§ 3.10 — Amendments to International Energy Conservation Code, 2021 edition
Code of Ordinances of the City of Allen, Texas (Codified through Ordinance No. 4212-2-26, adopted February 10, 2026 (Supp. No. 23)) · Allen Land Development Code § 3.10
Corpus is an independent public-information project, not the official City of Allen website. Stable reference: corpuslaw.us/code/dfe5ae71-7364-473d-b947-956219638a4e
Sec. 3.10. - Amendments to International Energy Conservation Code, 2021 edition.
The following amendments to the International Energy Conservation Code, 2021 edition, as adopted pursuant to section 3.01, are hereby adopted: 1. Section C102/R102 is amended by adding Section C102.1.2, and Section R102.1.2 to read as follows: C102.1.2 Alternative compliance. A building certified by a national, state, or local accredited energy efficiency program and determined by the Energy Systems Laboratory to be in compliance with the energy efficiency requirements of this section may, at the option of the code official, be considered in compliance. The United States Environmental Protection Agency's Energy Star Program certification energy code equivalency shall be considered in compliance. R102.1.2 Alternative compliance. A building certified by a national, state, or local accredited energy efficiency program and determined by the Energy Systems Laboratory to be in compliance with the energy efficiency requirements of this section may, at the option of the code official, be considered in compliance. The United States Environmental Protection Agency's Energy Star Program certification energy code equivalency shall be considered in compliance. Regardless of the program or the path to compliance, each 1- and 2-family dwelling shall be tested for air and duct leakage as prescribed in Section R402.4.1.2 and R403.3.3 respectively. 2. Section R202 is amended by adding a definition for the phrases "Dynamic Glazing" and "Projection Factor" to read as follows: DYNAMIC GLAZING. Any fenestration product that has the fully reversible ability to change its performance properties, including U-factor, solar heat gain coefficient (SHGC), or visible transmittance (VT). PROJECTION FACTOR. The ration of the horizontal depth of the overhang, eve or permanently attached shading device, divided by the distance measured vertically from the bottom of the fenestration glazing to the underside of the overhang, eave or permanently attached shading device. 3. Section R401.2.5 is deleted. 4. Section R402.4.1 is amended by adding Section R402.4.1.4 to read as follows: R402.4.1.4 Sampling options for R2 multifamily dwelling units. For buildings with eight or more testing units that must be tested as required by R402.1.2 or R402.1.3, the greater of seven units or 20 percent of the testing units in the building shall be tested, including a top floor unit, a ground floor unit, a middle floor unit, and a unit with the largest testing unit enclosure area. For each tested unit that exceeds the maximum air leakage rate, an additional three units shall be tested, including a mixture of testing unit types and locations. Where buildings have fewer than eight testing units, each testing unit shall be tested. 5. Section C402.5.2 is amended by amending item 2 to read as follows: 2. Dwelling and sleeping unit enclosure testing. For buildings with eight or more testing units, the greater of seven units or 20 percent of the testing units in the building shall be tested, including a top floor unit, a ground floor unit, a middle floor unit, and a unit with the largest testing unit enclosure area. For each tested unit that exceeds the maximum air leakage rate, an additional two three units shall be tested, including a mixture of testing unit types and locations. 6. Section R403.3 is amended by adding section 403.3.8 to read as follows: R403.3.8 Sampling options for R2 multifamily dwelling units. For buildings with eight or more testing units that must be tested as required by R403.3.5, the greater of seven units or 20 percent of the testing units in the building shall be tested, including a top floor unit, a ground floor unit, a middle floor unit, and a unit with the largest testing unit floor area. For each tested unit that exceeds the maximum duct leakage rate, an additional three units shall be tested, including a mixture of testing unit types and locations. Where buildings have fewer than eight testing units, each testing unit shall be tested. 7. Section C403.6 is amended by adding section C403.6.4 to read as follows: C403.6.4 Sampling options for R2 multifamily dwelling units. For buildings with eight or more testing units that must be tested as required by R403.6.3, the greater of seven units or 20 percent of the testing units in the building shall be tested, including a top floor unit, a ground floor unit, a middle floor unit, and a unit with the largest testing unit floor area. For each tested unit that does not meet the minimum ventilation rate, an additional three units shall be tested, including a mixture of testing unit types and locations. Where buildings have fewer than eight testing units, each testing unit shall be tested. 8. Table R406.4 Maximum Energy Rating Index is amended to read as follows: Table R406.42 Maximum Energy Rating Index Climate Zone | Energy Rating Index 3 | 63 2 This table is effective from September 1, 2019, to August 31, 2022. Table R406.43 Maximum Energy Rating Index Climate Zone | Energy Rating Index 3 | 59 3 This table is effective on September 1, 2022, to August 31, 2025 9. Section R408 is deleted.
(Ord. No. 3919-6-22, § 1, 6-14-2022)
Ask a question about Allen law
Corpus searches the Allen sections it holds and shows the ones that match, with their citations. Free, no sign-in.