§ 3.02 — Amendments to the International Building Code, 2021 edition
Code of Ordinances of the City of Allen, Texas (Codified through Ordinance No. 4212-2-26, adopted February 10, 2026 (Supp. No. 23)) · Allen Land Development Code § 3.02
Corpus is an independent public-information project, not the official City of Allen website. Stable reference: corpuslaw.us/code/c14f4986-f7e2-4156-bb4d-67b3ff5cd8c3
Sec. 3.02 - Amendments to the International Building Code, 2021 edition.
The following amendments to the International Building Code, 2021 edition, as adopted pursuant to section 3.01, are hereby adopted: 1. Section 101.4 is amended to read as follows: 101.4 Referenced codes. The other codes listed in Sections 101.4.1 through 101.4.9 and referenced elsewhere in this code, when specifically adopted, shall be considered part of the requirements of this code to the prescribed extent of each such reference. Whenever amendments have been adopted to the referenced codes and standards, each reference to said code and standard shall be considered to reference the amendments as well. Any reference to NFPA 70 or the ICC Electrical Code shall mean the Electrical Code as adopted. 2. Section 101.4 is amended by adding Sections 101.4.8 and 101.4.9 to read as follows: 101.4.8 Electrical. The provisions of the Electrical Code shall apply to the installation of electrical systems, including alterations, repairs, replacement, equipment, appliances, fixtures, fittings, and appurtenances thereto. 101.4.9 Swimming Pools and Spas. The provisions of the International Swimming Pool and Spa Code shall apply to the construction, alteration, movement, renovation, replacement, repair and maintenance of aquatic recreation facilities. 3. Sections 103 and 103.1 are amended by replacing the phrase "Department of Building Safety" with the phrase "Building Inspections Department" where it appears. 4. Section [A]104.2.1 is amended by adding the following language after the phrase "Section 1612" in the last sentence: … 104.10.1, and applicable provisions of Article V of the ALDC and the Code of Ordinance. 5. Section 105.2 is amended to read as follows: 105.2 Work exempt from permit. Exemptions from permit requirements of this code shall not be deemed to grant authorization for any work to be done in any manner in violation of the provisions of this code or any other laws or ordinances of this jurisdiction. Permits shall not be required for the following: Building: 1. Water tanks supported directly upon grade if the capacity does not exceed 5,000 gallons (18,925 L) and the ratio of height to diameter or width does not exceed 2 to 1. 2. Sidewalks and driveways not more than 30 inches (762 mm) above adjacent grade, and not over any basement or story below and which are not part of an accessible route or part of the exit discharge and the placement and/or location of concrete does not violate other city requirement. 3. Window awnings supported by an exterior wall of Group R-3, as applicable in Section 101.2, and Group U occupancies. (IRC) 4. One-story detached accessory structures used as tool and/or storage sheds, playhouses and similar uses provided the floor area does not exceed 120 square feet or the height does not exceed 8 feet and the placement of the structure does not violate any other city requirements such as, but not limited to, placement of any structure in the Private Drainage Easement (PDE). (IRC) 5. Flag Poles installed on a parcel where the primary use is a single-family dwelling, two family dwelling or townhome provided the installation does not exceed the height requirements for the residential zoning district where located as specified in the ALDC. (IRC) 6. Residential swimming or wading pools that are temporary in nature and less than 24 inches in depth and do not require nor are provided mechanical circulation or heating equipment of any kind. (IRC) 7. Replacement of residential windows meeting the requirements of the International Energy Code that does not require a modification of the structural opening and does not reduce the requirements for Emergency Escape and Rescue Openings as provided for in the International Residential Code. (IRC) 6. Section 109.2 is amended by adding Section 109.2.1 to read as follows: Section 109.2.1 Plan Review Fees. When submittal documents are required by Section 109.1, a plan review fee shall be paid at the time of submitting the submittal documents for plan review. Said plan review fee shall be as established by resolution of the City Council from time to time. The plan review fees are in addition to the permit fees. 7. Section 109 is amended by adding new Sections 109.7, 109.8, 109.8.1, 109.8.2, and 109.9 to read as follows: 109.7 Re-inspection fee. A reinspection fee as established by resolution of the city council may be charged when: 1. The inspection called for is not ready when the inspector arrives. 2. No building address or permit card is clearly posted. 3. City approved plans are not on the job site available to the inspector. 4. The building is locked or work otherwise not available for inspection when called. 5. The job site is red tagged twice consecutively for the same item. 6. The original red tag has been removed from the job site and/or, 7. Violations exist on the property including failure to maintain erosion control, trash control or tree protection. 