§ 15.35.320 — Amendment to 2025 CFC Section 5703 (General Requirements)
Fremont Municipal Code (Fremont Municipal Code current through Ordinance 02-2026 passed May 5, 2026 (Code Publishing Company, codepublishing.com, scraped 2026-11-18)) · Fremont Municipal Code § 15.35.320
Corpus is an independent public-information project, not the official City of Fremont website. Stable reference: corpuslaw.us/code/be760ccb-d48d-47b5-bc36-77614cfbc471
15.35.320 Amendment to 2025 CFC Section 5703 (General Requirements).
Section 5703 of the 2025 California Fire Code is amended as follows:1 5703.1 – 5703.6.11 {CFC text not modified} 5703.6.12 Monitoring. Flammable and combustible liquid storage or use systems must be monitored on a regular or continuous basis. A written monitoring plan must be submitted for approval by the chief and must be included in the Hazardous Materials Business Plan. Monitoring methods may include but are not limited to the following: 1. Visual inspection, no less than monthly. 2. Continuous leak detection and alarm system. 3. Any system which will provide continuous, reliable monitoring of the primary container(s) capable of alerting occupants to an alarm or trouble condition; all systems are subject to approval by the fire chief. (Ord. 11-2025 § 2, 9-16-25.)