Sec. 18-406. - Steam and hot water pipes.

(a) Clearance. (1) Steam and hot water pipes shall be installed with a clearance of at least one inch to all combustible material, except as specified in subsections (a)(2) and (a)(3) of this section. (2) At points where pipes carrying steam or hot water at not over 15 pounds per square inch gauge pressure, or hot water at not over 250 degrees Fahrenheit, emerge from a floor, wall or ceiling, the clearance at the opening through the finish floor boards or wall or ceiling boards may be less than one inch, but shall not be less than one-half inch. Each opening shall be covered with a plate of noncombustible material. (3) Hot water pipes on a system with automatic firing and with limit controls such that water temperature at the boiler or furnace cannot rise above 180 degrees Fahrenheit may be installed without clearance to combustible material. (b) Protection. (1) Coverings or insulation used on steam or hot water pipes shall be of noncombustible material. (2) Where steam pipes and hot water pipes pass through a floor, wall or ceiling of fire-resistive construction, the openings around them shall be filled with noncombustible material to prevent the passage of fire.

(Code 1973, § 30.36.070)

Ask a question about Racine law

Corpus searches the Racine sections it holds and shows the ones that match, with their citations. Free, no sign-in.