§ 15.35.160 — Amendment to the 2025 CFC Section 904 (Alternative Automatic Fire-Extinguishing Systems)
Fremont Municipal Code (Fremont Municipal Code current through Ordinance 02-2026 passed May 5, 2026 (Code Publishing Company, codepublishing.com, scraped 2026-11-18)) · Fremont Municipal Code § 15.35.160
Corpus is an independent public-information project, not the official City of Fremont website. Stable reference: corpuslaw.us/code/420ea23e-3224-4009-8b7e-cd1058deae76
15.35.160 Amendment to the 2025 CFC Section 904 (Alternative Automatic Fire-Extinguishing Systems).
Section 904 of the 2025 California Fire Code is amended as follows: 904.1 – 904.3.4 {CFC text not modified} 904.3.5 Monitoring. Where a building fire alarm system is installed, automatic fire-extinguishing systems shall be monitored by the building fire alarm system in accordance with NFPA 72 and Fire Department Standard 25A. 904.4 – 904.15.1.2 {CFC text not modified} 904.16 Ventilating Hood and Duct Systems and Air Handlers. All buildings with an existing or new fire alarm/sprinkler monitoring control panel shall interconnect all hood and duct systems and air handlers over 2000 cfm to the alarm panel. The hood and duct shall report to a central station as a fire condition. Air handlers shall report as a supervisory or trouble condition when the building is provided with fire sprinklers. They shall report as an alarm in buildings without fire sprinklers. (Ord. 11-2025 § 2, 9-16-25.)