§ 1204.4 — INSTALLATION OF DEVICES

Atlanta City Code (Code of Ordinances, Part II) (Supp. No. 108, Update 1: codified through Ordinance No. 2026-37 (26-O-1511), enacted September 30, 2026) · Atlanta Land Development Code, App. C, ch. I, § 1204.4

Corpus is an independent public-information project, not the official City of Atlanta website. Stable reference: corpuslaw.us/code/270ecf2b-5152-4b14-b112-7a8579c14b36

1204.4. - INSTALLATION OF DEVICES.

(a) General: Vacuum breakers and backflow preventers equipped with atmospheric vents or relief openings shall be installed and located to prevent any vent or relief opening from being submerged. They shall be installed as recommended by the manufacturer and protected from freezing. (1) Vacuum breaker atmospheric type (VB-AT) shall be installed at least six (6) inches above the highest outlet or the overflow level on the non-potable system and downstream of the last shut-off valve. (2) Vacuum breaker pressure type (V-PT) shall be installed twelve (12) inches above the highest outlet or the overflow level on the non-potable system. It may be installed upstream of the last shut-off valve. (3) Vacuum breaker hose type (V-HT) if not an integral part of the faucet or hydrant, this device shall be attached directly to the hose threads of the faucet and not be subjected to continuous pressure, static or flowing; nor shall it be attached to a freezeless type hydrant unless it is designed for this service. (4) Backflow preventer with intermediate atmospheric vent (BFP-IAV): Installation of this device below grade is prohibited. Where relief valve discharge from the device could cause water damage, it shall be piped via an air gap or a funnel, from the relief valve port to a floor drain or other approved location. A union shall be installed at the inlet and the outlet connections of the device, and a shut-off valve on the inlet and the outlet sides of the device. A strainer shall be included between the first shut-off valve and the device. Maximum permissible size is three-fourths (¾) inch. (5) Backflow preventer, double check valve (BFP-DCV). This device shall not be buried in earth but may be installed below ground in a meter box or pit provided the device is equipped with ball valve test cocks fitted with brass plugs. An approved shut-off valve shall be installed near the inlet and outlet sides of the device. A union or flange shall be near the inlet side of the device; when below ground, on both sides. (6) Backflow preventer, dual check (BFP-DuC): This device shall not be buried in earth but may be installed below ground in a meter box or pit. An approved shut-off valve and union shall be installed near the inlet side of the device; when below ground, on both sides. (7) Backflow preventer, reduced pressure zone (BFP-RPZ). Installation of this device below grade is prohibited. An approved shut-off valve and a union or flange shall be near the inlet and outlet sides. Where relief valve discharge from the device could cause water damage, it shall be piped via an air gap or a funnel from the relief valve port to an approved location. On sizes two (2) inches and smaller, a bronze strainer with 20-mesh stainless steel screen shall be installed between the first shut-off valve and the BFP head. On sizes larger than two (2) inches a strainer shall be used where required by the Administrative Authority. A. When the reduced pressure zone (RPZ) device is installed in a line subject to periodic no-flow conditions and the supply pressure is subject to periodic pressure dips, an auxiliary directional check valve with soft-disc shall be installed between the inlet shut-off valve and the BFP head. Makeup lines to chilled water systems and hydronic heating systems are examples of such installations. EXCEPTION: The auxiliary directional check valve will not be required when a water pressure reducing valve is installed in the same line with RPZ device and the reducing valve is located upstream of the device. B. The two shut-off valves that are necessary for periodic testing of a backflow preventer need not be attached directly to the inlet and the outlet connections of the device. They may be installed remotely from the backflow preventer provided such relocations do not interfere with the normal testing of the device and provided there are no intervening connections between the backflow preventer and the valves.

Ask a question about Atlanta law

Corpus searches the Atlanta sections it holds and shows the ones that match, with their citations. Free, no sign-in.