8. Any re-inspection fees assessed shall be paid before any more inspections are made on that job site. 109.8 Work without permit. 109.8.1 Investigation. Whenever work for which a permit is required by this code has been commenced without first obtaining a permit, a special investigation shall be made before a permit may be issued for such work. 109.8.1 Fee. An investigation fee, in addition to the permit fee, shall be collected whether or not a permit is subsequently issued. The investigation fee shall be equal to the amount of the permit fee required by this code or the city fee schedule as applicable, the payment of such investigation fee shall not exempt the applicant from compliance with all other provisions of either this code or the technical codes nor from the penalty described by law. 109.9 Unauthorized cover up fee. Any work concealed without first obtaining the required inspection in violation of section 110 shall be assessed a fee established by the city fee schedule. 8. Section 110.3.5 is amended by deleting the "Exception." 9. Section 116.5 is amended by adding a new Section 116.5.1 to read as follows: 116.5.1 Damage or renovations to existing structures. When a structure is renovated or is damaged to 50% of the gross floor area or if the value of the damage or renovation exceeds 50% of the value of the structure at the time of damage or renovation all requirements of this Code shall be complied with in any such repair, reconstruction, or renovation. 10. Section 202 is amended by amending the definitions of "Ambulatory Care Facility," "High-Rise Building," "Repair Garage," and "Special Inspector" and adding a definition for the phrase "Assisted Living Facilities" to read as follows: AMBULATORY CARE FACILITY. Buildings or portions thereof used to provide medical, surgical, psychiatric, nursing, or similar care on a less than 24-hour basis to individuals who are rendered incapable of self-preservation by the services provided. This group may include but not be limited to the following: - Dialysis centers - Sedation dentistry - Surgery centers - Colonic centers - Psychiatric centers ASSISTED LIVING FACILITIES. A building or part thereof housing persons, on a 24-hour basis, who because of age, mental disability or other reasons, live in a supervised residential environment which provides personal care services. The occupants are capable of responding to an emergency situation without physical assistance from staff. HIGH-RISE BUILDING. A building with an occupied floor located more than 55 feet (16764 mm) above the lowest level of fire department vehicle access. REPAIR GARAGE. A building, structure or portion thereof used for servicing or repairing motor vehicles. This occupancy shall also include garages involved in minor repair, modification and servicing of motor vehicles for items such as lube changes, inspections, windshield repair or replacement, shocks, minor part replacement and other such minor repairs. SPECIAL INSPECTOR. A qualified person employed or retained by an approved agency who shall prove to the satisfaction of the registered design professional in responsible charge and the Building Official as having the competence necessary to inspect a particular type of construction requiring special inspection. 11. Section 303.1.3 is amended by to read as follows: 303.1.3 Associated with Group E occupancies. A room or space used for assembly purposes that is associated with a Group E occupancy is not considered a separate occupancy except when applying the assembly requirements of Chapter 10 and 11. 12. Section 304.1 is amended to add the following to the list of occupancies, to read as follows: - Fire stations - Police stations with detention facilities for 5 or less 13. Section 307.1.1. Paragraph 4 is amended to read as follows: 4. Cleaning establishments … (text unchanged) … with Section 707 or 1-hour horizontal assemblies constructed in accordance with Section 711 or both. See also IFC Chapter 21, Dry Cleaning Plant. 14. Section 402.4.2.1 Tenant Separations is amended as follows: Each tenant space shall be separated from other tenant spaces by a fire partition wall sheet rocked on both sides and complying with Section 708. Exception: Existing conditions shall be subject to field inspection and reviewed for Approval at that time. 15. Section 403.1 is amended by amending paragraph 3 under "Exceptions" to read as follows: 3. The open-air portion of a building with a Group A-5 occupancy in accordance with Section 303.6. 16. Section 403.3.2 is amended to read as follows: (F)403.3.2 Water supply to required fire pumps. In buildings that are more than 120 feet (36.5 m) in building height, required fire pumps shall be supplied by connections to no fewer than two water mains located in different streets. Separate supply piping shall be provided between each connection to the water main and the pumps. Each connection and the supply piping between the connection and the pumps shall be sized to supply the flow and pressure required for the pumps to operate. (No change to exception) 17. Section 403.3 is amended by deleting the exception. 18. Section 506.2 is amended by deleting footnote "i" to Table 506.2. 