Sec. 8-9-152. - Protection of hydraulic cylinders and piping; additional requirements.

In addition to the requirements of Section 3.18.3.8 of the ASME Code: (1) Where hydraulic cylinders are buried underground, a protective coating acceptable to the Department shall be applied or a monitored cathodic protection system shall be installed that detects corrosion from galvanic or electrolytic action, salt water, or other underground conditions; (2) No new hydraulic elevator installation shall incorporate buried piping except by specific permission from of the Department. Existing buried hydraulic piping may remain until replaced, at which time the replacement piping shall not be buried except with the specific permission of the Department; (3) Prior to insertion of the hydraulic cylinder into the ground, the Department shall be notified that the hydraulic system is ready for inspection of the protective-coating or the monitoring cathodic protection system. It shall be unlawful to bury the hydraulic elevator components specified herein until the hydraulic system has been inspected as provided for by this section and accepted by the Department; (4) An outer cylinder casing is required on a new hydraulic elevator or where a cylinder is being replaced. This casing shall be made from not less than schedule 30 PVC or steel pipe three-eighths of an inch in thickness. A glued cap or an expandable type concrete plug shall be poured into the bottom of a casing or a welded plate closer. A dry casing shall be provided. Where needed, a dry non-conductive material shall be provided between the cylinder and casing to secure position of the cylinder. When using a pressurized casing system, the system shall be air tight and maintain a pressure not to exceed 30 PSIG during inspection; (5) Hydraulic elevators shall have all exposed horizontal runs of supply piping outside the elevator machine room enclosure protected by a substantial metal guard or shield of not less than one-eighth inch in thickness; and (6) Oil line supports shall be provided to eliminate stress at joints and fittings.

(Code 1964, § 7.7; Code 1984, § 7.7; Ord. No. 307-H, § 1(7.7), eff. 3-2-1979; Ord. No. 02-87, § 1(7.7), eff. 2-20-1987; Ord. No. 03-97, § 1(7.7), eff. 3-10-1997)

Ask a question about Detroit law

Corpus searches the Detroit sections it holds and shows the ones that match, with their citations. Free, no sign-in.