§ 3.04 — Amendments to the International Fire Code, 2021 edition
Code of Ordinances of the City of Allen, Texas (Codified through Ordinance No. 4212-2-26, adopted February 10, 2026 (Supp. No. 23)) · Allen Land Development Code § 3.04
Corpus is an independent public-information project, not the official City of Allen website. Stable reference: corpuslaw.us/code/878e9998-737e-4a90-989c-067af0702286
Sec. 3.04. - Amendments to the International Fire Code, 2021 edition.
The following amendments to the International Fire Code, 2021 edition, as adopted pursuant to section 3.01, are hereby adopted: 1. Section 102.1 is amended by amending Item 3 to read as follows: 3. Existing structures, facilities and conditions when required in Chapter 11 or in specific Sections of this code. 2. Sections 103.1, and 103.2 are amended to read as follows: 103.1 General. The Fire Code shall be enforced by the Division of Fire Prevention. The Division of Fire Prevention is hereby established as a division of the Fire Department of the City of Allen and shall operate under the supervision of the Chief of the Fire Department. 103.2 Appointment. The Assistant Fire Chief of Prevention is in charge of the Division of Fire Prevention and shall be appointed by the Fire Chief on the basis of proper qualification. (remainder of Section unchanged) 3. Section 104.1 is amended by adding Section 104.1.1 to read as follows: 104.1.1 Code Official. For the purpose of this code, "Code Official" shall mean the Fire Chief or his designated representative(s). 4. Section 105.1 is amended by adding Section 105.1.7 to read as follows: 105.1.7 Failure to obtain permit or working without a permit. Any person who fails to obtain a permit or is conducting work without a permit approved by the Allen Fire Department shall be liable to a fee of two (2) times the required permit fee figured in accordance with the fee schedule adopted by resolution of the city council. A minimum fee of one-hundred twenty dollars ($120.00) in addition to the required permit fee will be assessed. Working without a permit shall include non-compliance of Sections 105.3.5 and 105.4.6. 5. Section 105.2.3 is amended by adding Section 105.2.3.1 as follows: 105.2.3.1 Time limitation of application. Reinstatement of expired permits will require the applicant to resubmit permit application and required documents and shall be liable for applicable permit fees. 6. Section 105.3.3 is amended to read as follows: 105.3.3 Occupancy Prohibited before Approval. The building or structure shall not be occupied prior to the Fire Code Official issuing a permit, when required, and conducting associated inspections indicating the applicable provisions of this code have been met. No building or structure shall be used or occupied, and no change in the existing occupancy classification of a building or structure or portion thereof shall be made, until the Building Official has issued a Certificate of Occupancy. 7. Section 105.6 is amended to read as follows: 105.6 Required construction permits. The code official is authorized to issue construction permits for work set forth in Sections 105.6.1 to 105.6.24. 8. Section 105.6.11 is amended to read as follows: 105.6.11 Gates and barricades across fire apparatus access roads. A construction permit shall be required to install any system that during normal operation delays or prevents entry to, or obstructs a fire lane or street into, the premises of a residential or commercial area. 9. Section 105.6 is amended by adding Section 105.6.25 to read as follows: 105.6.25 Electronic access control systems. Construction permits are required to install or modify an electronic access control system, as specified in Chapter 10. A separate construction permit is required to install or modify a fire alarm system that may be connected to the access control system. Maintenance performed in accordance with this code is not considered a modification and does not require a permit. For the purpose of this section, electronic access control devices utilized for controlling ingress, egress, or both, shall be permitted. Additionally, electronic access control devices which allow for free egress shall also be permitted. 10. Section 105 is amended by adding Section 105.7 to read as follows: 105.7 Permit and other fees. Fees for each permit required, plan reviews, inspections, re-inspections, other regulatory storage/handling, and equipment use or process established by resolution of the city council from time to time and made a part of the City's Fee Schedule shall be paid prior to the issuance of such permit, performance of such service, or use of such equipment. 11. Section 106.4 is amended to read as follows: 106.4 Retention of construction documents. One set of construction documents shall be retained by the Fire Code Official until final approval of the work covered therein. One set of approved construction documents shall be returned to the applicant, and said set, along with the Fire Department Permit shall be kept on site of the building or work at all times during which the work authorized thereby is in progress. Construction documents shall be retained by the installing company as required by the Texas State Fire Marshal's Office, after final approval of work covered therein. 12. Section 107.3 Permit Valuations is deleted in its entirety. 13. Section 108.2 is amended by adding Section 108.2.3 to read as follows: 108.2.3 Inspection of existing premises. The Fire Chief, or designated representative, shall inspect all buildings, premises, or portion thereof as often as may be necessary. An initial inspection and one (1) re-inspection shall be made free of charge. If the Fire Chief or his designee is required to make follow-up inspections after the initial inspection and re-inspection to determine whether a violation or violations observed during the previous inspection have been corrected, a fee shall be charged. The occupant, lessee, or person making use of the building or premises shall pay said fee or fees within thirty (30) days of being billed as a condition to continue lawful occupancy of the building or premises. Fees for follow-up inspections after initial and re-inspection shall be as set forth in the fee schedule as adopted by resolution of the city council. Recurring violations from year to year will result in issuance of a citation and shall not be restricted to the inspection and re-inspection procedure as indicated in this Section. 14. Section 112.4 is amended to read as follows: 112.4 Violation Penalties. Any person, firm, or corporation violating any of the provisions or terms of this Article or Code adopted herein or shall fail to comply with any of the requirements thereof or who shall erect, install, alter, repair or do work in violation of the approved construction documents or directive of the fire code official, or of a permit or certificate used under the provisions of this code shall be guilty of a misdemeanor and, upon conviction in the Municipal Court of the City of Allen, shall be subject to a fine not to exceed two thousand and no/100 dollars ($2,000.00) for each offense. Each and every day any such violation shall continue shall be deemed to constitute a separate offense. 15. Section 113.4 is amended to read as follows: 113.4 Failure to comply. Any person who shall continue any work after having been served with a stop work order, except such work as that person is directed to perform to remove a violation or unsafe condition, shall be liable to a fine of not more than two thousand and no/100 ($2,000.00) dollars for each offense, and each and every day such violation shall continue shall be deemed to constitute a separate offense. 16. Section 202 is amended by adding definitions for the phrases "ADDRESSABLE FIRE DETECTION SYSTEM," "ANALOGUE ADDRESSABLE FIRE DETECTION SYSTEM," "DEFENDING IN PLACE," "SELF-SERVICE STORAGE FACILITY," "STANDBY PERSONNEL," and "UPGRADED OR REPLACED FIRE ALARM SYSTEM" to read as follows: ADDRESSABLE FIRE DETECTION SYSTEM. Any system capable of providing identification of each individual alarm-initiating device. The identification shall be in plain English and as descriptive as possible to specifically identify the location of the device in alarm. The system shall have the capability of alarm verification. ANALOG ADDRESSABLE FIRE DETECTION SYSTEM. Any system capable of calculating a change in value by directly measurable quantities (voltage, resistance, etc.) at the sensing point. The physical analog may be conducted at the sensing point or at the main control panel. The system shall be capable of compensating for long-term changes in sensor response while maintaining a constant sensitivity. The compensation shall have a preset point at which a detector maintenance signal shall be transmitted to the control panel. The sensor shall remain capable of detecting and transmitting an alarm while in maintenance alert. DEFEND IN PLACE. A method of emergency response that engages building components and trained staff to provide occupant safety during an emergency. Emergency response involves remaining in place, relocating within the building, or both, without evacuating the building. SELF-SERVICE STORAGE FACILITY. Real property designed and used for the purpose of renting or leasing individual storage spaces to customers for the purpose of storing and removing personal property on a self-service basis. STANDBY PERSONNEL. Qualified fire service personnel approved by the Fire Chief. When utilized, the number required shall be as directed by the Fire Chief. Charges for utilization shall be as normally calculated by the jurisdiction. UPGRADED OR REPLACED FIRE ALARM SYSTEM. A fire alarm system that is upgraded or replaced includes, but is not limited to the following: 1. Replacing one single board or fire alarm control unit component with a newer model. 2. Installing a new fire alarm control unit in addition to or in place of an existing one. 3. Conversion from a horn system to an emergency voice/alarm communication system. 4. Conversion from a conventional system to one that utilizes addressable or analog devices. 