§ 15.35.150 — Amendment to 2025 CFC Section 903 (Automatic Sprinkler Systems)

Fremont Municipal Code (Fremont Municipal Code current through Ordinance 02-2026 passed May 5, 2026 (Code Publishing Company, codepublishing.com, scraped 2026-11-18)) · Fremont Municipal Code § 15.35.150

Corpus is an independent public-information project, not the official City of Fremont website. Stable reference: corpuslaw.us/code/ae3729c2-1950-4692-82fc-86bb50b5b4a7

15.35.150 Amendment to 2025 CFC Section 903 (Automatic Sprinkler Systems).

Section 903 of the 2025 California Fire Code is amended as follows: 903.1 – 903.1.1 {CFC text not modified} 903.2 Where required. Approved automatic sprinkler systems in new buildings and structures shall be provided in the locations described in this section. Exceptions: 1. Automatic fire sprinkler protection for fixed guide way transit systems shall be as per Section 903.2.17. 2. Canopies over motor vehicle fuel dispensing facilities when constructed in accordance with Section 406.7.2 of the 2025 California Building Code. 3. Temporary construction trailers, less than 1,650 square feet, on-site less than one year and 10’ from property lines, building, structures and combustibles. 4. The following detached Group U occupancies: Barns, fences more than six feet high, grain silos accessory to residential occupancies, green houses, gazebos or similar structures accessory to residential occupancies, livestock shelters, retaining walls, tool or storage sheds, stables, tanks, towers. 5. Detached Group U occupancies housing dumpsters or refuse containers with floor areas of 500 sq. ft. or less are exempt from installation of automatic fire extinguishing systems. 6. Detached one-story Group U occupancies housing dumpsters or refuse containers with floor area of 500 to 1500 sq. ft. are exempt from installation of automatic fire extinguishing systems provided all the following requirements are met: a. Building is constructed to Type IV, Type V 1-Hour, or a higher fire-resistive construction, and b. Minimum five-foot setback to property line and ten-foot setback to any other building on the site is maintained. 7. Airport Control Towers (see 903.2.11.3 exception #1) 8. Parking shade structures or solar trellises when constructed of non-combustible materials, set back from property lines and separated from buildings in accordance with the California Building Code. 903.2.1 Group A and B. An automatic sprinkler system shall be provided throughout buildings and portions thereof used as Group A and B occupancies. 903.2.1.1 Group A-1. An automatic sprinkler system shall be provided throughout Group A-1 occupancies. 903.2.1.2 Group A-2. An automatic sprinkler system shall be provided throughout Group A-2 occupancies. 903.2.1.3 Group A-3. An automatic sprinkler system shall be provided throughout Group A-3 occupancies. 903.2.1.4 Group A-4. An automatic sprinkler system shall be provided throughout Group A-4 occupancies. 903.2.1.5 Group A-5. An automatic sprinkler system shall be provided throughout Group A-5 occupancies. 903.2.1.6 – 903.2.1.7 {CFC text not modified} 903.2.2 Group B. An automatic sprinkler systems shall be provided for Group B occupancies in addition as required in Sections 903.2.2.1 and 903.2.2.2. 903.2.2.1 Ambulatory care facilities. An automatic sprinkler system shall be provided throughout Ambulatory care facilities. 903.2.3 Group E. Except as provided for in Sections 903.2.3 for a new public-school campus and 907.2.3 (fire alarm and detection) for modernization of an existing public-school campus building(s), an automatic sprinkler system shall be provided for Group E occupancies. 903.2.4 Group F. An automatic sprinkler system shall be provided throughout all buildings containing Group F occupancies. 903.2.4.1 – 903.2.4.2 {CFC text not modified} 903.2.4.3 Deleted 903.2.5 Group H. An automatic sprinkler system shall be provided throughout all buildings containing Group H occupancies. 903.2.5.1 – 903.2.5.4 {CFC text not modified} 903.2.6 Group I. An automatic sprinkler system shall be provided throughout buildings with a Group I fire area. 903.2.6.1 {CFC text not modified} 903.2.6.2 {CFC text not modified} 903.2.7 Group M. An automatic sprinkler system shall be provided throughout buildings containing a Group M occupancy. 903.2.7.1 {CFC text not modified} 903.2.7.2 – deleted 903.2.7.3 {CFC text not modified} 903.2.8 Group R. An automatic sprinkler system installed in accordance with Section 903.3 shall be provided throughout all buildings with a Group R fire area. 903.2.8.1 – 903.2.8.3 {CFC text not modified} 903.2.9 Group S-1. An automatic sprinkler system shall be provided throughout all buildings containing a Group S-1 occupancy. 903.2.9.1 – 903.2.9.3 {CFC text not modified} 903.2.9.4 – deleted 903.2.10 Group S-2. An automatic sprinkler system shall be provided throughout buildings classified as parking garages in accordance with Section 406.4 of the California Building Code or where located beneath other groups. 903.2.10.1 Commercial Parking Garages. An automatic sprinkler system shall be provided throughout buildings used for the storage of commercial trucks and buses. 