15.35.120 Amendment to 2025 CFC Section 506 (Key Boxes).

Section 506 of the 2025 California Fire Code is amended as follows: 506.1 Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for lifesaving or fire-fighting purposes, the fire code official is authorized to require a Knox Rapid Entry System to be installed in an approved location. The Knox Rapid Entry System shall be of an approved type listed in accordance with UL 1037 and shall contain keys to gain necessary access as required by the fire code official. If any of the following items listed (1) through (8) is located at an occupancy, then a Knox Rapid Entry System shall be required. 1. Fire suppression and standpipe systems. When a building within the city limits is protected by an automatic fire suppression and/or standpipe system, it shall be equipped with a Knox Rapid Entry System, installed at a location approved by the fire code official or designee. 2. Automatic Alarm Systems. When a building within the city limits is protected by an automatic fire suppression and/or standpipe system, it shall be equipped with a Knox Rapid Entry System, installed at a location approved by the fire code official or designee. 3. Multi-family residential structures. Multi-family residential structures comprised of four (4) or more units which access the building or common areas or mechanical or an electrical room within the building are denied through locked doors. 4. Automatic Gates. When a property is accessed through a gate or cross arm that impedes ingress through required fire lanes by means of a key or swipe card, it shall be equipped with a key switch to be installed at a location approved by the fire code official or designee. 5. Security Padlock. When a property is protected by a locked fence or gate and where immediate access to the property is necessary for life saving and firefighting purposes, it shall be equipped with a security padlock to be installed at a location approved by the fire code official or designee. It shall then be the responsibility of the responsible party to see that the fence or gate is secured properly so that the security padlock is accessible. 6. Construction Sites. When a construction site is to be secured by a locked fence or gate, that site will fall under section 2 subsection E, during the duration of construction or until said fence or gate is removed. It shall then be the responsibility of the construction company to see that the fence or gate is secured properly so that the security padlock is accessible. 7. Security of Fire Department Connections (FDC). When a building is protected by an automatic sprinkler and/or standpipe system and the fire department connection is exposed to vandalism, the fire code official or designee shall require that a security gate be installed around the standpipe and that a Knox security cap be installed. Exception: This shall not apply to any owner-occupied one- and two-family dwellings. Owners of single- and two-family occupancies are encouraged to participate voluntarily utilizing a residential key box. 8. Remote Power Box. Where a building is equipped with the following items: the fire code official, can require to be installed a Knox Remote Power Box, to safely gain access to high-risk electrical areas by tripping the power on equipment and machinery. a) Generators b) Power distribution centers c) Light rail systems d) Telecommunication equipment e) HVAC controls f) Solar, photovoltaic, wind-powered systems g) Battery Storage Facilities 506.2 {CFC text not modified} 506.3 Emergency information Knox Document Cabinet. When an occupancy contains storage of hazardous materials that exceed the exempt amounts listed in Chapter 50 of the California Fire Code, or the occupancy is required by the fire chief to have available on-site pre-fire plans, the fire chief may require an approved emergency Knox Document Cabinet be installed on the premises for the storage of such information. The emergency information box shall be installed in an approved location, and the enclosed information shall be updated, annually or as changes dictate, by the occupant. 506.1.3 Knox Rapid Entry System storage cabinet contents. Any facility, firm, or corporation that handles, uses, or stores hazardous material and or total aggregate is more than 55 gallons of liquid, 500 pounds of solid, or 200 cubic feet of gas, shall have a Knox Document Cabinet, model #1302, for Fremont Fire Department use. Exception: not required for Underground Storage Tanks (UST). The cabinet shall contain the following items: 1. Binder for Document Cabinet with: 2. List of responsible parties’ phone numbers (i.e., plant manager, owner, all principal employees, management types, and major chemical manufacturers). 3. An aerial pre-plan of the facility, to include room numbering, extinguishing systems (outside stem and yoke (OSY), post indicator valves (PIV), fire department connections (FDC), drains, secondary containment, ventilation systems, and hydrant locations (See attached aerial pre-plan sample). 4. Alphabetical list of chemicals, room number location, and approximate quantity and strength (i.e., 50%, 60%, 85%, etc.). 5. Safety Data Sheet (SDS) of all chemicals in alphabetical order. 6. Keys for Document Cabinet: a. Keys to all locked doors with plastic identification tags corresponding to complex aerial pre-plan. 7. Location of Document Cabinet: a. The Knox Document Cabinet shall be located on the exterior of the building near the front entrance as shown by Fire Code Official or Designee. (Ord. 11-2025 § 2, 9-16-25.)

Ask a question about Fremont law

Corpus searches the Fremont sections it holds and shows the ones that match, with their citations. Free, no sign-in.