Sec. 3-83. - Transformers for outline lighting exceeding six hundred volts; requirements.

(a) Transformers shall comply with the following: (1) Voltage. The transformer secondary open-circuit voltage shall not exceed fifteen thousand (15,000) volts, with an allowance on test of one thousand (1,000) volts additional. In end-grounded transformers, the secondary, open-circuit voltage shall not exceed seven thousand five hundred (7,500) volts, with an allowance on test of five hundred (500) volts additional. (2) Type. Transformers shall be of type approved for the purpose and shall be limited in rating to a maximum of four thousand five hundred (4,500) volt-amperes. Open core-and-coil type transformers shall be limited to four thousand (4,000) volts, with an allowance on test of five hundred (500) volts. Transformers for outline lighting installations shall have secondary current ratings not in excess of thirty (30) milliampere, unless they and all wiring connected to them are installed in accordance with the provisions for electrical discharge lighting of the same voltage. (3) Exposure to Weather. Transformers used outdoors shall be of the weatherproof type or shall be enclosed in a separate metal box. (4) Secondary Connections. The high-voltage windings of transformers shall not be connected in parallel, and shall not be connected in series, except two (2) transformers, each having one (1) end of its high-voltage winding connected to the metal enclosure in series to form the equivalent of a midpoint grounded transformer. The grounded ends shall be connected by insulated conductors not smaller than No. 14; and (5) Accessibility. Transformers shall be accessible.

(Code 1962, § 21-21)

Ask a question about South Bend law

Corpus searches the South Bend sections it holds and shows the ones that match, with their citations. Free, no sign-in.