For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 15.01.230 — Chapter 5, Section 507.5.1.1—-Hydrants for FDC (standpipe, sprinkler systems and remote connections)

The Code of the City of Wichita, Kansas (Supp. No. 36, Update 1: codified through Ordinance No. 53-088, adopted July 28, 2026) · Wichita City Code § 15.01.230

Corpus is an independent public-information project, not the official City of Wichita website. Stable reference: corpuslaw.us/code/d76657e1-eb13-4df5-a03c-dd119b647eb9

Sec. 15.01.230. - Chapter 5, Section 507.5.1.1—-Hydrants for FDC (standpipe, sprinkler systems and remote connections).

Chapter 5, Section 507.5.1.1 of the International Fire Code, 2024 Edition, is amended to read as follows: 507.5.1.1 Hydrants for FDC (standpipe, sprinkler systems and remote connections). Buildings equipped with FDC's (standpipe, sprinkler system and/or remote connections) installed in accordance with Section 905 shall have a fire hydrant within 150 feet (45,720 mm) of the fire departments connection. The required hydrant shall be no closer than 40 feet (12,192 mm) to the structure. The required hydrant shall be no closer than 5 feet to the remote connection. Exception: The distance shall be permitted to exceed 150 feet (45,720 mm) where approved by the fire code official.

(Ord. No. 52-878, § 23, 1-13-26)