903.2.10.2 {CFC text not modified} 903.2.11 Specific building areas and hazards. In all occupancies, an automatic sprinkler system shall be installed for building design or hazards in the locations set forth in Sections 903.2.11.1 through 903.2.11.6. 903.2.11.1 Stories without openings. An automatic sprinkler system shall be installed throughout every story or basement without openings. 903.2.11.1.2 through 903.2.11.1.3 – deleted 903.2.11.2 {CFC text not modified} 903.2.11.3 {CFC text not modified} Exceptions – deleted 903.2.11.4 – 903.2.17.2.6 {CFC text not modified} 903.2.18 Group U private garages and carports accessory to Group R-3 occupancies. Carports and garages, accessory to Group R-3 occupancies, shall be protected by residential fire sprinklers in accordance with this section. Residential fire sprinklers shall be connected to, and installed in accordance with, an automatic residential fire sprinkler system that complies with Section R313 of the California Residential Code or with NFPA 13-D. Fire sprinklers shall be residential or quick response sprinklers, designed to provide a minimum density of .05 gpm/ft2 over the area of the garage and/or carport, but not to exceed two sprinklers for hydraulic calculation purposes. Garage doors shall not be considered obstructions with respect to sprinkler placement. Exception: Group U private garages and carports attached to Group R-3 Accessory Dwelling Units. 903.2.19 – 903.2.21 {CFC text not modified} 903.2.22 Additions to Group A, B, E, F, H, I, L, M, R, S, and certain miscellaneous Group U occupancies. For additions to existing Groups A, B, E, F, H, I, L, M, R, S, and U occupancies not exempted in 903.2, an automatic fire extinguishing system (AFES) shall be required throughout the entire building when one of the following thresholds is exceeded. For purposes of floor area calculations, Group U (attached private garages or similar) occupancies shall be included in the floor area calculation. 1. The combined floor area of the existing building plus the addition exceeds 5,000 square feet. 2. The addition exceeds 2,500 square feet. 3. The addition increases the floor area of the existing building by 50%. The increase in floor area shall be calculated cumulatively from July 1, 1999. Exception: The existing portion of a one- or two-story building with no basement does not require automatic fire extinguishing systems when the following conditions (a-c) are met: a. The addition is protected by an AFES. b. The addition and the existing structure are separated from the remaining spaces based on the non-sprinklered type of construction and occupancy in accordance with the CFC, including any required protection and fire rated openings. c. An Assembly, Education, Institutional and Multi-Family Residential occupancy installs an underwriter laboratory certified and National Fire Protection Association Standard 72 compliant fire alarm system. 903.2.23 Additions to existing R-3 occupancies. For additions to R-3 occupancies, an automatic fire extinguishing system (AFES) shall be required throughout the entire building when one of the following thresholds is exceeded. For purposes of floor area calculations, Group U attached private garages, or similar occupancies shall be included in the floor area calculation: 1. The combined floor area of the existing building plus the addition exceeds 5,000 square feet. 2. The addition increases the floor area of the existing structure by 50%. Exception: The entire residence, including the addition does not require an AFES when the following conditions are met: a. Additions under 500 sq ft (or under 1000 sq ft with an approved local or hard wired or similarly configured fire alarm system) and cumulative floor area ≤ 5000 sq ft are permitted. b. No Planning or Building Department variances or exceptions are needed to accommodate the addition. c. Exception (a) may be used cumulatively for conversion(s) of existing space to habitable space occurring after July 1, 1999, until the addition(s) total more than 50 percent of the original floor area. 903.2.24 Repair/Retrofit. All occupancies except Group U occupancies exempted in 903.2 damaged during a fire or natural disaster shall require an automatic fire-extinguishing system to be installed in the entire structure. Retrofit criteria shall be as follows: 1. All installations of automatic fire extinguishing systems and signaling devices shall comply with the current code. 2. Any occupancy that has been damaged as a result of a fire or natural disaster, except for otherwise noted, shall be retrofitted with an automatic fire extinguishing system to the entire building and structure in accordance with the following (a & b) criteria: a. When the estimated value of repair is less than 50 percent of the replacement value of the structure, the damaged portion(s) may be restored to their pre-damaged condition. b. When the estimated value of repair is 50 percent or more of the replacement value of the structure, the entire building shall be retrofitted with an automatic fire extinguishing system. 903.2.25 Retrofit for Essential Services Facilities. When the estimated value of repair contained in the engineering evaluation is more than 30 percent of the replacement value of the structure, the entire building shall be retrofitted with an automatic fire extinguishing system. 