5. The following are not considered an upgrade or replacement: 1. Firmware updates 2. Software updates 3. Replacing boards of the same model with chips utilizing the same or newer firmware 17. Section 202 is amended by amending the definitions of "AMBULATORY HEALTH CARE FACILITY," "ATRIUM," "FIRE WATCH," "FIREWORKS," "HIGH-PILED COMBUSTIBLE STORAGE," "HIGH RISE BUILDING," AND "REPAIR GARAGE" to read as follows: AMBULATORY HEALTH CARE FACILITY. Buildings or portions thereof used to provide medical, surgical, psychiatric, nursing, or similar care on a less than 24-hour basis to individuals who are rendered incapable of self-preservation. This group may include but not be limited to the following: a. Dialysis centers b. Procedures involving sedation c. Sedation dentistry d. Surgery centers e. Colonic centers f. Psychiatric centers ATRIUM. An opening connecting three or more stories … (remaining text unchanged) FIRE WATCH. A temporary measure intended to ensure continuous and systematic surveillance of a building or portion thereof by one or more qualified individuals or standby personnel when required by the Fire Code Official, for the purposes of identifying and controlling fire hazards, detecting early signs of unwanted fire, raising an alarm of fire and notifying the Fire Department. FIREWORKS. Any composition or device for the purpose of producing a visible or an audible effect for entertainment purposes by combustion, deflagration, or detonation, and/or activated by ignition with a match or other heat producing device that meets the definition of 1.4G fireworks or 1.3G fireworks as set forth herein. (remainder of text unchanged) HIGH-PILED COMBUSTIBLE STORAGE. add a second paragraph to read as follows: Any building or portion of building used for storage classified as a group S Occupancy or Speculative Building exceeding 6,000 square feet that has a clear height in excess of 14 feet, making it possible to be used for storage in excess of 12 feet, shall be considered to be high-piled storage. When a specific product cannot be identified; a fire protection system and life safety features shall be installed as for Group A cartooned, non-expanded plastics, to the maximum pile height. HIGH-RISE BUILDING. A building with an occupied floor located more than 55 feet (16,764 mm)above the lowest level of Fire Department vehicle access. REPAIR GARAGE. A building, structure or portion thereof used for servicing or repairing motor vehicles. This occupancy shall also include garages involved in minor repair, modification and servicing of motor vehicles for items such as lube changes, inspections, windshield repair or replacement, shocks, minor part replacement, and other such minor repairs. 18. Section 307.1.1 is amended to read as follows: 307.1.1 Prohibited Open Burning. Open burning that is offensive or objectionable because of smoke or emissions or when atmospheric conditions or local circumstances make such fires hazardous shall be prohibited. Exception: (No change) 19. Section 307.2 is amended to read as follows: 307.2 Permit required. A permit shall be obtained from the Fire Code Official in accordance with Section 105.6 prior to kindling a fire for recognized silvicultural, range, or wildlife management practices, prevention or control of disease or pests, or open burning. Application for such approval shall only be presented by, and permits issued to the owner of, the land upon which the fire is to be kindled. Examples of state, local law, or regulations referenced elsewhere in this Section may include but not be limited to the following: 1. Texas Commission on Environmental Quality (TCEQ) guidelines and/or restrictions; 2. State, County, or Local temporary or permanent bans on open burning; and 3. Local written policies as established by the Fire Code Official. 20. Section 307.3 is amended to read as follows: 307.3 Extinguishing Authority. The fire code official is authorized to order the extinguishment by the permit holder, another person responsible or the fire department of open burning that creates or adds to a hazardous or objectionable situation. 21. Section 307.4 is amended to read as follows: 307.4 Location. The location for open burning shall not be less than 300 feet (91,440 mm) from any structure, and provisions shall be made to prevent the fire from spreading to within 300 feet (91,440 mm) of any structure. Exceptions: (No change) 22. Section 307.4.1 is amended to read as follows: 307.4.1 Bonfires. A bonfire shall not be conducted within 50 feet (15,240 mm), or greater distance as determined by the Fire Code Official, or a structure or combustible material, unless the fire is contained in a barbecue pit. Conditions that could cause a fire to spread within the required setback of a structure shall be eliminated prior to ignition. 23. Section 307.4.3 is amended by adding a new paragraph 2 under "Exceptions" to read as follows: 2. Where buildings, balconies, and decks are protected by an approved automatic sprinkler system. 24. Section 307.4 is amended by adding Section 307.4.4 and Section 3.7.5 to read as follows: 307.4.4 Permanent Outdoor Firepits or Fire feature Devices. Permanently installed outdoor firepits and similar fire feature devices, manufactured and non-manufactured, shall not be installed within 10 feet of a structure or combustible material. Exceptions: 1. Permanent outdoor firepits of fire feature devices listed less than 100,000 BTU/hr shall not be installed within 10 feet of combustible materials (vertically and horizontally). 2. Permanently installed outdoor fireplaces constructed in accordance with the International Building Code. 307.4.4.1 Solid Fuels. All solid fuels are strictly prohibited for firepits and fire feature devices. Exception: One- and two-family dwellings. 307.4.4.2 Requirements for all firepits or fire feature devices. Comply with all of the following Requirements: 1. Flame shall be fully enclosed by an approved permanent means to prevent debris from entering the fire and the prevent occupants from becoming burned; 2. Provide an emergency fuel gas supply line shut-off device at least 20 feet from the firepit device location but not greater than 50 feet. Provide emergency fuel gas shut-off device signage clearly visible from firepit or fire feature device locations; 3. Floor surface shall be a solid continuous non-combustible material without any gaps and all joints sealed; and 4. Time device on fuel gas line set to automatically shut-off gas supply and extinguishes flame at a set time agreed upon by the Fire Code Official. 307.4.5 Trench Burns. Trench burns shall be conducted in air curtain trenches and in accordance with Section 307.2. 25. Section 307.5 is amended to read as follows: 307.5 Attendance. Open burning, trench burns, bonfires, or recreational fires and use of portable outdoor fireplaces shall be constantly attended until the … (remainder of Section unchanged) 26. Section 308.1.4 is amended to read as follows: 308.1.4 Open-flame cooking devices. Open-flame cooking devices, charcoal grills, and other similar devices used for cooking shall not be located or used on combustible balconies, decks, or within 10 feet (3,048 mm) of combustible construction. Exceptions: 1. One- and two-family dwellings, except that LP-gas containers are limited to a water capacity not greater than 50 pounds (22.68 kg) [nominal 20-pound (9.08 kg) LP-gas capacity] with an aggregate LP-gas capacity not to exceed 100 lbs. (5 containers); 2. Where buildings, balconies, and decks are protected by an approved automatic sprinkler system, except that LP-gas containers are limited to a water capacity not greater than 50 pounds (22.68 kg) [nominal 20-pound (9.08 kg) LP-gas capacity], with an aggregate LP-gas capacity not to exceed 40 lbs. (2 containers); and 3. LP-gas cooking devices having LP-gas container with a water capacity not greater than 2½ pounds [nominal 1 pound (0.454 kg) LP-gas capacity]. 27. Section of 308.1.4 is amended by adding Section 308.1.4.1 to read as follows: 308.1.4.1 Burning of refuse prohibited. The burning of refuse in a barbeque grill or open-flame cooking device is not an approved method for refuse disposal, is declared a public nuisance, and is prohibited anywhere in the City of Allen. Refuse shall mean and include garbage, rubbish, and trade waste defined as follows: Garbage. Garbage shall mean animal and vegetable matter such as that originating in houses, kitchens, restaurants, hotels, produce markets, food service, or processing establishments, greenhouses, hospitals, clinics, or veterinary facilities. Rubbish. Rubbish shall mean solids not considered to be highly flammable or explosive such as, but not limited to, rags, old clothes, leather, rubber, carpets, wood, excelsior, paper, ashes, tree branches, yard trimmings, furniture, metal food containers, glass, crockery, masonry, and other similar materials. Trade Waste. Trade waste shall mean all solid or liquid material resulting from construction, building operations, or the prosecution, or any business, trade, or industry such as, but not limited to, plastic products, cinders, and other forms of solid, or liquid waste materials. Materials Producing Dense Smoke Prohibited. The burning of rubber, asphaltic materials, combustible, and flammable liquids, impregnated wood, or similar materials which produce dense smoke are considered objectionable, a hazard, a public nuisance to the community, and are strictly prohibited. 28. Section 308.1.6.2 is amended by amending paragraph number 3 under "Exceptions" to read as follows: 3. Torches or flame-producing devices in accordance with Section 308.1.3. 29. Section 308.1.6.3 is amended to read as follows: 308.1.6.3 Sky Lanterns. A person shall not release or cause to be released an unmanned free-floating device containing an open flame or other heat source, such as but not limited to a sky lantern. 30. Section 311.5 is amended to read as follows: 311.5 Placards. The Fire Code Official is authorized to require marking of any vacant or abandoned buildings or structures determined to be unsafe pursuant to Section 110 of this code relating to structural or interior hazards, as required by Section 311.5.1 through 311.5.5. 31. Section 401.3 is amended by adding Section 401.3.4 to read as follows: 401.3.4 Fire Alarms and Nuisance Alarms. False alarms and nuisance alarms shall not be given, signaled, transmitted, caused, permitted to be given, signaled, or transmitted in any manner. 32. Section 403. is amended to read as follows: 403. Group E Occupancies. An approved fire safety and evacuation plan in accordance with Section404 shall be prepared and maintained for Group E occupancies and for buildings containing both a Group E occupancy, and an atrium. A diagram depicting two evacuation routes shall be posted in a conspicuous location in each classroom. Group E occupancies shall also comply with Sections 403..1 through 403..3. 33. Section 404.2.2 is amended by adding subparagraph 4.10 under paragraph to read as follows: 4.10 Fire extinguishing system controls. 34. Section 405.54 is amended to read as follows: 405.54 Time. The fire code official may require an evacuation drill at any time. Drills shall be held at unexpected times and under varying conditions to simulate the unusual conditions that occur in case of fire. Exceptions: 1. (No Change) 2. (No Change) 3. Notification of teacher/staff having supervision of light- or sound-sensitive students/occupants, such as those on the autism spectrum, for the protection of those students/occupants, shall be allowed prior to conducting a drill. 35. Section 501.4 is amended to read as follows: 501.4 Timing of installation. When fire apparatus access roads or a water supply for fire protection is required to be installed for any structure or development, they shall be installed, tested, and approved prior to the time of which construction has progressed beyond completion of the foundation of any structure. 