Sec. 8-9-158. - Operating devices and controls; electrical protective devices.
Electrical protective devices shall be provided in accordance with the following: (1) Slack-rope switch. Winding drum machines shall be provided with a slack-rope device equipped with a slack-rope switch of the enclosed manually reset type which shall cause the electric power to be removed from the elevator driving machine motor and brake where any hoisting rope becomes slack. (2) Motor-generator running switch. Where generator-field control is used, means shall be provided to prevent the application of power to the elevator driving machine motor and brake unless the motor generator set connections are properly switched for the running condition of the elevator. It is not required that the electrical connections between the elevator driving machine motor and the generator be opened in order to remove power from the elevator. (3) Compensating-rope sheave switch. Compensating-rope sheave shall be provided with a compensating-rope sheave switch or switches mechanically opened by the compensating-rope sheave before the sheave reaches its upper or lower limit of travel to cause the electric power to be removed from the elevator driving machine motor and brake. (4) Motor field sensing means. Where direct current is supplied to an elevator armature and shunt field or a driving machine motor, a motor field current sensing means shall be provided, which shall cause the electric power to be removed from the motor armature and brake unless current is flowing in the shunt field of the motor, except for static control elevators provided with a device to detect an overspeed condition prior to, and independent of, the operation of the governor overspeed switch. This device shall cause the power to be removed from the elevator driving machine motor armature and machine brake. (5) Emergency signaling device. An audible signaling device shall be provided and operable from the emergency stop switch and from a switch or button identified as "ALARM", which shall be provided in or adjacent to each car's operating panel in accordance with Section 8-9-192 of this Code. (6) Emergency stop switch. On all elevators, an emergency stop switch shall be provided in the car. Emergency stop switches shall be located in or adjacent to each car operating panel. When opened, the stop switch shall cause the electrical power to be removed from the elevator driving-machine motor and brake. In addition, the emergency stop switch shall: a. Be of the manually opened and closed type; b. Have red operating handles or buttons; c. Be conspicuously and permanently marked "STOP" and indicate the stop and run positions; d. Be positively opened mechanically and its opening not solely dependent on springs; e. Have push/pull type switch that is arranged to operate: push to run, pull to stop; and f. Be an audible signal device. (7) Broken rope, tape, or chain switches used in connection with machine room normal terminal stopping switches. Broken rope, tape, or chain switches, conforming to the requirements of Section 2.26.2.6 of the ASME Code, shall be provided in connection with normal terminal stopping devices located in machine rooms or traction elevators. Such switches shall be opened by a failure of the rope, tape, or chain. (8) Stop switch in pit. A stop switch, conforming to the requirements of Section 2.26.2.5 of the ASME Code, shall be provided in the pit of every elevator. See Section 2.26.2.7 of the ASME Code. (9) Stop switch on top of car. A stop switch, conforming to the requirements of Section 2.26.2.28 of the ASME Code, shall be provided on the top of every elevator car. (10) Car-safety mechanism switch. A switch, conforming to the requirements of Section 2.17.7 of the ASME Code, shall be required where a car safety is provided. (11) Governor overspeed switch. A governor overspeed switch shall be provided when required by Section 2.18.4 of the ASME Code. (12) Final terminal stopping devices. Final terminal stopping devices, conforming to the requirements of Section 2.25.3 of the ASME Code, shall be provided for every electric elevator. (13) Emergency terminal speed limiting devices. Where reduced stroke oil buffers are provided, as permitted by Section 2.22.4.1.2 of the ASME Code, emergency terminal speed limiting devices conforming to the requirements of Section 2.25.4.1 of the ASME Code shall be provided. (14) Buffer switches for oil buffers used with Type C car safeties. Oil-level and compression switches, conforming to the requirements of Sections 2.17.8.2.7 and 2.17.8.2.8 of the ASME Code shall be provided for all oil buffers used with Type C safeties. See 2.17.5.3 of the ASME Code. (15) Hoistway-door interlocks or hoistway-door electric contacts. Hoistway-door interlocks or hoistway-door electric contacts, conforming to the requirements of Section 2.102 of the ASME Code, shall be provided for all elevators. (16) Car-door or gate electric contacts. Car-door or gate electric contacts, conforming to the requirements of Section 2.14.4.2 of the ASME Code, shall be provided for all elevators. (17) Emergency terminal stopping devices. Emergency terminal stopping devices, conforming to the requirements of Section 2.25.4.2 of the ASME Code, shall be provided for all elevators where static control is used unless exempted by Section 2.25.4.2 of the ASME Code. (18) Car side-emergency-exit door contact switches. A car-door electric contact, conforming to the requirements of Section 2.14.1.10.2 of the ASME Code, shall be provided on every car side-emergency-exit door. (19) Motor-generator overspeed protection. Means shall be provided to cause the electric power to be removed automatically from the elevator driving-machine motor and brake should a motor generator set, driven by a direct-current motor, overspeed excessively. (20) Electric contacts for hinged car-platform sills. Hinged car platform sills, where provided, shall be equipped with electric contacts conforming to the requirements of Section 2.15.16 of the ASME Code. (21) In-car stop switch. On passenger elevators, a stop switch, either key operated or behind a locked cover, may be provided in the car and located in or adjacent to the car operating panel. The switch shall be clearly and permanently marked "Stop" and shall indicate the stop and run positions. The switch shall be positively opened mechanically and its opening shall not be solely dependent on springs. When opened, this switch shall cause the electric power to be removed from the elevator driving-machine motor and brake. (22) Buffer switches for gas spring-return oil buffers. Buffer switches, conforming to the requirements of Section 2.22.4.5 of the ASME Code, shall have contacts which are positively opened mechanically and their opening shall not be dependent solely on springs. (23) Stop switch in remote machine and control rooms. A stop switch, conforming to the requirements of Section 2.26.2.5 of the ASME Code, shall be provided in remote machine and control rooms where required by Section 2.7.3.5 of the ASME Code.
Ask a question about Detroit law
Corpus searches the Detroit sections it holds and shows the ones that match, with their citations. Free, no sign-in.