903.2.26 Retrofit for Historic Buildings or Structures. The minimum criteria for retrofit of Historic Buildings or Structures shall be included in FMC Section 15.95.070, with due consideration given to the historical rating and nature of the structures. Additional standards and criteria, as noted in the California Code of Regulations and the State of California Historic Building Code, shall apply. Where conflicts exist between the standards contained herein and the State of California Historic Building Code, the Historic Building Code shall govern. 903.2.27 Alterations to existing R-1, R-2, R-2.1 and R-4 Occupancies: Where the gross floor area of a proposed alteration and the gross floor area of any alterations that have been undertaken in a 10 year time period starting from January 1, 2017 that exceeds 50 percent of the existing gross floor area of the building, an automatic fire extinguishing system (AFES) shall be required throughout the entire building. The standard for calculating the size of alteration for determining the threshold for fire sprinkler systems shall be: 1. The square footage of every room being added or altered shall be included in the calculation of total square footage of addition or alteration. 2. The entire square footage of an individual room shall be considered added or altered when at least 50 percent or greater of the linear length of interior wall sheeting or ceiling of any one wall within the room is new, removed, or replaced. 903.3 through 903.3.1.1.1 {CFC text not modified} 903.3.1.1.2 Deleted 903.3.1.1.3 {CFC text not modified} 903.3.1.2 NFPA 13R in Group R Occupancies. Automatic sprinkler system in group R occupancies up to and including 4 stories in height shall be permitted to be installed throughout in accordance with NFPA 13R as amended in Chapter 80 and as follows. The sprinkler system shall include protection in the following areas: garages, carports, bathrooms, concealed spaces, closets, water heater closets, laundry rooms, attic spaces, under walkways, or overhangs, balconies or decks greater than four feet in depth, at each floor under stair landing that is wholly or partially enclosed, and other areas where deemed necessary by the Fire Chief and the Building Official to protect the public health and safety. 903.3.1.2.1 – deleted 903.3.1.2.2 – 903.3.1.3 {CFC text not modified} 903.3.1.3.1 NFPA 13D in Group R-3 Occupancies. An automatic fire sprinkler system shall be installed in all Group R-3 occupancies including garages, detached garages, and other attached rooms. When an Automatic Fire Extinguishing System is required, the system in R-3 occupancies up to 12,000 square feet may be installed to a modified NFPA 13D standard as follows: A modified NFPA 13D system shall include areas such as garages, carports, bathrooms, concealed spaces, closets, water heater closets, laundry rooms and attic spaces, under walkways, overhangs or balconies over four feet in depth, at each floor under stair landing that is wholly or partially enclosed; and meet the following requirements: 1. A one-inch water meter or larger may be required to meet AFES hydraulic calculations. 2. For new residences over 5,000 square feet, hydraulic calculations shall be required for all sprinkler heads in the most remote fire area up to a maximum of four sprinkler heads. For new residences of less than 5,000 square feet, hydraulic calculations shall be required for all sprinkler heads in the most remote area up to a maximum of two sprinkler heads. 3. Five gallons per minute for domestic use shall be added at the domestic and fire water supply split point. 4. In residences with high, sloped, beamed, soffited, cathedral ceilings or smooth flat ceilings greater than nine feet, additional fire sprinkler head discharge calculations may be required. 5. Each system shall have a single control valve arranged to shut off both the domestic and sprinkler systems. 6. In residential sprinkler projects, the fire chief with the concurrence of the building official may grant alternate methods of construction. Exceptions. This section does not apply to: a. Any structure exempt from permit requirements per the currently adopted California Building Code or the California Fire Code is exempt from the requirements for fire sprinklers. b. All exterior decks without roof covering adjacent to R-3 occupancies, unless otherwise required by the Fire Chief or Building Official. This exemption shall not apply to R-3 occupancies in the Wildland Urban Interface. 903.3.2 through 903.3.5.2 {CFC text not modified} 903.3.5.3 Underground water supply. The location of the fire department connection, post indicator valve and the routing of the water supply for multi-building facilities or buildings over 300,000 square feet shall be evaluated on an individual basis. Underground fire lines to the automatic sprinkler risers and fire hydrants to buildings over 300,000 square feet shall have separate loops. The same two points of connection to the public water supply can be utilized with separate piping to each loop of each building. Post Indicator Valve (PIV) shall be located after each backflow preventer and a Fire Department Connection (FDC) sufficient to provide the fire flow demand after the PIV at one point of connection. 