36. Section 503.1.1 is amended to read as follows: 503.1.1 Buildings and facilities. Approved fire apparatus … (intervening text unchanged) … building or facility. Except for one- or two-family dwellings, the path of measurement shall be along a minimum of a ten feet (10') wide unobstructed pathway around the external walls of the structure. ("Exception" remains unchanged) 37. Section 503.2.1 is amended to read as follows: 503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 24 feet (7,315 mm), exclusive of shoulders, except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 14 feet (4,267 mm). Any such fire lane or fire apparatus access road shall either connect both ends to a dedicated street or be provided with a turnaround having a minimum outer radius of 50 feet. If two or more interconnecting fire lanes are provided, the interior radius for that connection shall be required to be in accordance with the following: 1. For 90 degrees or greater turns only: a. 24-foot fire lane — 30-foot inside turning radius b. 30-foot fire lane — 10-foot inside turning radius 2. For turns tighter than 90 degrees: American Association of State and Highway Transportation Officials (AASHTO) Geometric design of Highways and Streets shall be utilized. Exception: Vertical clearance may be reduced; provided such reduction does not impair access by fire apparatus and approved signs are installed and maintained indicating the established vertical clearance when approved. 38. Sections 503.2.2 is amended to read as follows: 503.2.2 Authority. The Fire Code Official shall have the authority to require an increase in the minimum access widths and vertical clearances where they are inadequate for fire or rescue operations. 39. Section 503.2.3 is amended to read as follows: 503.2.3 Surface. Fire apparatus access roads shall be designed and maintained to support imposed loads of 95,000 Lbs. for fire apparatus and shall be surfaced so as to provide all-weather driving capabilities. All fire lanes shall be constructed to meet the City of Allen Engineering Standards. 40. Section 503.2.5 is amended to read as follows: 503.2.5 Dead ends. Dead end fire apparatus access roads are not permitted. An approved Fire Department vehicle access turn-around shall be required. 41. Section 503.3 is amended to read as follows: 503.3 Marking. Striping, signs, or other markings, when approved by the Fire Code Official, shall be provided for fire apparatus access roads to identify such roads, or prohibit the obstruction thereof. Striping, signs, and other markings shall be maintained in a clean and legible condition at all times and are replaced or repaired when necessary to provide adequate visibility. 1. Striping. Fire apparatus access roads shall be continuously marked by painted lines of red traffic paint six inches (6") in width to show the boundaries of the lane. The words "NO PARKING FIRE LANE" or "FIRE LANE NO PARKING" shall appear in four inch (4") white letters at 25 feet intervals on the red border markings along both sides of the fire lanes. Where a curb is available, the striping shall be on the vertical face of the curb. 2. Signs. Signs shall read "NO PARKING FIRE LANE" or "FIRE LANE NO PARKING" and shall be 12" wide and 18" high. Signs shall be painted on a white background with letters and borders in red, using not less than 2" lettering. Signs shall be permanently affixed to a stationary post and the bottom of the sign shall be six feet, six inches (6'6") above finished grade. Signs shall be spaced not more than fifty feet (50') apart along both sides of the fire lane. Signs may be installed on permanent buildings or walls or as approved by the Fire Chief. 42. Section 503.4 is amended to read as follows: 503.4 Obstruction of fire apparatus access roads. Fire apparatus access roads shall not be obstructed in any manner, including the parking of vehicles, whether attended or unattended for any period of time. Persons in charge of a construction project, such as, but not limited to, a General Contractor, are responsible to ensure that fire apparatus access roads are kept clear of vehicles and other obstructions at all times and may be issued a citation for non-compliance under this section. The minimum widths and clearances established in Section 503.2.1 and any area marked as a fire lane as described in Section 503.3 shall be maintained at all times. The Fire Chief and Police Chief, and their designated representatives, are authorized to remove or cause to be removed any material, vehicle, or object obstructing a fire apparatus access road at the expense of the owner of such material, vehicle, or object. 503.4.1 Obstruction and Control. No owner or person in charge of any premises served by a fire lane or access easement shall abandon, restrict, or close any fire lane or easement without first securing from the City approval of an amended plat or other acceptable legal instrument showing the removal of the fire lane. 503.4.2 Speed control devices. Speed bumps or other similar obstacles designed to slow the speed of traffic and that have the effect of slowing or impeding the response of fire apparatus shall require a permit as required in Section 105.7 of this code prior to installation. Speed control devices shall be constructed out of concrete, by approved molded plastic, or a similar material. 43. Section 503.6 is amended to read as follows: 503.6 Security Gates. The installation of security gates or other devices intended to limit the access of vehicles or persons shall comply with the Fire Marshal's Office established written policy statement. 44. Section 504 is amended by adding Section 504.4 to read as follows: 504.4 Fire Riser/Pump Room. Access to fire riser rooms and fire pump rooms shall be from the exterior of the building for which they serve. Interior access is not permitted. Fire riser rooms and fire pump rooms shall maintain temperatures of 40-90 o F, and fire pump rooms shall also maintain adequate air flow based on the requirements set forth by the fire pump manufacturer. 45. Section 505.1 is amended to read as follows: 505.1 Address identification. New and existing buildings shall be provided with approved address identification. The address identification shall be legible and placed in a position that is visible from the street or road fronting the property. Address identification characters shall contrast with their background. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Each character shall be not less than 6 inches (152.4 mm) high with a minimum stroke width of ½ inch (12.7 mm). Where required by the fire code official, address numbers shall be provided in additional approved locations to facilitate emergency response. Where access is by means of a private road, buildings do not immediately front a street, and/or the building cannot be viewed from the public way a monument, pole or other sign with approved 6-inch (152.4 mm) height building numerals or addresses and 4-inch (101.6 mm) height suite/apartment numerals of a color contrasting with the background of the building or other approved means shall be used to identify the structure. Numerals or addresses shall be posted on a minimum 20-inch (508 mm) by 30-inch (762 mm) background on border. Address identification shall be maintained. 505.1.1 Single Family Homes. R-3 Single Family occupancies shall have approved numerals of a minimum 4" high, 5/8" stroke and a color contrasting with the background clearly visible and legible from the street fronting the property and rear alleyway where such alleyway exists. 505.1.2 Multifamily Communities. Street Address shall be a minimum of 12" high with a 2" stroke. Individual building numbers shall be a minimum of 18" high with a 3" stroke. Buildings over 100 feet in length require a minimum of two (2) numbers per building. Apartment spread numbers shall be a minimum of 7" high with a one-inch stroke and corridor spread numbers shall be a minimum of 4" high with a 5/8" brush stroke. Individual apartment unit numbers shall be a minimum of 4" in height with a 5/8" stroke. 505.1.3 Large Office and Warehouse Buildings. Address must be visible from all access directions. Number shall be a minimum of 24" in height with a 4" stroke. Buildings over 500 feet long shall have two address locations if more than one access point is visible. Suite numbers shall be required for multi-tenant complexes and shall be located over the front door and on the rear door, 6" in height with a 1" brush stroke. 505.1.4 Shopping Centers, High Rise Buildings, and Other Applications. A minimum of 12" high numbers with a 2" brush stroke shall be visible from all access directions. Suite numbers are required over the door with 4" high numbers with a 5/8" brush stroke. Buildings beyond 100 feet from the street and 10,000 square feet shall install 18" numbers with a 3" stroke. 505.1.5 Marquee and Monument. Addresses installed on a marquee located next to the street will require numbers 12" high with a 2" brush stroke to be located a minimum of 3 feet above grade. Marquee and Monument signs must meet City of Allen Sign Ordinance Requirements. 46. Section 505 is amended by adding Section 505.3 to read as follows: 505.3 Directional/Equipment ID Signage. Directional and equipment identification signage may be required by the code official and shall meet the requirements as set forth in the Fire Marshal's Office written policy statement as outlined in the most current version of the Allen Fire Marshal's Office Sign Book. 47. Section 506.1 is amended by adding the following sentence at the end of the section: All new and existing occupancies, except single-family residences, shall provide (a) lock box(es) as specified in the Fire Marshal's Office written policy statement. 48. Section 507.4 is amended to read as follows: 507.4 Water supply test date and information. The water supply test used for hydraulic calculation of fire protection systems shall be conducted in accordance with NFPA 291 "Recommended Practice for Fire Flow Testing and Marking of Hydrants" and within one year of sprinkler plan submittal. The Fire Code Official shall be notified prior to the water supply test. Water supply tests shall be witnessed by the Fire Code Official, as required. The exact location of the static/residual hydrant and the flow hydrant shall be indicated on the design drawings. All fire protection plan submittals shall be accompanied by a hard copy of the waterflow test report, or as approved by the Fire Code Official. The report must indicate the dominant water tank level at the time of the test and the maximum and minimum operating levels of the tank, as well, or identify applicable water supply fluctuation. The licensed contractor must then design the fire protection system based on this fluctuation information, as per the applicable referenced NFPA standard. Reference Section 903.3.5 for additional design requirements. 