1204.7. - LAWN SPRINKLERS.

(a) Lawn sprinkler systems when connected to a public potable water system shall include adequate provision for control, drainage and backflow prevention. (1) If no chemicals are injected into the sprinkler system, minimum protection against backflow shall include an approved BFP-DCV. EXCEPTION: Where sprinkler pipe size does not exceed one (1) inch, and maximum flow rate 25 gpm, an approved BFP-DuC may be used in lieu of the DCV. (2) If chemicals are injected into the sprinkler system, minimum protection shall include an approved BFP-RPZ. Installation and protection of these devices shall be in accordance with Section 1105.4 or this Code. (b) Water from a public system shall not supplied to any lawn sprinkler system until it has been inspected and approved by the Administrative Authority.