903.3.6 {CFC text not modified} 903.3.7 Fire department connections. A fire department connection shall be provided for all buildings, or when the Fire Code Official deems them necessary. The type and location of fire department connections shall be approved by the Fire Code Official. Exception: Group R-3 occupancies less than 12,000 square feet do not require fire department connections. 903.3.8 – 903.3.9 {CFC text not modified} 903.3.10 Floor control valves. Floor control valves and waterflow detection assemblies shall be installed at each floor. An exterior control valve shall be provided for all buildings except Group R, Division 3 occupancies. Exception: Group R-2 without an interior hallway, R-3 and R-3.1. 903.3.11 Underground corrosion protection. A corrosion protection plan, including details and specifications for all ferrous underground piping must be designed and provided by a corrosion engineer certified by the National Association of Corrosion Engineers (NACE) or its equivalent. Exception: underground piping systems with cathodic protection on all ferrous piping. 903.3.12 Control Valves. Control valves and flow switches shall be installed on each floor. All control valves shall be monitored by a Central Station. 903.3.13 Stages. All stages shall be provided with an automatic fire extinguishing system. Such systems shall be provided throughout the stage and in dressing rooms, workshops, storerooms and other accessory spaces contiguous to such stages. 903.3.14 Stairs. An automatic sprinkler system shall be installed in enclosed usable space below or over a stairway in all occupancies. 903.3.15 Speculative Warehousing. The sprinkler system shall be designed to discharge at the following rates: 1. Where clear ceiling heights are 20 feet or less, 0.33 gallons per minute, per square foot, over a minimum area of 3,000 square feet. 2. Where clear ceiling heights are between 20 and 30 feet, 0.495 gallons per minute, per square foot, over a minimum area of 3,000 square feet. 3. Where clear ceiling heights are over 30 feet, 0.60 gallons per minute, per square foot, over a minimum of 3,000 square feet. 903.3.16 Modification to existing automatic fire extinguishing system (AFES). All changes or additions to any existing automatic fire sprinkler systems or underground fire lines must comply with all regulations within this section. 903.4.2 Monitoring. Alarm, supervisory and trouble signals shall be distinctly and descriptively different, transmitted to the control panel, local annunciator and automatically transmitted to an approved central station, remote supervising station, or proprietary supervising station as defined in NFPA 72 and the most current version of Fire Department Standard 25A. When approved by the fire code official, signals may sound an audible signal at a constantly attended location. 903.4.3 Alarms. Approved supervised audible and visual device(s) shall be connected to every automatic sprinkler system. Such sprinkler water-flow alarms devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Audible notification devices shall be provided inside each tenant space in a normally occupied area and on the exterior of the building in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall activate the building fire alarm system. Visible alarm notification appliances shall not be required except when required by Section 907. Group R-3 occupancies shall have local alarms. Local alarms shall be of sufficient intensity to be clearly audible in all bedrooms over background noise levels with all intervening doors closed. 1. An exterior audible and visual alarm shall be installed on the front 1/3 of the building facing public or private street access. 2. Interior alarm devices (minimum DCBL rating of 88) may be recessed into the wall, centrally located between sleeping rooms in hallway. 3. Such alarms shall be audible in all sleeping rooms with doors closed. 903.4.4 Central Station Monitoring. An approved central alarm monitoring company shall mean approved by the State Fire Marshal or a nationally recognized testing laboratory. All alarm transmitting devices and systems shall be installed and maintained in accordance with nationally recognized standards. Valve supervision, water-flow alarm and trouble signals shall be distinctly different and shall be automatically transmitted to an approved central station, remote station or proprietary supervising station as defined by national standards or, when approved by the building official with the concurrence of the fire chief, sound an audible signal at a consistently attended location. Exceptions: a. Underground key or hub valves in roadway boxes provided by the municipality or public utility need not be supervised. b. Monitored systems are not required for Group R, Division 3 occupancies. 903.5 – 903.6 {CFC text not modified} (Ord. 11-2025 § 2, 9-16-25.)

Ask a question about Fremont law

Corpus searches the Fremont sections it holds and shows the ones that match, with their citations. Free, no sign-in.