49. Section 507.5.1 is amended to read as follows: 507.5.1 Where required. As properties develop, fire hydrants shall be located at all intersecting streets and at the maximum spacing indicated in Table 507.5.1. Distances between hydrants shall be measured along the route that fire hose is laid by a fire vehicle from hydrant to hydrant. TABLE 507.5.1 MAXIMUM DISTANCE BETWEEN HYDRANTS OCCUPANCY | SPRINKLERED | NOT SPRINKLERED Residential (1 & 2 Family) | 600 feet | 500 feet Residential (Multi-Family) | 400 feet | 300 feet All Other | 500 feet | 300 feet There shall be a minimum of two (2) fire hydrants serving each property within the prescribed distance listed in Table 507.5.1. Protected Properties. Fire Hydrants shall be installed along fire lanes with spacing as required for street installations specified in 507.5.1. In addition, hydrants required to provide supplemental water supply for automatic fire protection systems shall be within 100 feet of the Fire Department connection (FDC) for such systems. 50. Section 507.5.4 is amended to read as follows: 507.5.4 Obstruction. Unobstructed access to fire hydrants shall be maintained at all times. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, Fire Department inlet connections or fire protection system control valves in a manner that would prevent such equipment or fire hydrants from being immediately discernible. The Fire Department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. 51. Section 507.5 is amended by adding Sections 507.5.7 through 507.5.16 to read as follows: 507.5.7 Fire Hydrant Type. All hydrants shall be of the three-way type with National Standard threads, breakaway construction, minimum 5¼" valve opening and shall comply with the latest AWWA specification C-502. The hydrant shall have a 4½" large connection with two 2½" side connections and shall be placed on water mains of no less than six inches (6") in size. Fire hydrants shall be Mueller "Centurion" or approved equal. All new hydrants shall come from the manufacturer with a silver powder coated and bonnet. Once installed, they shall be painted in accordance with Section 507.5.16. 507.5.8 Valves. Valves shall be placed on all fire hydrants leads. 507.5.9 Breakaway point. Fire hydrants shall be installed so that the breakaway point is no less than three (3) inches, and no greater than five (5) inches above the grade surface. 507.5.10 Curb Line. Fire hydrants shall be located a minimum of two (2) feet and a maximum of six (6) feet behind the curb line. No fire hydrant shall be placed in a cul-de-sac or the turning radius of fire lanes. 507.5.11 Positioning. All fire hydrants shall be installed so that the 4½" connection will face the fire lane or street. 507.5.12 Limiting Access Obstruction. Fire hydrants, when placed at intersections or access drives to parking lots, shall be placed so that the minimum obstruction of the intersection or access drive will occur when the hydrant is in use. 507.5.13 Private Property. Fire hydrants located on private property shall be accessible to the Fire Department at all times. All fire hydrants placed on private property shall be adequately protected by either curb stops, concrete posts or other approved methods. Such stops shall be the responsibility of the landowner on which the fire hydrant is installed. 507.5.14 Location to Building. Fire hydrants shall not be located closer than 50' to a building or height of building + 10'. 507.5.15 Identification. An approved blue, two-sided reflector shall be utilized to identify each hydrant location. The reflector shall be affixed to the center line of each roadway or fire access lane opposite fire hydrants. 507.5.16 Color. Fire hydrant caps and bonnet shall be painted according to the water main size to which it is attached (see Table 507.5.16). The remainder of the hydrant above ground shall be painted silver. TABLE 507.5.16 MAIN SIZE | COLOR 6" | Silver 8" | Blue 10" or greater | Yellow 52. Section 509.1 is amended by adding Section 509.1.2 to read as follows: 509.1.2 Sign Requirements. Unless more stringent requirements apply, lettering for signs required by this Section shall have a minimum height of two (2) inches when located inside a building and four (4) inches when located outside, or as approved by the Fire Code Official. The letters shall be of a color that contrasts with the background. 53. Section 509.2 is amended by adding Section 509.2.1 to read as follows: 509.2.1 Outside electrical disconnect. When electrical disconnects are not readily accessible on the exterior of a building, or an approved electrical room in which the building's main power disconnect does not have exterior access, an approved safety switch or other approved means of electrical disconnect shall be installed in an approved location on the exterior of the building. Knox EPO switches may be utilized. 54. Section 605.4 is amended to read as follows: 605.4 Fuel oil storage systems. Fuel oil storage systems shall be installed and maintained in accordance with this code. Tanks and fuel-oiled piping systems shall be installed in accordance with Chapter 13 of the International Mechanical Code and Chapter 57. 55. Sections 605.4.1 and 605.4.2 are amended to read as follows: 605.4.1 Fuel oil storage in outside, above-ground tanks. Where connected to a fuel-oil piping system, the maximum amount of fuel oil storage allowed outside above ground without additional protection shall be 660 gallons (2498 L). The storage of fuel oil above ground in quantities exceeding 660 gallons (2498 L) shall comply with NFPA 31 and Chapter 57. 605.4.1.1 Approval. Outdoor fuel oil storage tanks shall be in accordance with UL 142 or UL 2085, and also listed as double wall/secondary containment tanks. 605.4.2 Fuel oil storage inside buildings. Fuel oil storage inside buildings shall comply with Sections 605.4.2.2 through 605.4.2.8 and Chapter 57. 605.4.2.1 Approval. Indoor fuel oil storage tanks shall be in accordance with UL 80, UL 142, or UL 2085. 605.4.2.2 Quantity limits. One or more fuel oil storage tanks containing Class II, or III combustible liquid shall be permitted in a building. The aggregate capacity of all tanks shall not exceed the following: 1. 660 gallons (2498 L) in unsprinklered buildings, where stored in a tank complying with UL 80, UL142 or UL2085 for Class III liquids, and also listed as a double wall/secondary containment tank for Class II liquids; 2. 1,320 gallons (4996 L) in buildings equipped with an automatic sprinkler system in accordance with Section 903.3.1.1, where stored in a tank complying with UL 142 or UL 2085 as a double-wall secondary containment tank; and 3. 3,000 gallons (11 356 L) where stored in protected above-ground tanks complying with UL 2085 and Section 5704.2.9.7 and the room is protected by an automatic sprinkler system in accordance with Section 903.3.1.1. 56. Section 807.5.2.2 is amended to read as follows: 807.5.2.2 Artwork in Corridors. Artwork and teaching materials shall be limited on the walls of corridors to not more than 20 percent of the wall area. Such materials shall not be continuous from floor to ceiling or wall to wall. Curtains, draperies, wall hangings, and other decorative material suspended from the walls or ceilings shall meet the flame propagation performance criteria of NFPA 701 in accordance with Section 807 or be noncombustible. Exception: Corridors protected by an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 shall be limited to 50 percent of the wall area. 57. Section 807.5.2.3 is amended to read as follows: 807.5.2.3 Artwork in Classrooms. Artwork and teaching materials shall be limited on walls of classrooms to not more than 50 percent of the specific wall area to which they are attached. Curtains, draperies, wall hangings and other decorative material suspended from the walls or ceilings shall meet the flame propagation performance criteria of NFPA 701 in accordance with Section 807 or be noncombustible. 58. Section 807.5.5.2 is amended to read as follows: Section 807.5.5.2 Artwork in corridors. Artwork and teaching materials shall be limited on the walls of corridors to not more than 20 percent of the wall area. Such materials shall not be continuous from floor to ceiling or wall to wall. Curtains, draperies, wall hangings, and other decorative material suspended from the walls or ceilings shall meet the flame propagations performance criteria of NFPA 701 in accordance with Section 807 or be noncombustible. 59. Section 807.5.5.3 is amended to read as follows: Section 807.5.5.3 Artwork in classrooms. Artwork and teaching materials shall be limited on walls of classrooms to not more than 50 percent of the specific wall area to which they are attached. Curtains, draperies, wall hangings, and other decorative material suspended from the walls or ceilings shall meet the flame propagation performance criteria of NFPA 701 in accordance with Section 807 or be noncombustible. 60. Section 901.6.1 is amended by adding Section 901.6.1.1 to read as follows: 901.6.1.1 Standpipe Testing. Building owners/managers must maintain and test standpipe systems as per NFPA 25 requirements. The following additional requirements shall be applied to the testing that is required every 5 years: 1. The piping between the Fire Department Connection (FDC) and the standpipe shall be hydrostatically tested for all FDC's on any type of standpipe system. Hydrostatic testing shall also be conducted in accordance with NFPA 25 requirements for the different types of standpipe systems. 2. For any manual (dry or wet) standpipe system not having an automatic water supply capable of flowing water through the standpipe, the tester shall connect hose from a fire hydrant or portable pumping system (as approved by the Fire Code Official) to each FDC, and flow water through the standpipe system to the roof outlet to verify that each inlet connection functions properly. Confirm that there are no open hose valves prior to introducing water into a dry standpipe. There is no pressure criteria required at the outlet. Verify that check valves function properly and that there are no closed control valves on the system. 3. Any pressure relief, reducing, or control valves shall be tested in accordance with the requirements of NFPA 25. All hose valves shall be exercised. 4. If the FDC is not already provided with approved caps, the contractor shall install such caps for all FDC's as required by the Fire Code Official. 5. Upon successful completion of standpipe test, place a blue tag (as per "Texas Administrative Code"), Fire Sprinkler Rules for Inspection, Test and Maintenance Service (ITM) Tag) at the bottom of each standpipe riser in the building. The tag shall be check-marked as "Fifth Year" for Type of ITM, and the note on the back of the tag shall read "5 Year Standpipe Test" at a minimum. 6. The procedures required by the Texas Administrative Code Fire Sprinkler Rules with regard to Yellow Tags and Red Tags or any deficiencies noted during the testing, including the required notification of the local Authority Having Jurisdiction (Fire Code Official) shall be followed. 7. Additionally, records of the testing shall be maintained by the owner and contractor, if applicable, as required by the State Rules mentioned above and NFPA 25. 