§ 1204.2 — DEVICES FOR PROTECTING THE POTABLE WATER SUPPLY

Atlanta City Code (Code of Ordinances, Part II) (Supp. No. 108, Update 1: codified through Ordinance No. 2026-37 (26-O-1511), enacted September 30, 2026) · Atlanta Land Development Code, App. C, ch. I, § 1204.2

Corpus is an independent public-information project, not the official City of Atlanta website. Stable reference: corpuslaw.us/code/b92aba24-edbc-4099-a39e-21a65a08410b

1204.2. - DEVICES FOR PROTECTING THE POTABLE WATER SUPPLY.

(a) Vacuum breakers and backflow preventers shall be selected on the degree of hazard and the type cross-connection involved. The degree of hazard is determined by whether the impurities are contaminants or pollutants. The type protection shall be determined as follows: (1) Non-Pressure Type Cross Connection. A low inlet connection shall be protected by an approved vacuum breaker or backflow preventer when not protected by a minimum air gap. (2) A pressure type cross-connection shall be protected by an appropriate backflow preventer only. (3) Atmospheric or pressure type vacuum breakers may not be used on pressure type cross-connections. (b) Backflow preventer assemblies, fittings, components and accessories two (2) inches or smaller shall be bronze with threaded connections. Sizes two and one-half (2½) inches and larger may be iron or bronze, with flanged connections. See Appendix D for Selection Guide. (c) When a backflow preventer (RPZ-BFP) is required at the service-connection to contain a premises from the main, and when the water purveyor and the plumbing official agree to allow the BFP to be installed in the service pipe immediately inside a building on premises, it shall be unlawful to tap into this service pipe between the BFP and the service-connection. Any branch connection(s) on an existing service pipe, that is to be contained by a BFP immediately inside a building, shall be permanently disconnected or equipped with backflow preventer(s) that are commensurate with the degree(s) of hazard.

Ask a question about Atlanta law

Corpus searches the Atlanta sections it holds and shows the ones that match, with their citations. Free, no sign-in.