19. Section 708.4.2 is amended by amending paragraph 1 under "Exceptions" to read as follows: Exceptions: 1. Buildings equipped with an automatic sprinkler system installed throughout in accordance with Section 903.3.1.1, or in accordance with Section 903.3.1.2 provided that sprinkler protection is provided in the space between the top of the fire partition and the underside of the floor or roof sheathing, deck or slab above as required for systems complying with Section 903.3.1.1. Portions of buildings containing concealed spaces filled with noncombustible insulation as permitted for sprinkler omission shall not apply to this exception for draft stopping. 20. Section 901.6.1 is amended by adding Section 901.6.1.1, to read as follows: 901.6.1.1 Standpipe Testing. Building owners/managers must maintain and test standpipe systems as per NFPA 25 requirements. The following additional requirements shall be applied to the testing that is required every 5 years. 1. The piping between the Fire Department Connection (FDC) and the standpipe shall be back flushed or inspected by approved camera when foreign material is present or when caps are missing, and also hydrostatically tested for all FDC's on any type of standpipe system. Hydrostatic testing shall also be conducted in accordance with NFPA 25 requirements for the different types of standpipe systems. 2. For any manual (dry or wet) standpipe system not having an automatic water supply capable of flowing water through the standpipe, the tester shall connect hose from a fire hydrant or portable pumping system (as approved by the fire code official) to each FDC, and flow water through the standpipe system to the roof outlet to verify that each inlet connection functions properly. Confirm that there are no open hose valves prior to introducing water into a dry standpipe. There is no required pressure criteria at the outlet. Verify that check valves function properly and that there are no closed control valves on the system. 3. Any pressure relief, reducing, or control valves shall be tested in accordance with the requirements of NFPA 25. All hose valves shall be exercised. 4. If the FDC is not already provided with approved caps, the contractor shall install such caps for all FDC's as required by the fire code official. 5. Upon successful completion of standpipe test, place a blue tag (as per Texas Administrative Code, Fire Sprinkler Rules for Inspection, Test and Maintenance Service (ITM) Tag) at the bottom of each standpipe riser in the building. The tag shall be check-marked as "Fifth Year" for Type of ITM, and the note on the back of the tag shall read "5 Year Standpipe Test" at a minimum. 6. The procedures required by Texas Administrative Code Fire Sprinkler Rules with regard to Yellow Tags and Red Tags or any deficiencies noted during the testing, including the required notification of the local Authority Having Jurisdiction (fire code official) shall be followed. 7. Additionally, records of the testing shall be maintained by the owner and contractor, if applicable, as required by the State Rules mentioned above and NFPA 25. 8. Standpipe system tests where water will be flowed external to the building shall not be conducted during freezing conditions or during the day prior to expected nighttime freezing conditions. 9. Contact the fire code official for requests to remove existing fire hose from Class II and III standpipe systems where employees are not trained in the utilization of this firefighting equipment. All standpipe hose valves must remain in place and be provided with an approved cap and chain when approval is given to remove hose by the fire code official. 21. Section 903.1.1 is amended to read as follows: (F)903.1.1 Alternative protection. Alternative automatic fire-extinguishing systems complying with Section 904 shall be permitted in addition to automatic sprinkler protection where recognized by the applicable standard, or as approved by the fire code official. 22. Section 903.2 is amended to read as follows: (F)903.2 Where required. Approved automatic sprinkler systems in new buildings and structures shall be provided in the locations described in Section 903.2.1 through 903.2.12. Automatic sprinklers shall not be installed in elevator machine rooms, elevator machine spaces, and elevator hoist ways, other than pits where such sprinklers would not necessitate shunt trip requirements under any circumstances. Storage shall not be allowed with the elevator machine room. Signage shall be provided at the entry doors to the elevator machine room indicating "ELEVATOR MACHINERY - NO STORAGE ALLOWED." 23. Section 903.2 is amended by deleted the paragraph titled "Exception." 24. Section 903.2.9 is amended by adding Section 903.2.9.3 to read as follows: (F)903.2.9.3 Self-service storage facility. An automatic sprinkler system shall be installed throughout all self-service storage facilities. 25. (F)Section 903.2.11.3 is amended to read as follows: 903.2.11.3 Buildings over 35 feet in height. An automatic sprinkler system shall be installed throughout buildings that have one or more stories, other than penthouses in compliance with Section 1510 of the International Building Code, that is located 35 feet (10668 mm) or more above the lowest level of fire department vehicle access, measured to the finished floor. Exception: Open parking structures in compliance with Section 406.5 of the International Building Code, having no other occupancies above the subject garage. 