8. Standpipe system tests where water will be flowed external to the building shall not be conducted during freezing conditions or during the day prior to expected night time freezing conditions. 9. Contact the Fire Code Official for requests to remove existing fire hose from Class II and III standpipe systems where employees are not trained in the utilization of this firefighting equipment. All standpipe hose valves must remain in place and be provided with an approved cap and chain when approval is given to remove hose by the Fire Code Official. 61. Section 901.6 is amended by adding Section 901.6.4 to read as follows: 901.6.4 False Alarms and Nuisance Alarms. False alarms and nuisance alarms shall not be given, signaled or transmitted or caused or permitted to be given, signaled or transmitted in any manner. 62. Section 901.7 is amended to read as follows: 901.7 Systems Out of Service. Where a required fire protection system is out of service or in the event of an excessive number of activations, the fire department and the fire code official shall be notified immediately and, where required by the fire code official, the building shall either be evacuated or an approved fire watch shall be provided for all occupants left unprotected by the shut down until the fire protection system has been returned to service. (remaining unchanged) 63. Section 903.1.1 is amended to read as follows: 903.1.1 Alternative protection. Alternative automatic fire-extinguishing systems complying with Section 904 shall be permitted in addition to automatic sprinkler protection where recognized by the applicable standard, or as provided by the Fire Code Official. 64. Section 903.1 is amended by adding Section 903.1.2 to read as follows: 903.1.2 Residential Systems. Unless specifically allowed by this code or the International Building Code, residential sprinkler systems installed in accordance with NFPA 13D or NFPA 13R shall not be recognized for the purpose of exceptions or reductions, commonly referred to as "trade-offs," permitted by other requirements of this code. In addition, residential sprinkler systems installed in accordance with NFPA 13R must include attics, breezeways, and patios. Garage areas must also be covered in residential sprinkler systems installed in accordance with NFPA 13D and NFPA 13R. If an urban living or multi-family structure includes any secondary uses to the building other than residential living units, then a NFPA 13 system is to be utilized. Exception: Group R-3 attached garages need not be sprinklered throughout if a dry sprinkler is installed within 5 feet (1,524 mm) of the door opening between the garage and attached residence. Residential fire sprinkler risers shall be located on a heated wall in the garage. Exception: Other riser location as approved by the Allen Fire Department Prevention Division. 65. Section 903.2 is amended to read as follows: 903.2 Where required. Approved automatic sprinkler systems in new buildings and structures shall be provided in the locations described in Sections 903.2.1 through 903.2.12. Automatic Sprinklers shall not be installed in elevator machine rooms, elevator machine spaces, and elevator hoistways. Storage shall not be allowed within the elevator machine room. Signage shall be provided at the entry doors to the elevator machine room indicating "ELEVATOR MACHINERY - NO STORAGE ALLOWED." 66. Section 903.2 is further amended by deleting the paragraph titled "Exception." 67. Section 903.2.4.2 is amended to read as follows: 903.2.4.2 Group F-1 distilled spirits. An automatic sprinkler system shall be provided throughout a Group F-1 fire area used for the manufacture of distilled spirits involving more than 120 gallons of distilled spirits (>16% alcohol) in the fire area at any one time. 68. Section 903.2.9 is amended by adding Section 903.2.9.3 to read as follows: 903.2.9.3 Group S-1 distilled spirits or wine. An automatic sprinkler system shall be provided throughout a Group S-1 fire area used for the bulk storage of distilled spirits or wine involving more than 120 gallons of distilled spirits or wine (>16% alcohol) in the fire area at any one time. 69. Section 903.2.9 is amended by adding Section 903.2.9.5 to read as follows: 903.2.9.5 Self-service storage facility. An automatic sprinkler system shall be installed throughout all self-service storage facilities. A screen shall be installed at eighteen (18") inches below the level of the sprinkler heads to restrict storage above that level. This screen shall be a mesh of not less than one (1) inch not greater than six (6") inches in size. This screen and its supports shall be installed such that all elements are at least eighteen (18") inches below any sprinkler head. 70. Section 903.2.11.3 is amended to read as follows: 903.2.11.3 Buildings 35 feet or more in height. An automatic sprinkler system shall be installed throughout buildings with a floor level, other than penthouses in compliance with Section 1510 of the International Building Code located 35 feet (10,668 mm) or more above the lowest level of Fire Department vehicle access. Exception: Open parking structures in compliance with Section 406.5 of the International Building Code. 71. Section 903.2.11 is amended by adding Sections 903.2.11.7, 903.2.11.8, and 903.2.11.9 to read as follows: 903.2.11.7 High-Piled Combustible Storage. For any building with a clear height exceeding 12 feet (4,572 mm), see Chapter 32 to determine if those provisions apply. 903.2.11.8 Spray Booths and Rooms. New and existing spray booths and spraying rooms shall be protected by an approved automatic fire-extinguishing system. 903.2.11.9 Buildings Over 6,000 square feet. An automatic sprinkler system shall be installed throughout all buildings with a building area over 6,000 square feet. For the purpose of this provision, fire walls shall not define separate buildings. For this Section only, area measurement shall be based on outside dimensions of exterior walls, exclusive of vent shafts and courts, without deduction for corridors, stairways, closets, the thickness of interior walls, columns, or other features. The floor area of a building, or portion thereof, not provided with surrounding exterior walls shall be the usable area under the horizontal projection of the roof or floor above. For upper-level attic type rooms, areas where the ceiling height is less than five feet (5'0") shall not be considered. Unfinished spaces framed to permit future expansion of floor area shall be considered as part of the area. Joists designed to support floor loads shall be assumed to be for future area. Exception: Open parking garages in compliance with Section 406.5 of the International Building Code. 903.2.11.9.1 Modifications, repairs, and additions to existing buildings. An automatic sprinkler system shall be installed throughout in accordance with NFPA 13, 13D, or 13R as applicable and this code in all existing buildings when: 1. Enlarged to a floor area of 6,000 square feet or greater; 2. The building has a floor are greater than 6,000 square feet and the square footage is increased; 3. The cumulative remodel of any building, over any period of time on or after March 11, 2008, results in the floor area of the building becoming equal to or greater than 6,000 square feet; 4. Fifty (50) percent or more of the roof assembly is replaced, or repaired, due to fire damage or structural failure, or when the removal of existing fire rated assemblies result in an increase of the original basic allowable area; or 5. Required to be protected in accordance with this Code or other provisions of Article III of the ALDC. 72. Section 903.3.1.1.1 is amended to read as follows: 903.3.1.1.1 Exempt locations. When approved by the Fire Code Official, automatic sprinklers shall not be required in the following rooms or areas where such... (text unchanged) because it is damp, of fire-resistance-rated construction, or contains electrical equipment. 1. Any room where the application of water, or flame and water, constitutes a serious life or fire hazard; 2. Any room or space where sprinklers are considered undesirable because of the nature of the contents, when approved by the Code Official; 3. Generator and transformer rooms, under the direct control of a public utility, separated from the remainder of the building by walls and floor/ceiling or roof/ceiling assemblies having a fire-resistance rating of not less than 2 hours; and 4 Elevator machine rooms, machinery spaces, and hoistways, other than pits where such sprinklers would not necessitate shunt trip requirements under any circumstances. 73. Section 903.3.1.2 is amended to read as follows: 903.3.1.2 NFPA 13R sprinkler systems. Automatic sprinkler systems in Group R occupancies shall be permitted to be installed throughout in accordance with NFPA 13R where the Group R occupancy meets all of the following conditions: 1. Four stories or less above grade plane. 2. The floor level of the highest story is 35 feet (10,668 mm) or less above the lowest level of fire department vehicle access. 3. The flow level of the lowest story is 35 feet (10,668 mm) or less below the lowest level of fire department vehicle access. 74. Section 903.3.1.2.2 is amended to read as follows: 903.3.1.2.2 Corridors and balconies. Sprinkler protection shall be provided in all corridors and for all balconies. 75. Section 903.3.1.2.3 is amended to read as follows: 903.3.1.2.3 Attics and Attached Garages. Sprinkler protection is required in attached garages and in the following attic spaces: 1. Attics that are used or intended for living purposes or storage shall be protected by an automatic sprinkler system; 2. Where fuel-fired equipment is installed in an unsprinklered attic, not fewer than one quick response intermediate temperature sprinkler shall be installed above the equipment; 3. Attic spaces of buildings that are two or more stories in height above grade plane or above the lowest level of fire department vehicle access; and 4. Group R-4, Condition 2 occupancy attics not required by Item 1 or 3 to have sprinklers shall comply with one of the following: 4.1 Provide automatic sprinkler system protection. 4.2 Provide a heat detection system throughout the attic that is arranged to activate the building fire alarm system. 4.3 Construct the attic using noncombustible materials. 4.4 Construct the attic using fire-retardant-treated wood complying with Section 2303.2 of the International Building Code. 4.5 Fill the attic with non-combustible insulation. 76. Section 903.3.1.3 is amended to read as follows: 903.3.1.3 NFPA 13D Sprinkler Systems. Automatic sprinkler systems installed in one- and two- family dwellings; Group R-3; Group R-4 Condition 1 and townhouses shall be permitted to be installed throughout in accordance with NFPA 13D or in accordance with state law. 77. Section 903.3.1 is amended by adding Section 903.3.1.4 to read as follows: 903.3.1.4 Freeze protection. Freeze protection systems for automatic fire sprinkler systems shall be in accordance with the requirements of the applicable referenced NFPA standard and this section. 