§ 1204.6 — FIXTURE OUTLETS WITH THREADED HOSE CONNECTIONS
Atlanta City Code (Code of Ordinances, Part II) (Supp. No. 108, Update 1: codified through Ordinance No. 2026-37 (26-O-1511), enacted September 30, 2026) · Atlanta Land Development Code, App. C, ch. I, § 1204.6
Corpus is an independent public-information project, not the official City of Atlanta website. Stable reference: corpuslaw.us/code/edf13d5f-12fb-4858-91ef-fe9b1402c7ea
1204.6. - FIXTURE OUTLETS WITH THREADED HOSE CONNECTIONS.
(a) All faucets with standard threaded hose connections shall be protected against backflow or back-siphonage as follows: (1) When the outlet end of any hose can reach an elevation six (6) inches of the faucet to be protected, and when a spring-loaded nozzle can be attached to the end of the hose, the faucet shall be equipped with a VB meeting the requirements of ASSE Standard 1011. (2) When the outlet end of any hose cannot reach an elevation six (6) inches of the faucet, or any vacuum breaker protecting it, and when a spring-loaded nozzle cannot be attached to the end of the hose, the faucet shall be protected by a VB that may be the atmospheric type meeting the requirements of ASSE Standard 1001 or other approved type. EXCEPTION: 1. Where the above VB's cannot be used on a piece of equipment or valve, an approved pressure-type VB or a backflow preventer (BFP) commensurate with the degree of hazard shall be installed in the water supply branch upstream of the equipment or valve. 2. Hose-Type vacuum breakers (VB-HT) used outside a building may be integral with or attached to the faucet outlet and shall be non-removable. When used on frost-proof hydrants, they shall permit the draining of the hydrant barrel, either automatically or manually. 3. Underground yard hydrants that have a drainage hole at the bottom of the casing shall, in addition to the VB-HT, be isolated from the potable distribution system by not less than a dual check backflow preventer (BFP-DuC) meeting ASSE Standard 1024, and installed in the supply branch upstream of the hydrant. The BFP shall be the same size as the supply pipe to the hydrant. 4. Where a branch supply line serves two or more yard hydrants, a single BFP may be installed in the common branch upstream from the hydrants. BFP's for this service that are larger than one (1) inch shall be DCV assemblies meeting ASSE Standard 1015. See Section 1204.4 of the code for restrictions.
Ask a question about Atlanta law
Corpus searches the Atlanta sections it holds and shows the ones that match, with their citations. Free, no sign-in.