Sec. 15.01.310. - Chapter 9, Section 903.2.9 amended—Group S-1.
Chapter 9, Section 903.2.9 of the International Fire Code, 2024 Edition, is amended to read as follows: 903.2.9 Group S-1 An automatic sprinkler system shall be provided throughout all buildings containing a Group S-1 occupancy where one of the following conditions exists: 1. A Group S-1 fire area exceeds 12,000 square feet (1,115 m 2 ). Exception: A Group II or III aircraft hangar, as defined by NFPA 409, used of storage of aircraft only when the fire area exceeds 18,000 square feet (1,672 m 2 ). See Section 412.3.6.2 for fire area allowances for ancillary uses. 2. A Group S-1 fire area is located more than three stories above grade plane. 3. The combined area of all Group S-1 fire areas on all floors, including any mezzanines, exceeds 24,000 square feet (2,230 m 2 ). 4. A Group S-1 fire area used for the storage of commercial motor vehicles where the fire area exceeds 5,000 square feet (464 m 2 ). 5. A Group S-1 fire area used for the storage of lithium-ion or lithium metal powered vehicles where the fire area exceeds 500 square feet (46.4 m 2 ).
(Ord. No. 52-878, § 31, 1-13-26)