903.3.1.4.1 Attics. Only dry pipe, preaction, or listed antifreeze automatic fire sprinkler systems shall be allowed to protect attic spaces. Exception: Wet-pipe fire sprinkler systems shall be allowed to protect non-ventilated attic spaces where: 1. The attic sprinklers are supplied by a separate floor control valve assembly to allow ease of draining the attic system without impairing sprinklers throughout the rest of the building; 2. Adequate heat shall be provided for freeze protection as per the applicable referenced NFPA standard; and 3. The attic space is a part of the building's thermal, or heat, envelope, such that insulation is provided at the roof deck, rather than at the ceiling level. 903.3.1.4.2 Heat trace/insulation. Heat trace/insulation shall only be allowed where approved by the fire code official for small sections of large diameter water-filled pipe. 78. Section 903.3.5 is amended by adding the following sentence at the end of the section: Water supply as required for such systems shall be provided in conformance with the supply requirements of the respective standards; however, every fire protection system shall be designed with a 10 psi safety factor. Reference Section 507.4 for additional design requirements. 79. Section 903.3.7 is amended by adding Sections 903.3.7.1 and 903.3.7.2 to read as follows: 903.3.7.1 Missing or damaged FDC caps. Missing or damaged FDC caps shall be replaced with locking "Knox" FDC caps. All new FDCs and standpipe hose valve connections shall have Knox caps or plugs installed. 903.3.7.2 Remote FDCs. Remote fire department connections shall be installed as a separate underground supply line to the fire riser room. A remote FDC cannot tie into the underground fire main supply. 80. Section 903.4 is amended by adding the following paragraph after the paragraph titled "Exceptions": Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds. All control valves in the sprinkler and standpipe systems except for Fire Department hose connection valves shall be electrically supervised to initiate a supervisory signal at the central station upon tampering. 81. Section 903.4.1 is amended by adding Section 903.4.1.1 to read as follows: 903.4.1.1 Dry pipe fire sprinkler monitoring. Dry pipe fire sprinkler systems shall be monitored for high pressure water flow, low air supervisory, and high air supervisory. 82. Section 903.4.2 is amended by adding the following sentence at the end of the section: The alarm device required on the exterior of the building shall be a weatherproof horn/strobe notification appliance with a minimum 75 candela strobe rating, installed as close as practicable to the fire department connection. 83. Section 903.4 is amended by adding Sections 903.4.4 and 903.4.5 to read as follows: 903.4.4 Individual zone controls. Individual zone control valves shall be installed as follows: 1. Multi-story buildings shall be zoned by floor and have separate control valves installed that will allow each floor to be independently shut-off without having an effect on the operation of the sprinkler system on other floors; 2. Multi-story multi-family residential buildings that are separated by a breezeway or fire rated assembly can be zoned by building section if approved in advance by Allen Fire Rescue. The required sectional control valves shall be located in the main sprinkler control valve room or as directed by the Chief or his designee; 3. Hazardous areas such as spray booths, flammable liquid storage rooms, etc. shall be separate zones and have separate control valves installed that will allow the sprinkler system in these areas to be independently shut-off without having an effect on the operation of the system in other areas. The required zone control valves shall be located in an accessible area outside the spray booth or room or in the main sprinkler control valve room; 4. Special systems such as pre-action systems shall be separate zones and have separate control valves installed that will allow the sprinkler system in these areas to be independently shut-off without having an effect on the operation of the system in other areas; 5. Computer rooms shall be separate zones and have separate control valves installed that will allow the sprinkler system in these areas to be independently shut-off without having an effect on the operation of the system in other areas; 6. Where sprinklers are installed in racks, separate indicating control valves and drains shall be provided and arranged so that ceiling and in-rack sprinklers can be controlled independently; 7. Subfloor areas shall have separate control valves installed that will allow the subfloor area to be independently shutoff without having an effect on the operation of the sprinkler system in other areas. The required zone control valves shall be located in an accessible area outside the subfloor area; and 8. Where the zoning of the sprinkler system and installation of separate control valves will increase the level of fire protection for the building, and the life safety of the occupants and firefighters as determined by the Fire Marshal (AHJ). 903.4.5 Monitoring and Supervising. All valves on connections to water supplies, sectional control and isolation valves, and other valves in supply pipes to sprinklers and other fixed water-based fire suppression systems shall be supervised and monitored at all times. Graphic maps shall be posted in the sprinkler riser room depicting sprinkler zones. Proper tagging and/or signage complying with Fire Department specifications shall identify all valves as to their function and identify their location. 84. Section 903.6 is amended by adding Section 903.6.1 to read as follows: 903.6.1 Spray booths and rooms. New and existing spray booths and spray rooms shall be protected by an approved automatic fire-extinguishing system in accordance with Section 2404. 85. Section 905.3 is amended by adding Section 905.3.9 to read as follows: 905.3.9 Building Exceeding 10,000 square feet. In buildings exceeding 10,000 square feet in area per story and where any portion of the building's interior area is more than 200 feet (60960 mm) of travel, vertically and horizontally, from the nearest point of fire department vehicle access, Class I automatic wet or manual wet standpipes shall be provided. Exceptions: 1. Automatic dry and semi-automatic dry standpipes are allowed as provided for in NFPA 14 where approved by the Fire Code Official. 2. R-2 occupancies of four stories or less in height having no interior corridors. 86. Section 905.4 is amended by amending numbered paragraphs 1, 3, and 5 to read as follows: 1. In every required exit stairway, a hose connection shall be provided for each story above and below grade plane. Hose connections shall be located at an intermediate landing between stories, unless otherwise approved by the fire code official. 3. In every exit passageway, at the entrance from the exit passageway to other areas of a building. Exception: Where floor areas adjacent to an exit passageway are reachable from an exit stairway hose connection by a … (remainder of Exception unchanged) 5. Where the roof has a slope less than four units vertical in 12 units horizontal (33.3-percent slope), each standpipe shall be provided with a two-way hose connection located to serve the roof or at the highest landing of an exit stairway with stair access to the roof provided in accordance with Section 1011.12. 87. Section 905.4 is amended by adding a new numbered paragraph 7 to read as follows: 7. When required by this Chapter, standpipe connections shall be placed adjacent to all required exits to the structure and at two hundred feet (200') intervals along major corridors thereafter, or as otherwise approved by the fire code official. 88. Section 905.8 is amended to read as follows: 905.8 Dry standpipes. Dry standpipes shall not be installed. Exception: Where subject to freezing and in accordance with NFPA 14. Additionally, manual dry standpipe systems shall be supervised with a minimum of 10 psi and a maximum of 40 psig air pressure with a high/low supervisory alarm. Manual dry standpipes may not be utilized inside a structure other than an approved open parking garage. 89. Section 905.9 is amended by adding the following paragraph after the "Exceptions": Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds. All control valves in the sprinkler and standpipe systems, except for Fire Department hose connection valves, shall be electrically supervised to initiate a supervisory signal at the central station upon tampering. 90. Section 906.1 (1) is amended by deleting Exception 3 in its entirety. 91. Section 907.1 is amended by adding Section 907.1.4 to read as follows: 907.1.4 Design Standards. All alarm systems, new or replacements, shall be addressable. Alarm systems serving more than 20 smoke detectors shall have analog initiating devices. 92. Section 907.2.1 is amended to read as follows: 907.2.1 Group A. A manual fire alarm system that activates the occupant notification system in accordance with new Section 907.5 shall be installed in Group A occupancies having an occupant load of 300 or more persons or more than 100 persons above or below the lowest level of exit discharge. Group A occupancies not separated from one another in accordance with Section 707.3.10 of the International Building Code shall be considered as a single occupancy for the purposes of applying this section. Portions of Group E occupancies occupied for assembly purposes shall be provided with a fire alarm system as required for the Group E occupancy. Exception: (No change) Activation of fire alarm notification appliances shall: 1. Cause illumination of the means of egress with light of not less than 1 foot-candle (11 lux) at the walking surface level; and 2. Stop any conflicting or confusing sounds and visual distractions. 93. Section 907.2.3 is amended by amending the first paragraph and adding paragraph 1.1 under paragraph 1 of "Exceptions" to read as follows: 907.2.3 Group E. A manual fire alarm system that initiates the occupant notification signal utilizing an emergency voice/alarm communication system meeting the requirements of Section 907.5.2.2 and installed in accordance with Section 907.6 shall be installed in Group E educational occupancies. When automatic sprinkler systems or smoke detectors are installed, such systems or detectors shall be connected to the building fire alarm system. An approved smoke detection system shall be installed in Group E day care occupancies. Unless separated by a minimum of 100' open space, all buildings, whether portable buildings or the main building, will be considered one building for alarm occupant load consideration and interconnection of alarm systems. Exceptions: 1. (No change) 1.1. Residential In-Home day care with not more than 12 children may use interconnected single station detectors in all habitable rooms. (For care of more than five children 2 1/2 or less years of age, see Section 907.2.6.) 