. 907.1.3.1 Remote Annunciator Location. All new or existing systems that require a new Fire Alarm Control Panel shall have a remote annunciator at the main entrance. It shall be visible to approaching emergency personnel. 907.1.4 – 907.1.5 {CFC text not modified} 907.2 {CFC text not modified} Exceptions: 1. deleted 2. – 3. {CFC text not modified} 907.2.1 – 907.2.5.1 {CFC text not modified} 907.2.2.2 Laboratories involving research and development or testing. A fire alarm system activated by an air-sampling-type smoke detection system or a radiant-energy-sensing detection system shall be installed throughout the entire fire area utilized for the research and development or testing of lithium-ion or lithium metal batteries. In addition, a manual fire alarm box shall be installed per CFC section 907.4.2 near the closest exit door(s) containing the storage of lithium-ion or lithium metal batteries. 907.2.2.3 – 907.2.4 {CFC text not modified} 907.2.4.1 Manufacturing involving lithium-ion or lithium metal batteries. A fire alarm system activated by an air-sampling-type smoke detection system or a radiant-energy-sensing detection system shall be installed throughout the entire fire area where lithium-ion or lithium metal batteries are manufactured; and where the manufacturer of vehicles, energy storage systems or equipment containing lithium-ion or lithium metal batteries where the batteries are installed as part of the manufacturing process. In addition, a manual fire alarm box shall be installed per CFC section 907.4.2 near the closest exit door(s) containing the storage of lithium-ion or lithium metal batteries. 907.2.5.1 All new H occupancies, or existing H occupancies that require a new fire alarm control panel, and that have a local detection system(s) shall interconnect, or otherwise configure, the system(s) to report to a Central Station as a fire condition or alarm condition. The report shall be in nomenclature easy to understand (e.g. Water, not H20). 907.2.6 – 907.2.7.1.1 {CFC text not modified} 907.2.7.2 Storage of lithium-ion or lithium metal batteries. A fire alarm system activated by an air-sampling-type smoke detection system or a radiant-energy-sensing detection system shall be installed in a room or space within a Group M occupancy where required for the storage of lithium-ion or lithium metal batteries in accordance with Section 320. In addition, a manual fire alarm box shall be installed per CFC section 907.4.2 near the closest exit door(s) containing the storage of lithium-ion or lithium metal batteries. 907.2.8 – 907.2.10.1 {CFC text not modified} 907.2.10.2 Storage of lithium-ion or lithium metal batteries. A fire alarm system activated by an air-sampling-type smoke detection system or a radiant-energy-sensing detection system shall be installed throughout the entire fire area where required for the storage of lithium-ion or lithium metal batteries in accordance with Section 320. In addition, a manual fire alarm box shall be installed per CFC section 907.4.2 near the closest exit door(s) containing the storage of lithium-ion or lithium metal batteries. 907.2.11 – 907.2.29.1 {CFC text not modified} 907.3 Fire safety functions. Automatic fire detectors utilized for the purpose of performing fire safety functions shall be connected to the building’s fire alarm control unit where a fire alarm or sprinkler monitoring system is installed. Detectors shall, upon actuation, perform the intended function and activate the alarm notification appliance or activate a visible and audible supervisory signal at a constantly attended location when approved by the Fire Code Official. In buildings not required to be equipped with a fire alarm or sprinkler monitoring system, the automatic fire detector shall be powered by normal electrical service and, upon actuation, perform the intended function. The detectors shall be located in accordance with NFPA 72 and Fire Department Standard 25A. 907.3.1 Duct Smoke Detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building’s fire alarm control unit when a fire alarm/sprinkler monitoring is installed. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a central station or when approved by the Fire Code Official at a constantly attended location and shall perform the intended fire safety function in accordance with this code and the California Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s notification appliances. 2. In occupancies, not required to be equipped with a fire alarm or sprinkler monitoring system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location and shall be identified as air duct detector supervisory. 907.3.2 – 907.6.1.1 {CFC text not modified} 907.6.2 Power Supply. The primary and secondary power supply for the alarm system shall be provided in accordance with NFPA 72 and Fire Department Standard 25A. Exception: {CFC text not modified} 907.6.3 Initiating device identification. The fire alarm/fire sprinkler monitoring system shall identify the specific initiating device address/zone, location, device type, floor level per the Fire Department Standard 25A including indication of normal, alarm, trouble and supervisory status as appropriate. Exception: 1. deleted 2. deleted 3. deleted 4. Fire alarm systems or devices that have multiple devices on a single zone and the existing wiring can be used with the new replacement system. 907.6.3.1 {CFC text not modified} 907.6.4 Zones. Fire alarm and sprinkler monitoring systems shall be divided into zones where required by this section. For the purposes of annunciation and notification, zoning shall be in accordance with Fire Department Standard 25A. 907.6.4.1 – 907.6.4.1.1 {CFC text not modified} 907.6.4.2 High-rise buildings. In high-rise buildings, and Group I-2 occupancies having occupied floors located more than 75 feet (22860mm) above the lowest level of fire department vehicle access, a separate zone by floor shall be provided for all the following types of alarm-initiating devices where provided: 1. Smoke detectors. 2. Sprinkler water-flow devices. 3. Manual fire alarm boxes. 4. Other approved types of automatic fire detection devices or suppression systems in accordance with Fire Department Standard 25A. 907.6.4.3 {CFC text not modified} 1. Fire alarm initiating devices with individual annunciation in accordance with the Fire Department Standard 25A. 2. {CFC text not modified} 3. Fire alarm system troubles in accordance with the Fire Department Standard 25A. 4. {CFC text not modified} 5. {CFC text not modified} 907.6.4.4 – 907.6.5 {CFC text not modified} 907.6.6 Monitoring. Fire alarm system shall transmit distinctly and descriptively different alarm, supervisory and trouble signals to an approved supervising station in accordance with NFPA 72 and Fire Department Standard 25A or when approved by the Fire Code Official, shall sound an audible signal at a constantly attended location. 907.6.6.1 – 907.10.1 {CFC text not modified} (Ord. 11-2025 § 2, 9-16-25.)

Ask a question about Fremont law

Corpus searches the Fremont sections it holds and shows the ones that match, with their citations. Free, no sign-in.