Sec. 15.01.280. - Chapter 9, 903.2.1.2 amended—Group A-2.

Chapter 9, Section 903.2.1.2 of the International Fire Code, 2024 Edition, is amended to read as follows: 903.2.1.2 Group A-2 An automatic sprinkler system shall be provided throughout stories containing Group A-2 occupancies and throughout all stories from the Group A-2 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists: 1. The fire area exceeds 5,000 square feet (464 m 2 ). 2. The fire area has an occupant load of 100 or more. Exception: The fire area occupant load may go to 299 people if a 3rd exits in accordance with Section 1007.1.2 and Section 1016.2 and a manual fire alarm system that activates an occupant notification system in accordance with Section 907.5 is added that is approved by the fire code official or the building official or the plans examiner reviewing the project. 3. The fire area is located on a floor other than a level of exit discharge serving such occupancies.

(Ord. No. 52-878, § 28, 1-13-26)