§ 3-87 — Enclosures for outline lighting in excess of six hundred volts
Code of Ordinances of the City of South Bend, Indiana (Codified through Ordinance No. 11254-26, enacted February 9, 2026 (Supp. No. 65)) · South Bend Code of Ordinances § 3-87
Corpus is an independent public-information project, not the official City of South Bend website. Stable reference: corpuslaw.us/code/105e9280-89f8-47c0-abd3-d8824ced6524
Sec. 3-87. - Enclosures for outline lighting in excess of six hundred volts.
(a) Enclosures for outline lighting shall conform to the following: (1) Conductors and Terminals. Cabinets and outline troughs shall have conductors and terminals, except the supply leads enclosed; (2) Cutouts, Flashers, etc. Cutouts, flashers and similar devices shall be enclosed in metal boxes, the doors of which shall be arranged so that they can be opened without removing obstructions or finished parts of the enclosure; (3) Enclosures Exposed to Weather. Enclosures for outside use shall be waterproof and shall have an ample number of drain holes, each not larger than one-half (½) of an inch or smaller than one-fourth (¼) of an inch; (4) Material. Outline lighting shall be constructed of metal or other noncombustible material; (5) Strength. Enclosures shall have ample strength and rigidity; (6) Thickness of Metal. Sheet copper shall be at least twenty (20) ounce, twenty eight hundredths (.028) of an inch. Sheet steel may be of No. 28 USS gauge, one hundred and forty-nine thousands (.0149) of an inch; except, that for outline lighting, sheet steel shall be of No. 24 USS gauge two hundred and thirty-nine thousands (.0239) of an inch, unless ribbed, corrugated or embossed over its entire surface, when it may be of No. 26 USS gauge, one hundred and seventy-nine thousands (.0179) of an inch.
(Code 1962, § 21-21)
Ask a question about South Bend law
Corpus searches the South Bend sections it holds and shows the ones that match, with their citations. Free, no sign-in.