26. Section 903.2.11 is amended by adding Sections 903.2.11.7, 903.2.11.8, and 903.2.11.9 to read as follows: 903.2.11.7 High-piled combustible storage. For any building with a clear height exceeding 12 feet (4572 mm) see Chapter or 32 to determine if those provisions apply. 903.2.11.8 Spray booths and rooms. New and existing spray booths and spraying rooms shall be protected by an approved automatic fire-extinguishing system. 903.2.11.9 Buildings over 6,000 square feet. An automatic sprinkler system shall be installed throughout all buildings with a building area over 6,000 square feet, and in all existing buildings that are enlarged to be 6,000 square feet or greater. For the purpose of this provision, fire walls shall not define separate buildings. Exception: Open parking garages in compliance with Section 406.5 of the International Building Code. 27. Section 903.3.1.1.1 is amended to read as follows: (F)903.3.1.1.1 Exempt locations. When approved by the fire code official, automatic sprinklers shall not be required in the following rooms or areas where such (intervening text unchanged) because it is damp, of fire-resistance-rated construction or contains electrical equipment. 1. Any room where the application of water, or flame and water, constitutes a serious life or fire hazard. 2. Any room or space where sprinklers are considered undesirable because of the nature of the contents, when approved by the code official. 3. Generator and transformer rooms, under the direct control of a public utility, separated from the remainder of the building by walls and floor/ceiling or roof/ceiling assemblies having a fire-resistance rating of not less than 2 hours. 4. Elevator machine rooms, machinery spaces and hoist ways, other than pits where such sprinklers would not necessitate shunt trip requirements under any circumstances. 28. Section 903.3.1.2 is amended by adding Section 903.3.1.2.3 to read as follows: (F)903.3.1.2.3 Attached Garages and Attics. Sprinkler protection is required in attached garages, and in the following attic spaces: 10. (Remainder Unchanged) 11. (Remainder Unchanged) 12. Attic spaces of buildings of combustible construction and that are two or more stories in height above grade plane or above the lowest level of fire department vehicle access. 13. Group R-4, Condition 2 occupancy attics not required by item 1 or 3 to have sprinklers shall comply with one of the following; (Remainder Unchanged) 29. Section 903.3.1.3 is amended to read as follows: (F)903.3.1.3 NFPA 13D sprinkler systems. Automatic sprinkler systems installed in one- and two-family dwellings; Group R-3; Group R-4 Condition 1 and townhouses shall be permitted to be installed throughout in accordance with NFPA 13D or in accordance with state law. 30. Section 903.3.4 is amended by adding a new Section 903.3.1.4 to read as follows: (F)903.3.1.4 Freeze protection. Freeze protection systems for automatic fire sprinkler systems shall be in accordance with the requirements of the applicable referenced NFPA standard and this section. 903.3.1.4.1 Attics. Only dry-pipe, pre-action, or listed automatic fire sprinkler systems shall be allowed to protect attic spaces. Exception: Wet-pipe fire sprinkler systems shall be allowed to protect non-ventilated attic spaces where: 1. The attic sprinklers are supplied by a separate floor control valve assembly to allow ease of draining the attic system without impairing sprinklers throughout the rest of the building, and 2. Adequate heat shall be provided for freeze protection as per the applicable referenced NFPA standard, and 3. The attic space is a part of the building's thermal, or heat, envelope, such that insulation is provided at the roof deck, rather than at the ceiling level. 903.3.1.4.2 Heat trace/insulation. Heat trace/insulation shall only be allowed where approved by the fire code official for small sections of large diameter water-filled pipe. 31. Section 903.3.5 is amended by adding the following sentence to the end of the section: Water supply as required for such systems shall be provided in conformance with the supply requirements of the respective standards; however, every water-based fire protection system shall be designed with a 10 psi safety factor. Reference Section 507.4 for additional design requirements. 32. Section 903.4 is amended by adding the following paragraph after "Exceptions": Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds. All control valves in the sprinkler and standpipe systems except for fire department hose connection valves shall be electrically supervised to initiate a supervisory signal at the central station upon tampering. 33. Section 903.4.2 is amended by adding the following sentence at the end of the section: The alarm device required on the exterior of the building shall be weatherproof horn/strobe notification appliance with a minimum 75 candela strobe rating, installed as close as practicable to the fire department connection. 34. Section 905.2 is amended to read as follows: 905.2 Installation standard. Standpipe systems shall be installed in accordance with this section and NFPA 14 Manual dry standpipe systems shall be supervised with a minimum of 10 psig and a maximum of 40 psig air pressure with a high/low alarm. 