Sec. 8-9-157. - Electrical requirements.
(a) All electrical equipment and wiring for lighting of the elevator machine room, machinery space, control room, hoistway and pit, including the main line disconnect switch located in the elevator machine room or control room, shall be installed in accordance with the requirements of Chapter 8, Article III, of the 2019 Detroit City Code, Electrical Code, Section 2.26 of the ASME Code, and this article. (b) Main line disconnect means for new and altered elevators shall be an enclosed externally operable fused circuit switch, heavy-duty type and feature a dual cover interlock, or a circuit breaker capable of being locked in the open position. (c) Where circuit breakers are used as a disconnecting means, they shall not be opened automatically by a fire alarm system. (d) Where there is more than one driving machine, the disconnect switches or circuit breakers shall be numbered to correspond to the number of the driving machine which it controls in accordance with Section 2.29 of the ASME Code. (e) Conductors and optical fibers, including low-voltage signal equipment applications, that are located in hoistways, machine rooms, machinery space, control rooms, or control spaces in or on a car, excluding traveling cables that connect the car and hoistway wiring, shall be installed in rigid metal conduit, intermediate metal conduit, electrical metallic tubing, rigid non-metallic conduit, or wireways, or shall be Type MC, MI, or AC cable.
Ask a question about Detroit law
Corpus searches the Detroit sections it holds and shows the ones that match, with their citations. Free, no sign-in.