§ 15.01.270 — Chapter 9, 901.4.7.3 incorporated—Environment

The Code of the City of Wichita, Kansas (Supp. No. 36, Update 1: codified through Ordinance No. 53-088, adopted July 28, 2026) · Wichita City Code § 15.01.270

Corpus is an independent public-information project, not the official City of Wichita website. Stable reference: corpuslaw.us/code/a32f6753-7ea2-4395-9853-2d8e10e4c685

Sec. 15.01.270. - Chapter 9, 901.4.7.3 incorporated—Environment.

Chapter 9, Section 901.4.7.3 of the International Fire Code, 2024 Edition, is incorporated to read as follows: 901.4.7.3 Environment Automatic sprinkler system riser rooms and fire pump rooms shall be maintained at a temperature of not less than 40 degrees. Heating units shall be permanently installed (non-switched). Exterior riser rooms shall have low-temperature detection connected to the fire alarm system.

(Ord. No. 52-878, § 27, 1-13-26)