35. Section 905.3 is amended by adding Section 905.3.9, to read as follows: 905.3.9 Building area. In buildings exceeding 10,000 square feet in area per story, and where any portion of the building's interior area is more than 200 feet (60960 mm) of travel, vertically and horizontally, from the nearest point of fire department vehicle access. Class I automatic wet or manual wet standpipes shall be provided. Exceptions: 1. Automatic dry and semi-automatic standpipes are allowed as provided for in NFPA 14. 2. R-2 occupancies of four stories or less in height having no interior corridors. 36. Section 905.4, Paragraphs 1, 3, and 5 are amended to read as follows: 1. In every required exit stairway, a hose connection shall be provided for each story above and below grade plane. Hose connections shall be located at an intermediate landing between stories, unless otherwise approved by the fire code official. 3. In every exit passageway, at the entrance from the exit passageway to other areas of a building. Exception: Where floor areas adjacent to an exit passageway are reachable from an exit stairway hose connection by a (remainder unchanged). 5. Where the roof has a slope less than four unit's vertical in 12 unit's horizontal (33.3-percent slope), each standpipe shall be provided with a two-way hose connection located to serve the roof or at the highest landing of an exit stairway with stair access to the roof provided in accordance with Section 1011.12. 37. Section 905.4 is amended by adding a new Paragraph 7 to read as follows: 7. When required by this Chapter, standpipe connections shall be placed adjacent to all required exits to the structure and at two hundred feet (200') intervals along major corridors thereafter, or as indicated by the fire code official. 38. Section 905.9 is amended by adding the following paragraph after "Exceptions": Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds. All valves in the sprinkler and standpipe systems except for fire department hose connection valves shall be electrically supervised to initiate a supervisory signal at the central station upon tampering. 39. Section 907.1 is amended by adding Section 907.1.4 to read as follows: 907.1.4 Design standards. Where a new fire alarm system is installed, the devices shall be addressable. Fire alarm systems utilizing more than 20 smoke detectors shall have analog addressable. 40. Section 907.2.1 is amended to read as follows: 907.2.1 Group A. A manual fire alarm system that activates the occupant notification system in accordance with Section 907.5 shall be installed in Group A occupancies having an occupant load of 300 or more persons or more than 100 persons above or below the lowest level of exit discharge. Group A occupancies not separated from one another in accordance with 707.3.10 of the International Building Code shall be considered as a single occupancy for the purposes of applying this section. Portions of Group E occupancies occupied for assembly purposes shall be provided with a fire alarm system as required for the Group E occupancy. Activation of fire alarm notification appliances shall: 1. Cause illumination of the means of egress with light of not less than 1 foot-candle (11 lux) at the walking surface level, and 2. Stop any conflicting or confusing sounds and visual distractions. ("Exception" remains unchanged) 41. Section 907.2.3 is amended by amending the first paragraph to read as follows: 907.2.3 Group E. A manual fire alarm system that initiates the occupant notification signal utilizing an emergency voice/alarm communication system meeting the requirements of Section 907.5.2.2 and installed in accordance with Section 907.6 shall be installed in Group E educational occupancies. When automatic sprinkler systems or smoke detectors are installed, such systems or detectors shall be connected to the building fire alarm system. An approved smoke detection system shall be installed in Group E day care occupancies. Unless separated by a minimum of 100' open space, all buildings, whether portable buildings or the main building, will be considered one building for alarm occupant load consideration and interconnection of alarm systems. 42. Section 907.2.3 is amended by amending Paragraph 1 under "Exceptions" to read as follows: Exceptions: 1. A manual fire alarm system is not required in Group E educational and day care occupancies with an occupant load of less than 50 when provided with an approved automatic sprinkler system. 1.1. Residential In-Home day care with not more than 12 children may use interconnected single station detectors in all habitable rooms. (For care of more than five children 2 1/2 or less years of age, see Section 907.2.6.) 43. Section 907.2.10.1 is amended to read as follows: Section 907.2.10.1 Group R-1. Single- or multiple-station smoke alarms and carbon monoxide alarms shall be installed and maintained in all the following locations in Group R-1: (Paragraphs 1, 2, and 3 remain unchanged) 4. For new construction, an approved carbon monoxide alarm shall be installed outside of each separate sleeping area in the immediate vicinity of the bedrooms in dwelling units that have an attached garage or gas fired appliance. 