Sec. 18-398. - Design temperature of heating systems.

(a) Heating systems for one- and two-family residences shall be capable of heating the dwelling to 70 degrees Fahrenheit when the temperature outdoors is minus 15 degrees Fahrenheit with a 15 mph wind. Manual J, Calculating Heat Losses, Second Edition, 1964, National Warm Air Heating and Air Conditioning Association, or its succeeding publication, shall be an acceptable design standard for purposes of determining heating requirements. The chief building inspector shall be furnished with heat loss calculations upon request. (b) Buildings other than one- and two-family dwelling units shall be heated in accordance with the requirements of the Heating, Ventilating and Air Conditioning Code, Industrial Commission, State of Wisconsin.

(Code 1973, § 30.36.010(c))