§ 1204.8 — FIRE SUPPRESSION SYSTEMS

Atlanta City Code (Code of Ordinances, Part II) (Supp. No. 108, Update 1: codified through Ordinance No. 2026-37 (26-O-1511), enacted September 30, 2026) · Atlanta Land Development Code, App. C, ch. I, § 1204.8

Corpus is an independent public-information project, not the official City of Atlanta website. Stable reference: corpuslaw.us/code/74627c98-6d03-4a9b-a34c-03e6287a6c09

1204.8. - FIRE SUPPRESSION SYSTEMS.

(a) For the purposes of this Code, fire suppression systems shall be classified as follows: (1) Sprinkler system. (2) Standpipe system. (3) Combined system (both sprinkler and standpipe system). (b) For purposes of cross-connection control, fire suppression sprinkler systems shall be classified by water source as follows: (1) CLASS I—Directly supplied from public water mains only; no pumps, tanks or reservoirs; no physical connection from other water supplies; no antifreeze or additives of any kind; all sprinkler drains discharging to atmosphere, dry well, or other safe outlets. (2) CLASS II—Directly supplied from public water mains, same as class I except that booster pumps may be installed in supply lines. (3) CLASS III—Directly supplied from public water mains, same as Class I, plus one or more of the following: Elevated storage tanks or pressure tanks; fire pumps taking suction from above-ground covered reservoirs or tanks. All storage facilities shall be filled from the potable water supply and maintained in a potable condition. (4) CLASS IV—Directly supplied from public main similar to Classes I and II, and with an auxiliary water supply on or available to the premises; or an auxiliary water supply located within 1700 feet of the pumper connection. (5) CLASS V—Directly supplied from public mains, and interconnected with auxiliary supplies, such as: pumps taking suction from reservoirs exposed to contamination, or rivers and ponds; driven wells, mills or other industrial water systems; or where antifreeze or other additives are used. (6) CLASS VI—Directly supplied from the public water mains only, with or without gravity storage or pump suction tanks, and inter-connected with industrial systems. (c) All fire suppression systems shall be isolated from the potable water supply as follows: (1) CLASS I and II sprinkler systems shall be isolated by one of the following: (A) An approved BFP-DCV meeting UL Standard 312 and classified or listed by and bearing a label or seal of a nationally recognized fire suppression testing laboratory such as UL or FM; or (B) An approved BFP-DDC meeting UL Standard 312 and classified or listed by and bearing a label or seal of a nationally recognized fire suppression testing laboratory such as UL or FM; or (C) A method of containments consisting of the following: i) An indicating gate valve with test cocks for testing and draining, ii) An internally loaded check valve with test cocks for testing and draining, iii) A check valve with test cocks for testing and draining. The wet system alarm check valve meeting ANSI/UL Standard 193 or a directional check valve meeting UL Standard 312 are acceptable for this valve, and iv) An indicating gage valve if the valving arrangement requires it. (2) CLASS I or II Standpipe and combined systems shall be isolated from the potable water system by a BFP-DCV or BFP-DDC meeting UL Standard 312 and classified or listed by and bearing a label or seal of a nationally recognized fire suppression testing laboratory such as UL or FM. (3) A CLASS III sprinkler, standpipe and combined systems shall be isolated from the potable water system by a BFP-DCV or BFP-DDC meeting UL Standard 312 and classified or listed by and bearing a label or seal of a nationally recognized fire suppression testing laboratory such as UL or FM. (4) A CLASS IV or V sprinkler, standpipe and combined systems connected to a water source shall be isolated from the potable water system by a BFP-RPZ meeting UL Standard 312 and classified or listed by and bearing a label or seal of a nationally recognized fire suppression testing laboratory such as UL or FM. (5) A CLASS VI sprinkler, standpipe and combined systems connected to a water source shall be isolated from the public potable water system by a system designed and sealed by a professional engineer licensed in Georgia. NOTE: For additional installation requirements of fire suppression systems, see Rules of Georgia Safety Fire Commissioner. (d) The purpose of certain checking devices currently used, or likely to be used, in conjunction with fire suppression systems is outlined below to separate approved and non-approved devices for backflow prevention: (1) Directional Check: To provide the directional flow only. (2) Alarm Check: To signal an alarm, summon the fire department, etc., when a sprinkler head flows water and to provide directional flow. (3) Detector Check: To detect unauthorized use of water for other than fire service and leaks and to provide directional flow. (4) Double Check: To prevent backflow of polluted water from fire suppression systems into the potable water system and to provide directional flow. (5) Double Detector Check: To prevent backflow of polluted water from fire suppression systems into the potable water system, to detect unauthorized use of water or leaks in the fire suppression systems and to provide directional flow. (6) Reduced Pressure Check: To prevent backflow of contaminated water from fire suppression systems into the potable water system and to provide directional flow. (7) Reduced pressure detector check.* To prevent backflow of contaminated water from fire suppression systems into the potable water system and detect unauthorized use of water or leaks and to provide directional flow. *This device is listed in anticipation of its becoming available. (e) Directional checks, alarm checks, detector checks, etc., may not be used as a component part of a backflow preventer assembly unless approved by the Administrative Authority; e.g., the addition of a second check to one of the above devices may not be substituted for an approved BFP unless such addition results in a device identical to that furnished by the manufacturer as an approved BFP and the resulting assembly qualifies for the appropriate label. (f) An approved double check valve BFP may serve also as a directional check. Similarly, an approved double check detector check BFP may serve the multi-purpose of backflow preventer, detector check, and directional check. (g) The shut-off valves that are necessary for periodic testing of a backflow preventer may be installed remotely from the backflow preventer provided such relocations do not interfere with the normal testing of the device and shall be readily accessible for testing. (h) The shut-off valves required for periodic testing of a backflow preventer shall be listed by a nationally recognized testing laboratory for the intended service and the inlet valve shall include an approved test cock on the inlet side of the valve. NOTE: See definitions of contaminant and pollutant. (i) To distinguish between systems used exclusively for fire service, and those used for both fire service and domestic water service, the following definitions shall apply: (1) Combined System: Consists of bulk and express risers that supply both standpipe and sprinkler systems. This system is for fire service only. (2) Combination System: A standpipe riser that supplies both fire service and domestic water service. [Table 12.1. Minimum Air Gaps for Plumbing Fixture (Copy illegible)]

Ask a question about Atlanta law

Corpus searches the Atlanta sections it holds and shows the ones that match, with their citations. Free, no sign-in.