5. Where work requiring a permit occurs in existing dwellings that have attached garages or gas fired appliances; carbon monoxide alarms shall be provided. 44. Section 907.2.10.2 is amended to read as follows: Section 907.2.11.2 Groups R-2, R-3, R-4 and I-1. Single-or multiple-station smoke alarms and carbon monoxide alarms shall be installed and maintained in Groups R2, R-3, R-4 and I-1 regardless of occupant load at all the following locations: (Paragraphs 1, 2, and 3 remain unchanged) 4. For new construction, an approved carbon monoxide alarm shall be installed outside of each separate sleeping area in the immediate vicinity of the bedrooms in dwelling units that have an attached garage or gas fired appliances. 5. Where work requiring a permit occurs in existing dwellings that have attached garages or gas fired appliances carbon monoxide alarms shall be provided. 45. Section 907.2.13 is amended by replacing exception 3 to read as follows: 3. Open air portions of buildings with an occupancy in Group A-5 in accordance with Section 303.1 of the International Building Code; however, this exception does not apply to accessory uses including but not limited to sky boxes, restaurants, and similarly enclosed areas as determined by the building official. 46. Section 907.4.2 is amended by adding Section 907.4.2.7, to read as follows: 907.4.2.7 Type. Manual alarm initiating devices shall be an approved double action type. 47. Section 907.6.1 is amended by adding Section 907.6.1.1, to read as follows: 907.6.1.1 Wiring installation. All fire alarm systems shall be installed in such a manner that a failure of any single initiating device or single open in an initiating circuit conductor will not interfere with the normal operation of other such devices. All signaling line circuits (SLC) shall be installed in such a way that a single open will not interfere with the operation of any addressable devices (Class A). Outgoing and return SLC conductors shall be installed in accordance with NFPA 72 requirements for Class A circuits and shall have a minimum of four feet separation horizontal and one-foot vertical between supply and return circuit conductors. The initiating device circuit (IDC) from a signaling line circuit interface device may be wired Class B, provided the distance from the interface device to the initiating device is ten feet or less. 48. Section 907.6.3 is amended by deleting all four Exceptions. 49. Section 907.6.6 is amended by adding the following sentence at the end of the paragraph: See 907.6.3 for the required information transmitted to the supervising station. 50. Section 910.2 is amended by amending paragraphs 2 and 3 under "Exceptions" to read as follows: 2. Only manual smoke and heat removal shall be required in areas of buildings equipped with early suppression fast-response (ESFR) sprinklers. Automatic smoke and heat removal is prohibited. 3. Only manual smoke and heat removal shall be required in areas of buildings equipped with control mode special application sprinklers with a response time index of 50 (meters-seconds) ½ or less that are listed to control a fire in stored commodities with 12 or fewer sprinklers. Automatic smoke and heat removal is prohibited. 51. Section 910.2 is amended by adding Sections 910.2.3 to read as follows: 910.2.3 Group H. Buildings and portions thereof used as a Group H occupancy as follows: 1. In occupancies classified as Group H-2 or H-3, any of which are more than 15,000 square feet (1394 m2) in single floor area. Exception: Buildings of noncombustible construction containing only noncombustible materials. 2. In areas of buildings in Group H used for storing Class 2, 3, and 4 liquid and solid oxidizers, Class 1 and unclassified detonable organic peroxides, Class 3, and 4 unstable (reactive) materials, or Class 2, or 3 water-reactive materials as required for a high-hazard commodity classification. Exception: Buildings of noncombustible construction containing only noncombustible materials. 52. Section 910.3 is amended by adding Section 910.3.4; to read as follows: 910.3.4 Vent operation. Smoke and heat vents shall be capable of being operated by approved automatic and manual means. Automatic operation of smoke and heat vents shall conform to the provisions of Sections 910.3.2.1 thru 910.3.2.3 (F)910.3.4.1 Sprinklered buildings. Where installed in buildings equipped with an approved automatic sprinkler system, smoke and heat vents shall be designed to operate automatically. The automatic operating mechanism of the smoke and heat vents shall operate at a temperature rating at least 100 degrees F (approximately 38 degrees Celsius) greater than the temperature rating of the sprinklers installed. Exception: Manual only system per Section 910.2. (F)910.3.4.2 Non-Sprinklered buildings. Where installed in buildings not equipped with an approved automatic sprinkler system, smoke and heat vents shall operate automatically by actuation of a heat-responsive device rated at between 100ºF (56ºC) and 220ºF (122ºC) above ambient. Exception: Listed gravity-operated drop out vents. 53. Section 910.4.3.1 is amended to read as follows: (F)Section 910.4.3.1 Makeup air. Makeup air openings shall be provided within 6 feet (1829 mm) of the floor level. Operation of makeup air openings shall be automatic. The minimum gross area of makeup air inlets shall be 8 square feet per 1,000 cubic feet per minute (0.74 m 2 per 0.4719 m 3 /s smoke exhaust. 