Sec. 15.01.360. - Chapter 9, Section 910.2.1 amended—Group F-1 and S-1.

Chapter 9, Section 910.2.1 of the International Fire Code, 2024 Edition, is amended to read as follows: 910.2.1 Group F-1 and S-1 Smoke and heat vents installed in accordance with Section 910.3 or a mechanical smoke removal system installed in accordance with Section 910.4 shall be installed in buildings and portions there of used as Group F-1 or S-1 occupancy having more than 50,000 square feet (4,645 m 2 ) of undivided area. In occupied portions of a building equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 where the upper surface of the story is not a roof assembly, a mechanical smoke removal system in accordance with Section 910.4 shall be installed. Exceptions: 1. Group S-1 aircraft repair hangars. 2. Areas completely separated by non-combustible partitions so that no one area exceeds 50,000 square feet (4,645 m 2 ). Openings shall be provided with approved automatic or self-closing devices to enclosure of the opening.