94. Section 907.2.10 is amended to read as follows: 907.2.10 Group S. A manual fire alarm system that activates the occupant notification system in accordance with Section 907.5 shall be installed in Group S public- and self-storage occupancies for interior corridors and interior common area. Visible notification appliances are not required within storage units. Exception: (No change) 95. Section 907.2.13 is amended by amending Exception 3 to read as follows: 3. Open air portions of buildings with an occupancy in Group A-5 in accordance with Section 303.1 of the International Building Code, when used for open air seating; however, this Exception does not apply to accessory uses including but not limited to sky boxes, restaurants and similarly enclosed areas. 96. Section 907.4.2 is amended by adding Section 907.4.2.7 to read as follows: 907.4.2.7 Type. Manual alarm initiating devices shall be an approved double action type. 97. Section 907.6.1 is amended by adding Section 907.6.1.1 to read as follows: 907.6.1.1 Wiring Installation. All fire alarm systems shall be installed in such a manner that a failure of any single initiating device or single open in an initiating circuit conductor will not interfere with the normal operation of other such devices. All signaling line circuits (SLC) shall be installed in such a way that a single open will not interfere with the operation of any addressable devices (Class A). Outgoing and return SLC conductors shall be installed in accordance with NFPA 72 requirements for Class A circuits and shall have a minimum of four feet separation horizontal and one foot vertical between supply and return circuit conductors. The initiating device circuit (IDC) from a signaling line circuit interface device may be wired Class B, provided the distance from the interface device to the initiating device is ten feet or less. 98. Section 907.6.3 is amended by deleting all four Exceptions. 99. Section 907.6.6 is amended by adding the following sentence to end of the paragraph: See 907.6.3 for the required information transmitted to the supervising station. 100. Section 907.6.6 is amended by adding Section 907.6.6.4 to read as follows: 906.6.6.4 Communication requirements. All alarm systems, new or replacements, shall transmit alarm, supervisory and trouble signals descriptively to the approved central station, remote supervisory station or proprietary supervising station as defined in NFPA 72, with the correct device designation and location of addressable device identification. Alarms shall not be permitted to be transmitted as a General Alarm or Zone condition. 101. Section 907 is amended by adding Section 907.11 to read as follows: 907.11 Password Protection Prohibited. No fire alarm system shall be protected by a password or pin number that would hinder immediate silencing capabilities by the Fire Department. 102. Section 910.2 is amended by amending paragraphs 2, and 3 under "Exceptions" to read as follows: 2. Manually activated, engineered mechanical smoke and heat exhaust systems shall be required in areas of buildings equipped with early suppression fast-response (ESFR) sprinklers. Automatic smoke and heat removal is prohibited. 3. Manually activated, engineered mechanical smoke and heat exhaust systems shall be required in areas of buildings equipped with control mode special application sprinklers with a response time index of 50 (meters-seconds) 1/2 or less that are listed to control a fire in stored commodities with 12 or fewer sprinklers. Automatic smoke and heat removal is prohibited. 103. Section 910.2 is amended by adding Section 910.2.3 to read as follows: 910.2.3 Group H. Buildings and portions thereof used as a Group H occupancy as follows: 1. In occupancies classified as Group H-2, or H-3, any of which are more than 15,000 square feet (1,394 m2) in single floor area. Exception: Buildings of noncombustible construction containing only noncombustible materials. 2. In areas of buildings in Group H used for storing Class 2, 3, and 4 liquid and solid oxidizers, Class 1, and unclassified detonable organic peroxides, Class 3, and 4 unstable (reactive) materials, or Class 2, or 3 water-reactive materials as required for a high-hazard commodity classification. Exception: Buildings of noncombustible construction containing only noncombustible materials. 104. Section 910.4.3.1 of the International Fire Code Section 910.4.3.1 is amended to read as follows: 910.4.3.1 Makeup Air. Makeup air openings shall be provided within 6 feet (1829 mm) of the floor level. Operation of makeup air openings shall be automatic. The minimum gross area of makeup air inlets shall be 8 square feet per 1,000 cubic feet per minute (0.74 m2 per 0.4719 m3/s) of smoke exhaust. 105. Section 912.2 is amended by adding Section 912.2.3 to read as follows: 912.2.3 Hydrant distance. An approved fire hydrant shall be located within 100 feet of the Fire Department connection as the fire hose lays along an unobstructed path. 106. Section 913.2.1 is amended by adding the following sentence and Exception to read as follows: When located on the ground level at an exterior wall, the fire pump room shall be provided with an exterior Fire Department access door that is not less than 3 feet in width, and 6 feet 8 inches in height, regardless of any interior doors that are provided. A key box shall be provided at this door, as required by Section 506.1. Exception: When it is necessary to locate the fire pump room on other levels or not at an exterior wall, the corridor leading to the fire pump room access from the exterior of the building shall be provided with equivalent fire resistance as that required for the pump room, or as approved by the Fire Code Official. Access keys shall be provided in the key box as required by Section 506.1. 107. Section 913.4 is amended by adding the following sentence at the end of the section: The fire-pump system shall also be supervised for "loss of power," "phase reversal," and "pump running" conditions by supervisory signal on district circuits. 108. Section 914.3.1.2 is amended to read as follows: 914.3.1.2 Water Supply to required Fire Pumps. In buildings that are more than 120 feet (128 m) in building height, required fire pumps shall be supplied by connections to no fewer than two water mains located in different streets. Separate supply piping shall be provided between each connection to the water main and the pumps. Each connection and the supply piping between the connection and the pumps shall be sized to supply the flow and pressure required for the pumps to operate. Exception: (No change to exception) 109. Section 1006.2.2 is amended by adding Section 1006.2.2.7 to read as follows: 1006.2.2.7 Electrical Rooms. For electrical rooms, special exiting requirements may apply. Reference the Electrical Code as adopted. 110. Section 1009.8 is amended by adding Exception 7 to read as follows: 7. Buildings regulated under State Law and built, in accordance with State registered plans, including any variances or waivers granted by the State, shall be deemed to be in compliance with the requirements of Section 1009 and chapter 11. 111. Section 1010.2.5 is amended by amending Exceptions 3, and 4 to read as follows: 3. Where a pair of doors serves an occupant load of less than 50 persons in a Group B, F, M, or S occupancy. (Remainder unchanged) 4. Where a pair of doors serves a Group A, B, F, M, or S occupancy (Remainder unchanged) 112. Section 1020.2 is amended by adding paragraph 6 under "Exceptions" to read as follows: 6. In Group B occupancies, corridor walls and ceilings need not be of fire-resistive construction within a single tenant when the space is equipped with an approved automatic fire alarm system with corridor smoke detection. The actuation of any detector shall activate alarms audible in all areas served by the corridor. The smoke-detection system shall be connected to the building's fire alarm system where such a system is provided. 113. Section 1030.1.1.1 is deleted. 114. Section 1032.2 is amended to read as follows: 1032.2 Reliability. Required exit accesses, exits, or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency. An exit or exit passageway shall not be used for any purpose that interferes with a means of egress. Security devices affecting means of egress shall be subject to approval of the Fire Code Official. 115. Section 1103.3 is amended by adding the following sentence to end of paragraph: Provide emergency signage as required by Section 604. 116. Section 1103.5.1 is amended by adding the following sentence to end of paragraph: Fire sprinkler system installation shall be completed with 24 months from date of notification by the fire code official. 117. Section 1103.5 is amended by adding Section 1103.5.6 to read as follows: 1103.5.6 Spray Booths and Rooms. Existing spray booths and spray rooms shall be protected by an approved automatic fire-extinguishing system in accordance with Section 2404. 118. Section 1103.7 is amended by adding Sections 1103.7.7 and 1103.7.7.1 to read as follows: 1103.7.7 Fire Alarm System Design Standards. Where an existing fire alarm system is upgraded or replaced, the devices shall be addressable. Fire alarm systems utilizing more than 20 smoke and/or heat detectors shall have analog initiating devices. Exception: Existing systems need not comply unless the total building, or fire alarm system, remodel or expansion exceeds 30% of the building. When cumulative building, or fire alarm system, remodel or expansion initiated after the date of original fire alarm panel installation exceeds 50% of the building, or fire alarm system, the fire alarm system must comply within 18 months of permit application. 1103.7.7.1 Communication requirements. Refer to Section 907.6.6 for applicable requirements. 119. Section 1203.1.3 is amended to read as follows: 1203.1.3 Installation. Emergency power systems and standby power systems shall be installed in accordance with the International Building Code, NFPA 70, NFPA 110, and NFPA 111. Existing installations shall be maintained in accordance with the original approval, except as specified in Chapter 11. Exception: Where the system is supplied with natural gas from a utility provider and is approved. 120. Section 1203.1 is amended by adding Section 1203.1.10 to read as follows: 1203.1.10 Critical Operations Power Systems (COPS). For Critical Operations Power Systems necessary to maintain continuous power supply to facilities or parts of facilities that require continuous operation for the reasons of public safety, emergency management, national security, or business continuity, see NFPA 70. 