54. Section 910.4.4 is amended to read as follows: (F)Section 910.4.4 Activation. The mechanical smoke removal system shall be activated automatically by the automatic sprinkler system or by an approved fire detection system. Individual manual controls shall also be provided. Exception: Manual only systems per Section 910.2. 55. Section 912.2 is amended by adding Section 912.2.3 to read as follows: [F] 912.2.3 Hydrant distance. An approved fire hydrant shall be located within 100 feet of the fire department connection as the fire hose lays along an unobstructed path. 56. Section 913.2.1 is amended by adding Section 913.2.1.1 with Exception to read as follows: Section 913.2.1.1 Fire Pump Room Access. When located on the ground level at an exterior wall, the fire pump room shall be provided with an exterior fire department access door that is not less than 3 feet in width and 6 feet - 8 inches in height, regardless of any interior doors that are provided. A key box shall be provided at this door, as required by IFC Section 506.1. Exception: When it is necessary to locate the fire pump room on other levels or not at an exterior wall, the corridor leading to the fire pump room access from the exterior of the building shall be provided with equivalent fire resistance as that required for the pump room, or as approved by the Fire Code official. Access keys shall be provided in the key box as required by Section 506.1 57. Section 913.4 is amended by adding the following sentence at the end of the section: The fire-pump system shall also be supervised for "loss of power," "phase reversal," and "pump running" conditions by supervisory signal on district circuits. 58. Section 1006.2.2 is amended by adding Section 1006.2.2.7 to read as follows: 1006.2.2.7 Electrical rooms. For electrical rooms, special exiting requirements may apply. Reference the Electrical Code as adopted. 59. Section 1009.1 is amended by adding a new paragraph 4 under "Exceptions": 4. Buildings regulated under State law and built in accordance with State registered plans, including any variances or waivers granted by the State, shall be deemed to be in compliance with the requirements of Section 1009. 60. Section 1009.8 is amended by adding Exception 7 to read as follows: 7. Buildings regulated under State Law and built-in accordance with State registered plans, including variances or waivers granted by the State, shall be deemed to be in compliance with the requirements of Section 1009 and Chapter 11. 61. Section 1010.2.5 is amended by amending Exceptions 3, and 4 to read as follows: 3. Where a pair of doors serves an occupant load of less than 50 persons in a Group B, F, M, or S occupancy … (Remainder unchanged) 4. Where a pair of doors serves a Group A, B, F, M, or S occupancy. (Remainder unchanged) 62. Section 1015.8 is amended to read as follows: 1. Operable windows where the top of the sill of the opening is located more than 55 feet (16764 mm) above the finished grade or other surface below and that are provided with window fall prevention devices that comply with ASTM F2006. 63. Section 1020.2 is amended by adding Exception 6 to read as follows: 6. In Group B occupancies, corridor walls and ceilings need not be of fire-resistive construction within a single tenant space when the space is equipped with approved automatic smoke-detection within the corridor. The actuation of any detector shall activate self-annunciating alarms audible in all areas within the corridor. Smoke detectors shall be connected to an approved automatic fire alarm system where such system is provided. 64. Section 1020.7 is amended to read as follows: 1020.7 Corridor continuity. All corridors shall be continuous from the point of entry to an exit and shall not be interrupted by intervening rooms. 65. Section 1030.1.1.1 is deleted. 66. Section 1101.1 is amended by adding an "Exception" to read as follows: Exception: Components of projects regulated by and registered with Architectural Barriers Division of Texas Department of Licensing and Regulation shall be deemed to be in compliance with the requirements of this chapter. 67. Table 1505.1 is amended by amending footnote "b" to read as follows and deleting footnote "c." b. Non-classified roof coverings shall be permitted on buildings of U occupancies having not more than 120 square feet of projected roof area. When exceeding 120 square feet of projected roof area, buildings of U occupancies may use non-rated non-combustible roof coverings. 68. Section 1511.1 is amended by amending the first paragraph to read as follows: 1511.1 General. Materials and methods of applications used for recovering or replacing an existing roof covering shall comply with the requirements of Chapter 15. All individual replacement shingles shall be in compliance with the rating required by Table 1505.1. (Exception text unchanged) 69. Section 2211.1 is amended by adding paragraph 5 to read as follows: 5. All framed walls top plates must be braced and supported by structural members to ceiling steel or roof at 6' (foot) on center spacing. (Lay in grid is not a structural support). 70. 