Chapter 10, Section 1012.10 of the International Fire Code, 2024 Edition, is amended to read as follows: 1012.10 Edge protection Edge protection complying with Section 1012.10.1 or 1012.10.2 shall be provided on each side of ramp runs and at each side of ramp landings. Exceptions: 1. Edge protection is not required on ramps that are not required to have handrails, provided they have flared sides that comply with the Americans with Disabilities Act Accessibility Guidelines Sec. 406.3. 2. Edge protection is not required on the sides of ramp landings serving an adjoining ramp run of stairway. 3. Edge protection is not required on the sides of ramp landings having a vertical drop off of not more than ½ inch (12.7 mm) within 10 inches (254 mm) horizontally of the required landing area.