121. Section 1203.2 is amended to read as follows: 1203.2 Where required. Emergency and standby power systems shall be provided where required by Sections 1203.2.1 through 1203.2.19 or elsewhere identified in this code or any other referenced code. 122. Section 1203.2.4 is amended to read as follows: 1203.2.4 Emergency Voice/alarm Communications Systems. Emergency power shall be provided for emergency voice/alarm communications systems in the following occupancies, or as specified elsewhere in this code, as required in Section 907.5.2.2.5. The system shall be capable of powering the required load for a duration of not less than 24 hours, as required in NFPA 72. Covered and Open Malls, Section 907.2.20 and 914.2 Group A Occupancies, Sections 907.2.1 and 907.5.2.2 Special Amusement Buildings, Section 907.2.12.3 and 914.7 High-rise Buildings, Section 907.2.13 and 914.3 Atriums, Section 907.2.14 and 914.4 Deep Underground Buildings, Section 907.2.19 123. Section 1203.2.15 is amended to read as follows: 1203.2.15 Means of Egress Illumination. Emergency power shall be provided for means of egress illumination in accordance with Sections 1008.3 and 1104.5.1. (90 minutes) 124. Section 1203.2.16 is amended to read as follows: 1203.2.16 Membrane Structures. Emergency power shall be provided for exit signs in temporary tents and membrane structures in accordance with Section 3103.12.6.1. (90 minutes) Standby power shall be provided for auxiliary inflation systems in permanent membrane structures in accordance with Section 2702 of the International Building Code. (4 hours) Auxiliary inflation systems shall be provided in temporary air-supported and air-inflated membrane structures in accordance with Section 3103.10.4. 125. Section 1203.2.18 is amended to read as follows: 1203.2.18 Smoke Control Systems. Standby power shall be provided for smoke control systems in the following occupancies, or as specified elsewhere in this code, as required in Section 909.11: Covered Mall Building, International Building Code, Section 402.7 Atriums, International Building Code, Section 404.7 Underground Buildings, International Building Code, Section 405.8 Group I-3, International Building Code, Section 408.4.2 Stages, International Building Code, Section 410.3.7.2 Special Amusement Buildings (as applicable to Group A's), International Building Code, Section 411.1 Smoke Protected Seating, Section 1029.6.2.1 Buildings considered to be a high-rise. 126. Section 1203.2 is amended by adding Sections 1203.2.20, 1203.2.21, 1203.2.22, 1203.2.23, 1203.2.24, 1203.2.25, and 1203.2.26 to read as follows: 1203.2.20 Covered and Open Mall Buildings. Emergency power shall be provided in accordance with Section 907.2.20 and 914.2.3. 1203.2.21 Airport Traffic Control Towers. A standby power system shall be provided in airport traffic control towers more than 65 feet in height. Power shall be provided to the following equipment: 1. Pressurization equipment, mechanical equipment and lighting. 2. Elevator operating equipment. 3. Fire alarm and smoke detection systems. 1203.2.22 Smokeproof Enclosures and Stair Pressurization Alternative. Standby power shall be provided for smokeproof enclosures, stair pressurization alternative and associated automatic fire detection systems as required by the International Building Code, Section 909.20.7.2. 1203.2.23 Elevator Pressurization. Standby power shall be provided for elevator pressurization system as required by the International Building Code, Section 909.21.5. 1203.2.24 Elimination of Smoke Dampers in Shaft Penetrations. Standby power shall be provided when eliminating the smoke dampers in ducts penetrating shafts in accordance with the International Building Code Section 717.5.3, Exception 2.3. 1203.2.25 Common Exhaust Systems for Clothes Dryers. Standby power shall be provided for common exhaust systems for clothes dryers located in multistory structures in accordance with the International Mechanical Code, Section 504.10, Item 7. 1203.2.26 Means of Egress Illumination in Existing Buildings. Emergency power shall be provided for means of egress illumination in accordance with Section 1104.5 when required by the fire code official. (90 minutes in I-2, 60 minutes elsewhere.) 127. Section 2304.1 is amended to read as follows: 2304.1 Supervision of Dispensing. The dispensing of fuel at motor fuel-dispensing facilities shall be in accordance with the following: 1. Conducted by a qualified attendant; and/or, 2. Shall be under the supervision of a qualified attendant; and/or 3. Shall be an unattended self-service facility in accordance with Section 2304.3. At any time, the qualified attendant of Item 1 or 2 above is not present, such operations shall be considered as an unattended self-service facility and shall also comply with Section 2304.3. 128. Section 2401.2 is deleted. 129. Section 3103.3.1 is deleted. 130. Table 3206.2 is amended by amending Footnote "h" to read as follows: h. Where storage areas are protected by either early suppression fast response (ESFR) sprinkler systems or control mode special application sprinklers with a response time index of 50 (meters-second) 1/2 or less that are listed to control a fire in the stored commodities with 12 or fewer sprinklers, installed in accordance with NFPA 13, manual smoke and heat vents or manually activated engineered mechanical smoke exhaust systems shall be required within these areas. Table 3206.2 is amended by adding Footnote "j" to row titled "High Hazard," and "Greater than 300,000" to read as follows: j. High hazard high-piled storage areas shall not exceed 500,000 square feet. A 2-hour fire wall constructed in accordance with Section 706 of the International Building Code shall be used to divide high-piled storage exceeding 500,000 square feet in area. 131. Section 3311.1 is amended by adding the following sentence to the end of the section: When fire apparatus access roads are required to be installed for any structure or development; they shall be approved prior to the time at which construction has progressed beyond completion of the foundation of any structure. 132. Section 5601.1.3 is amended to read in its entirety as follows: 5601.1.3. Fireworks. The possession, manufacture, storage, sale, handling, and use of fireworks are prohibited. Exceptions: 1. Only when approved for fireworks displays, storage, and handling of fireworks as allowed in Section 5604, and 5608. 2. The use of fireworks for approved displays as allowed in Section 5608. 133. Section 5703.6 is amended by adding a sentence to read as follows: 5703.6 Piping systems. Piping systems, and their component parts, for flammable and combustible liquids shall be in accordance with Sections 5703.6.1 through 5703.6.11. An approved method of secondary containment shall be provided for underground tank and piping systems. 134. Section 5704.2.11.4 is amended to read as follows: 5704.2.11.4 Leak Prevention. Leak prevention for underground tanks shall comply with Sections5704.2.11.4.1 and 5704.2.11.4.1 through 5704.2.11.4.3. An approved method of secondary containment shall be provided for underground tank and piping systems. 135. Section 5704.2.11.4.2 is amended to read as follows: 5704.2.11.4.2 Leak detection. Underground storage tank systems shall be provided with an approved method of leak detection from any component of the system that is designed and installed in accordance with NFPA 30 and as specified in Section 5704.2.11.4.3. 136. Section 5704.2.11.4 is amended by adding Section 5704.2.11.4.3 to read as follows: 5704.2.11.4.3 Observation Wells. Approved sampling tubes of a minimum 4 inches in diameter shall be installed in the backfill material of each underground flammable or combustible liquid storage tank. The tubes shall extend from a point 12 inches below the average grade of the excavation to ground level and shall be provided with suitable surface access caps. Each tank site shall provide a sampling tube at the corners of the excavation with a minimum of 4 tubes. Sampling tubes shall be placed in the product line excavation within 10 feet of the tank excavation and one every 50 feet routed along product lines towards the dispensers, a minimum of two are required. 137. Section 5707.4 is amended by adding the following paragraph: Mobile fueling sites shall be restricted to commercial, industrial, governmental, or manufacturing, where the parking area having such operations is primarily intended for employee vehicles. Mobile fueling shall be conducted for fleet fueling or employee vehicles only, not the general public. Commercial sites shall be restricted to office-type or similar occupancies that are not primarily intended for use by the public. 138. Section 6103.2.1 is amended by adding Section 6103.2.1.8 to read as follows: 6103.2.1.8 Jewelry Repair, Dental Labs, and Similar Occupancies. Where natural gas service is not available, portable LP-Gas containers are allowed to be used to supply approved torch assemblies or similar appliances. Such containers shall not exceed 20-pound (9.0 kg) water capacity. Aggregate capacity shall not exceed 60-pound (27.2 kg) water capacity. Each device shall be separated from other containers by a distance of no less than 20 feet. 139. Section 6104.2 is amended by adding Exception 2 to read as follows: 2. Except as permitted in Sections 308 and 6104.3.2, LP-gas containers are not permitted in residential areas. 140. Section 6104.3 is amended by adding Section 6104.3.3 to read as follows: 6104.3.3 Spas, Pool Heaters, and Other Listed Devices. Where natural gas service is not available, an LP-gas container is allowed to be used to supply spa and pool heaters or other listed devices. Such container shall not exceed 250-gallon water capacity per lot. See Table 6104.3 for location of containers. Exception: Lots where LP-gas can be off-loaded wholly on the property where the tank is located may install up to 500 gallon above ground or 1,000 gallon underground approved containers. 141. Section 6107.4 is amended to read as follows: 6107.4 Protecting Containers from Vehicles. Where exposed to vehicular damage due to proximity to alleys, driveways or parking areas, LP-gas containers, regulators and piping shall be protected in accordance with Section 312. 142. Section 6109.13 is amended to read as follows: 6109.13 Protection of Containers. LP-gas containers shall be stored within a suitable enclosure or otherwise protected against tampering. Vehicle impact protection shall be provided as required by Section 6107.4. 143. Appendix L Requirements for Fire Fighter Air Replenishment Systems is amended by adding Section L101.2 to read as follows: Section L101.2 Required Location. In new buildings, fill stations shall be required when any of the following conditions occur: 1. Any new building 5 or more stories in height; 2. Any new building with 2 or more floors below grade; and 3. Any new building 500,000 feet or more in size. Each stairwell shall have a supply riser. SCBA fill stations shall be located on odd numbered floors in the primary stairwell and on even numbered stairs in the secondary stairwells. The primary stairwell will be the stair located closest to the main entrance.
(Ord. No. 3919-6-22, § 1, 6-14-2022)
Ask a question about Allen law
Corpus searches the Allen sections it holds and shows the ones that match, with their citations. Free, no sign-in.