Sec. 15.01.300. - Chapter 9, Table 903.2.8 amended—Group R.
Chapter 9, Table 903.2.8 of the International Fire Code, 2024 Edition, is amended to read as follows: 903.2.8 Group R An automatic sprinkler system installed in accordance with Section 903.3 shall be provided throughout all buildings with a Group R fire area. Exceptions: 1. One- or two-family dwelling unit. 2. Dwelling units in three- and four-family dwellings separated from each other by wall and/or floor assemblies having not less than a 2-hour fire-resistance rating. Fire resistance-rated floor/ceiling and wall assemblies shall extend to and be tight against an exterior wall, and wall assemblies shall extend from the foundation to the underside of the roof sheathing. The roof shall be a minimum of class C roof covering, and the roof decking or sheathing is of non-combustible materials or approved fire-retardant-treated wood for a distance of 4 feet (1,219 mm) on each side of the wall or walls. There shall be no penetrations through this area of the roof deck or sheathing. Where buildings, or portions thereof, are arranged above or below adjacent units, and automatic sprinkler system shall be provided throughout all units.
(Ord. No. 52-878, § 30, 1-13-26)