§ 8-9-147 — Venting of hoistways; exceptions

2019 Detroit City Code (Supp. No. 4: codified through Ordinance No. 2024-17, effective March 26, 2024, and Ordinance No. 2024-32, effective June 25, 2024) · Detroit City Code § 8-9-147

Corpus is an independent public-information project, not the official City of Detroit website. Stable reference: corpuslaw.us/code/29c79320-6342-4709-b2bd-69a0f8b40cd8

Sec. 8-9-147. - Venting of hoistways; exceptions.

Hoistways of elevators, new or altered construction, that serve more than three floors above or below grade, or more than 36 feet of rise, shall be furnished with the means to vent smoke and hot gases into the outer air in the event of fire, provided, that for occupancies of other than Use-Groups R-1, R-2, I-1, I-2 and similar occupancies with overnight sleeping quarters, venting of the hoistway is not required where the building is equipped throughout with approved sprinkler heads that are installed at the top of the hoistway.

(Code 1984, § 7.4.1; Ord. No. 03-97, § 1(7.4.1), eff. 3-10-1997)