2702 is amended by adding the section 2702.5 to read as follows: 2702.5 Designated critical operations areas (DCOA) in areas within a facility or site requiring continuous operation for the purpose of public safety, emergency management, national security or business continuity, the power systems shall comply with NFPA 70 Article 708. 71. Section 2901.1 is amended by adding the following sentences: The provisions of this Chapter are meant to work in coordination with the provisions of Chapter 4 of the International Plumbing Code. Should any conflicts arise between the two chapters, the Building Official shall determine which provision applies. 72. Section 2902.1 is amended by adding the following sentence: In other than E Occupancies, the minimum number of fixtures in Table 2902.1 may be requested in writing, by the applicant stating reasons for a reduced number and approved by the Building Official. 73. Section 2902.1 is amended by adding footnote "g" to read as follows: g. Drinking fountains are not required in M Occupancies with an occupant load of 100 or less, B Occupancies with an occupant load of 25 or less, and for dining and/or drinking establishments. 74. Section 2902.1 is amended by adding Section 2902.1.4 to read as follows: 2902.1.4 Additional fixtures for food preparation facilities. In addition to the fixtures required in the Chapter, all food service facilities shall be provided with additional fixtures set out in this section. 2902.1.4.1 Hand washing lavatory. At least one hand washing lavatory shall be provided for use by employees that is accessible from food preparation, food dispensing and ware washing areas. Additional hand washing lavatories may be required based on convenience of use by employees. 2902.1.4.2 Service sink. In new or remodeled food service establishments, at least one service sink or one floor sink shall be provided so that it is conveniently located for the cleaning of mops or similar wet floor cleaning tool and for the disposal of mop water and similar liquid waste. The location of the service sink(s) and/or mop sink(s) shall be approved by the Building Official or health department. 75. Section 2902.2.2 is amended by deleting exception 6. 76. Section 3001.2 is deleted. 77. Section 3002.1 is amended by adding Exceptions 1 and 2 to read as follows: 1. Elevators completely located within atriums shall not require hoist way enclosure protection. 2. Elevators in open or enclosed parking garages that serve only the parking garage, shall not require hoistway enclosure protection. 78. Section 3005.4 is amended to read in its entirety as follows: Section 3005.4 Machine rooms, control rooms, machinery spaces and control spaces. Elevator machine rooms, control rooms, control spaces, and machinery spaces shall be enclosed with fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both. The fire-resistance rating shall be not less than the required rating of the hoistway enclosure served by the machinery. Openings in the fire barriers shall be protected with assemblies having a fire protection rating not less than required for the hoistway enclosure door. Exceptions: 1. Elevator machine rooms, control rooms, machinery spaces and control spaces completely located within atriums shall not require enclosure protection. 2. Elevator machine rooms, control rooms, machinery spaces and control spaces in open or enclosed parking garages that serve only the parking garage, shall not require enclosure protection. 79. Section 3005 is amended by adding Section 3005.7 and Section 3005.8 to read as follows: 3005.7 Fire protection in machine rooms, control rooms, machinery spaces and control spaces. 3005.7.1 Automatic sprinkler system. The building shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, except as otherwise permitted by Section 903.3.1.1.1 and as prohibited by Section 3005.7.2.1. 3005.7.2.1 Prohibited locations. Automatic sprinkler shall not be installed in machine rooms, elevator machinery spaces, control rooms, control spaces and elevator hoistways. 3005.7.2.2 Sprinkler system monitoring. The sprinkler system shall have a sprinkler control valve supervisory switch and water flow initiating device provided for each floor that is monitored by the building's fire alarm system. 3005.7.3 Water protection. An approved method to prevent water from infiltrating into the hoistway enclosure from the operation of the automatic sprinkler system outside the elevator lobby shall be provided. 3005.7.4 Shunt trip. Means for elevator shutdown in accordance with Section 3005.5 shall not be installed. 3005.8 Storage. Storage shall not be allowed within the elevator machine room, control room, machinery spaces and/or control spaces. Provide approved signage at each entry to the above listed locations stating: "No Storage Allowed." 80. Section 3006.2 is amended by amending paragraph 5 to read as follows: 5. The building is a high rise and the elevator hoist way is more than 55 feet (16764 mm) in height. The height of the hoist way shall be measured from the lowest floor at or above grade to the highest floors served by the hoist way.
(Ord. No. 3919-6-22, § 1, 6-14-2022)
Ask a question about Allen law
Corpus searches the Allen sections it holds and shows the ones that match, with their citations. Free, no sign-in.