Chapter 10, Section 1008.3.2 of the International Fire Code, 2024 Edition, is amended to read as follows: 1008.3.2 Illumination level under emergency power Emergency lighting facilities shall be arranged to provide initial illumination that is not less than an average of 1 foot-candle (11 lux) and a minimum at any point of 0.1 foot-candle (1 lux) measured along the path of egress at floor level. Illumination levels shall be permitted to decline to 0.6 foot-candle (6 lux) average and a minimum at any point of 0.06 foot-candle (0.6 lux) at the end of the emergency lighting time duration. A maximum-to-minimum illumination uniformity ratio of 40 to 1 shall not be exceed. In Group I-2 occupancies, failure of single lamp in a luminaire shall not reduce the illumination level to less than 0.2 foot-candle (2.2 lux). Exception: Emergency lighting facilities shall be arranged at intervals not to exceed 50 feet (15,240 mm) on center or 25 feet (7,620 mm) in any one direction along the path or egress. Obstructions or changes in direction or exit travel shall be considered the conclusion of the emergency light facility.
(Ord. No. 52-878, § 42, 1-13-26)
Ask a question about Wichita law
Corpus searches the Wichita sections it holds and shows the ones that match, with their citations. Free, no sign-in.